European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D191-00-201-IS           Issue 1          03-06-2019                         Sheet 1 of 8

 

INSTRUCTION MANUAL 

D1xB2X05, D1xB2X10, D1xB2X15 & D1xB2X21 Xenon 

Beacons For use in Hazardous Locations

 

 

 

 
 
 
 
 
 
 
 
 
 

1)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 HIGH VOLTAGE SHOCK HAZARD. WAIT 5 

MINUTES AFTER REMOVING POWER 
BEFORE OPENING THE ENCLOSURE 

 DO NOT PAINT 

 TO REDUCE THE RISK OF IGNITION OF 

HAZARDOUS ATMOSPHERES, THE FIRST 
CONDUIT RUN MUST HAVE A SEALING 
FITTING CONNECTED WITHIN 18 INCHES 
OF ENCLOSE. SUBSEQUENT CONDUIT 
RUNS MUST HAVE A SEALING FITTING 
CONNECTED AS CLOSE AS PRACTICAL TO 
THE WALL OF THE ENCLOSURE, BUT IN 
NO CASE MORE THAN THE SIZE OF THE 
CONDUIT OR 50MM, WHICHEVER IS THE 
LESSER. 

 TO PREVENT IGNITION OF GROUP A, B, C 

AND D ATMOSPHERES - SEE       
INSTRUCTION FOR CHEMICAL 
COMPATIBILITY 

 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON 
HUMIDE 

 HAUT TENSION, RISK DE CHOC. 

ATTENDEZ 5 MINUTES APRES AVOIR 
DEBRANCHE L’ALIMENTATION AVANT 
D’OUVRIR LA BOITIER 

 NE PAS PEINTURER 

 POUR RÉDUIRE LE RISQUE 

D'INFLAMMATION DES ATMOSPHÈRES 
DANGEREUSES, LE PREMIER CONDUIT 
DE CONDUIT DOIVENT AVOIR UN 
RACCORD D'ÉTANCHÉITÉ RACCORDÉ À 
MOINS DE 18 POUCES DE 
L'ENFERMEMENT. POUR SUBSÉQUENT 
LES

 

CONDUITES DE CONDUIT LA 

DISTANCE ENTRE LA SURFACE DE LA 
MASSE DE REMPLISSAGE AU PLUS PRÈS 
DE L’ENVELOPPE DOIT ÊTRE AUSSI 

PETITE QUE CE QUI EST RÉALISABLE 
MAIS EN AUCUN CAS SUPÉRIEURE À LA 
PLUS PETITE DES DIMENSIONS 
CORRESPONDANT À LA TAILLE DU 
CONDUIT OU À 50 MM. 

 POUR PRÉVENIR L'INFLAMMATION DES 

ATMOSPHÈRES DES GROUPES A, B, C ET 
D-VOIR L'INSTRUCTION POUR LA 
COMPATIBILITÉ CHIMIQUE 

 

2)  Rating & Marking Information 

 

2.1 Fire Alarm Ratings 

 
The Following models are certified as visual alarm devices for 
fire  alarm  use 

– private mode  only  when used with  Clear or 

Red lens covers: 
 
D1xB2X05DC024  /  D1xB2X10DC024  /  D1xB2X15DC024  / 
D1xB2X21DC024 
 
On-axis light output per UL1638: 
 

Model 

Light Intensity in cd 
Clear 
Lens 

Red Lens 

D1xB2X05DC024 - 1Hz 

20.44 

5.89 

D1xB2X05DC024 - 1.33Hz 

14.47 

4.17 

D1xB2X05DC024 - 1.5Hz 

11.1 

2.13 

D1xB2X10DC024 - 1Hz 

69.81 

23.66 

D1xB2X10DC024 - 1.33Hz 

49.42 

16.75 

D1xB2X10DC024 - 1.5Hz 

35.71 

8.57 

D1xB2X15DC024 - 1Hz 

98.61 

31.83 

D1xB2X15DC024 - 1.33Hz 

69.81 

22.53 

D1xB2X15DC024 - 1.5Hz 

50.44 

11.53 

D1xB2X21DC024 - 1Hz 

215.85 

70.74 

D1xB2X21DC024 - 1.33Hz 

155.12 

50.84 

D1xB2X21DC024 - 1.5Hz 

137.47 

45.05 

 
2.2 surge current ratings for use in fire alarm systems 

 
 
 
 

Model

 

Nominal 
Voltage

 

Voltage 
Range

 

Flash 
Rate 

Peak 
Surge 
current

 

RMS 
surge 
current

 

D1xB2X05DC024 

24Vdc 

20-
28Vdc 

1Hz 

955mA 

370mA 

1.33Hz 

960mA 

370mA 

1.5Hz 

955mA 

365mA 

Double 

960mA 

355mA 

D1xB2X10DC024 

24Vdc 

20-
28Vdc 

1Hz 

970mA 

700mA 

1.33Hz 

970mA 

700mA 

1.5Hz 

990mA 

700mA 

Double 

990mA 

695mA 

D1xB2X15DC024 

24Vdc 

20-
28Vdc 

1Hz 

990mA 

925mA 

1.33Hz 

990mA 

930mA 

1.5Hz 

990mA 

925mA 

Double 

990mA 

905mA 

D1xB2X21DC024 

24Vdc 

20-
28Vdc 

1Hz 

1590mA 

1220mA 

1.33Hz 

1710mA 

1240mA 

1.5Hz 

1590mA 

1240mA 

Double 

1650mA 

1200mA 

Содержание D1 B2X05 Series

Страница 1: ...NT AVOIR UN RACCORD D TANCH IT RACCORD MOINS DE 18 POUCES DE L ENFERMEMENT POUR SUBS QUENT LES CONDUITES DE CONDUIT LA DISTANCE ENTRE LA SURFACE DE LA MASSE DE REMPLISSAGE AU PLUS PR S DE L ENVELOPPE...

Страница 2: ...ABCD T4A Ta 55 C to 55 C Class II Div 1 Group EFG T4 Ta 55 C to 40 C Class III Div 1 Ta 55 C to 40 C The D1xB2X21DC024 D1xB2X21DC048 Xenon Beacons are rated as follows Class I Div 1 Group ABCD T3B Ta...

Страница 3: ...Beacons are rated as follows Ex db IIC T3 Ta 55 C to 80 C Ex db IIC T4 Ta 55 C to 65 C Ex tb IIIC T132 C Ta 55 C to 80 C The D1xB2X15AC115 D1xB2X15AC230 Xenon Beacons are rated as follows Ex db IIC T...

Страница 4: ...ent Dust Groupings Group IIIA Combustible Flyings Group IIIB Non conductive Dust Group IIIC Conductive Dust Maximum Surface Temperature for Dust Applications 104 C D1xB2X05DC 116 C D1xB2X05AC 135 c D1...

Страница 5: ...codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training 4 1 Safe Installation Requirements To maintain the ingress protection rating and...

Страница 6: ...aling washer must be fitted under the cable glands or blanking plugs For use in explosive dust atmospheres a minimum ingress protection rating of IP6X must be maintained For use in explosive gas atmos...

Страница 7: ...500 Ohms Minimum Power 2 0W The resistor must be connected directly across the ve and ve terminals as shown in the following drawing Form the resistor legs as shown in Fig 7a fit the resistor across...

Страница 8: ...new lens cover Fig 10 Replacement of beacon lens cover Fit the wire guard back onto the housing over the new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fixings...