European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-201-IS Issue 1 03-06-2019 Sheet 1 of 8
INSTRUCTION MANUAL
D1xB2X05, D1xB2X10, D1xB2X15 & D1xB2X21 Xenon
Beacons For use in Hazardous Locations
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
DO NOT PAINT
TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, THE FIRST
CONDUIT RUN MUST HAVE A SEALING
FITTING CONNECTED WITHIN 18 INCHES
OF ENCLOSE. SUBSEQUENT CONDUIT
RUNS MUST HAVE A SEALING FITTING
CONNECTED AS CLOSE AS PRACTICAL TO
THE WALL OF THE ENCLOSURE, BUT IN
NO CASE MORE THAN THE SIZE OF THE
CONDUIT OR 50MM, WHICHEVER IS THE
LESSER.
TO PREVENT IGNITION OF GROUP A, B, C
AND D ATMOSPHERES - SEE
INSTRUCTION FOR CHEMICAL
COMPATIBILITY
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON
HUMIDE
HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER
NE PAS PEINTURER
POUR RÉDUIRE LE RISQUE
D'INFLAMMATION DES ATMOSPHÈRES
DANGEREUSES, LE PREMIER CONDUIT
DE CONDUIT DOIVENT AVOIR UN
RACCORD D'ÉTANCHÉITÉ RACCORDÉ À
MOINS DE 18 POUCES DE
L'ENFERMEMENT. POUR SUBSÉQUENT
LES
CONDUITES DE CONDUIT LA
DISTANCE ENTRE LA SURFACE DE LA
MASSE DE REMPLISSAGE AU PLUS PRÈS
DE L’ENVELOPPE DOIT ÊTRE AUSSI
PETITE QUE CE QUI EST RÉALISABLE
MAIS EN AUCUN CAS SUPÉRIEURE À LA
PLUS PETITE DES DIMENSIONS
CORRESPONDANT À LA TAILLE DU
CONDUIT OU À 50 MM.
POUR PRÉVENIR L'INFLAMMATION DES
ATMOSPHÈRES DES GROUPES A, B, C ET
D-VOIR L'INSTRUCTION POUR LA
COMPATIBILITÉ CHIMIQUE
2) Rating & Marking Information
2.1 Fire Alarm Ratings
The Following models are certified as visual alarm devices for
fire alarm use
– private mode only when used with Clear or
Red lens covers:
D1xB2X05DC024 / D1xB2X10DC024 / D1xB2X15DC024 /
D1xB2X21DC024
On-axis light output per UL1638:
Model
Light Intensity in cd
Clear
Lens
Red Lens
D1xB2X05DC024 - 1Hz
20.44
5.89
D1xB2X05DC024 - 1.33Hz
14.47
4.17
D1xB2X05DC024 - 1.5Hz
11.1
2.13
D1xB2X10DC024 - 1Hz
69.81
23.66
D1xB2X10DC024 - 1.33Hz
49.42
16.75
D1xB2X10DC024 - 1.5Hz
35.71
8.57
D1xB2X15DC024 - 1Hz
98.61
31.83
D1xB2X15DC024 - 1.33Hz
69.81
22.53
D1xB2X15DC024 - 1.5Hz
50.44
11.53
D1xB2X21DC024 - 1Hz
215.85
70.74
D1xB2X21DC024 - 1.33Hz
155.12
50.84
D1xB2X21DC024 - 1.5Hz
137.47
45.05
2.2 surge current ratings for use in fire alarm systems
Model
Nominal
Voltage
Voltage
Range
Flash
Rate
Peak
Surge
current
RMS
surge
current
D1xB2X05DC024
24Vdc
20-
28Vdc
1Hz
955mA
370mA
1.33Hz
960mA
370mA
1.5Hz
955mA
365mA
Double
960mA
355mA
D1xB2X10DC024
24Vdc
20-
28Vdc
1Hz
970mA
700mA
1.33Hz
970mA
700mA
1.5Hz
990mA
700mA
Double
990mA
695mA
D1xB2X15DC024
24Vdc
20-
28Vdc
1Hz
990mA
925mA
1.33Hz
990mA
930mA
1.5Hz
990mA
925mA
Double
990mA
905mA
D1xB2X21DC024
24Vdc
20-
28Vdc
1Hz
1590mA
1220mA
1.33Hz
1710mA
1240mA
1.5Hz
1590mA
1240mA
Double
1650mA
1200mA