background image

 

 

E2S Warning Signals

      Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D210-00-651-IS

 

Issue 1

 

13-01-23

 

 

Sheet 7 of 13

 

 

If a fault is found the SIL 2 unit will go into 

Fault mode

 
If power is disrupted the SIL 2 unit will go into 

Fault mode

, in 

fault mode the Power relay RLY1-1 will close whilst SIL 2 
relay RLY1-2 will become open be circuit between terminals 
1 & 2. 
 

 

 

Fault modes

 - The fault modes listed 15-1 & 15-2 below will 

make the SIL 2 unit change the state for relays RLY1-1 and 
RLY1-2. 
 
In fault mode the Power relay RLY1-1 will close whilst SIL 2 
relay RLY1-2 will become open circuit between terminals 1 & 
2. 
 

15-1 Sounder Failure 
 

 

Tone Failure 

 No Tone detected 

 

Sounder Controller failure 

 No tone generation 

pulse detected 

 

Tone Rate Failure 

 Regular tone cycle erratic 

 

15-2 Power Failure / SIL 2 Failure 
 

 

SIL 2 Controller failure 

 Internal function and 

system checking flags fault 

 

Rapid Power cycling 

 System indicates power 

instability 

 

Total Power Failure  

 
It is possible to reset these faults if they were transitory. 
 
Resetting Failure (by power cycling) - It is possible that the 
SIL 2 unit can be reset by powering the unit off for a period 
greater than 20 seconds. On restarting the unit and running 
through the commissioning cycle the fault may clear. 
 
Resetting Failure (by Hard Reset) - It is possible that the SIL 
2 unit can be reset by hard resetting the unit using the reset 
jumper within the unit (see section 18-4) on hard resetting. 
On restarting the unit and running through the commissioning 
cycle, the fault may clear. It is necessary to run the test 
function cycle again to see if the fault is still evident. 
 
If the hard reset process does not correct the latched fault the 
alarm horn sounder may require further investigation, please 
contact your local E2S representative. 

 
 
 
 
 
 
 
 
 
 
 

Commissioning System - Functional start-up of System 
(Normally in reverse polarity mode) 

 
When Commissioning system the power must not be 

disrupted to the SIL 2 Unit within the unit’s initialization cycle 

which is 

5 seconds

 
Once past this period the SIL 2 system is fully operational 
and will be in monitoring the sounder and power in Standby 
mode. 
 
The relay RLY1-2 on the SIL 2 unit will only remain open for a 
maximum of 1 second on commissioning start-up. RLY1-2 
will subsequently close contacts 1 & 2 indicating healthy 
operation. Contact 1 & 2 will only remain open in the event of 
a fault or a loss of power. 
 

System Testing (Active Mode normal polarity) 

 
The SIL 2 system will remain monitoring the power in standby 
mode until the polarity is changed to normal mode to enable 
an active system for sounder functional testing. 
 

Important

: - The polarity must be held in active mode for a 

period in excess of 

15 seconds

 to ensure a full system check 

is performed. 
 
Once the test period has been completed the unit can be 
switched back to standby mode by reversing the polarity. 
 
If no faults have been found during the test the relays will 
remain in steady state. 
 
The SIL 2 unit will continue to monitor the power and module 
function. 
 

Important

: - The automated test cycle 

must

 be undertaken 

on at least a weekly basis to maintain the SIL 2 units 
reliability. 
 

System Activation (Active Mode normal polarity) 

 
The SIL 2 system will remain monitoring the power in standby 
mode until the polarity is changed to Active mode to enable 
an active system for sounder to function as a warning 
signaling device. 
 

Important

 :- The polarity must be held in active mode for a 

period in excess of 15 seconds to ensure a full system check 
is performed whilst in alarm mode, although it is expected 
that during a system activation this period will be significantly 
greater. 

 

Note

 :- The fault indication signal on TB1 can take up to 50 

milliseconds to indicate system fault. 

 
 
 
 
 
 
 
 
 

Содержание BExS110D-SIL

Страница 1: ...e table shows the input current taken by the various sounders The current levels shown above are for the 440Hz Continuous tone nominal input voltage Nominal current at nominal voltage Table 1 Electric...

Страница 2: ...mixture likely to occur in normal operation Zone 2 Explosive gas air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane...

Страница 3: ...ure and the O ring seal is in place When replacing the flameproof cover casting ensure that it is square with the flameproof chamber casting before inserting Carefully push the cover in place allowing...

Страница 4: ...in the flameproof enclosure See section 7 of this manual for access to the flameproof enclosure Wires having a cross sectional area between 0 5 mm to 2 5mm can be connected to each terminal way If an...

Страница 5: ...pattern generation and signal output checks Default Tone 1 0 0 0 0 0 0 ON 1 OFF 0 Figure 7 DIP switch configuration Refer to D210 95 651 IS Tone Table for tone selection Table 2 below is a summary of...

Страница 6: ...ndby mode and Active mode Health status of power supply Sounder correct function and tone pattern The SIL 2 sounder operates as part of a SIL 2 system The sounder will after commissioning remain power...

Страница 7: ...ase contact your local E2S representative Commissioning System Functional start up of System Normally in reverse polarity mode When Commissioning system the power must not be disrupted to the SIL 2 Un...

Страница 8: ...sounder check on pattern generation and signal output checks Important Only tones use tones that are stated as SIL 2 approved for the SIL 2 application Ensure that the unit is set to one of these tone...

Страница 9: ...he circuit Note a cable short circuit will not be detectable in this configuration For one unit only Sounder power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB1 C...

Страница 10: ...ts and faults occur If multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single alarm horn sounder For more information see manual D197 00...

Страница 11: ...pins 2 3 linked Places power supply terminal Fault resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 13 J2 Header pin positions Fault Resistor FR 18 4 SIL 2 Hard Reset Function Power...

Страница 12: ...sound output despite no input BExS110D SIL Failure to Sound Integrity in respect of failure to release SIL 2 Total Failure rate 0 304 pmh hazardous failure rate revealed 0 233 pmh hazardous failure r...

Страница 13: ...9 k CSR Current Sense Resistor is E 2 7 k EOL End Of Line resistor is F 3 3 k Two digit resistor coding on other units BExS110DFDC024AB1S1R AZ Where the FR Fault Resistor is A 2 2 k EOL End Of Line r...

Страница 14: ...n over 0 5s Continuous 660Hz 1 1 0 0 1 0 2 5 Alternating 554 440Hz at 1Hz 0 0 1 0 1 0 2 5 Intermittent 554Hz at 0 875Hz 1 0 1 0 1 0 2 5 800Hz pulsing at 2Hz 0 1 1 0 1 0 6 5 Sweeping 800 1000Hz at 50Hz...

Страница 15: ...e 1 ve Stage 1 ve For full 4 Wire SIL 2 Connection Monitor SIL 2 ve and SIL 2 ve Terminals 1 2 in RLY1 2 Two or Three Stage Configuration Config 1b Line Monitoring Common Positive Header pins set to n...

Страница 16: ...oup Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIB or IIC T4 Gb II 2G Ex db...

Страница 17: ...are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment including amendment by Directive 2015 863 EU Regulation EC 1907 2006 Registration Evalu...

Страница 18: ...duction process Module D Sira Certification Service Notified Body No 0518 Rake Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the eq...

Страница 19: ...and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Отзывы: