European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. D201-00-031-IS           Issue 1          18-08-16                         Sheet 2 of 7                                                                                            

 

3)  Type Approval Standards

 

 

The hootronic sounder carries an EC Type Examination 
Certificate and IECEx Certificate of Conformity, and have 
been certified to comply with the following standards: 

 

EN60079-0:2012+A11:2013 / IEC60079-0:2011 (Ed 6):  
Explosive Atmospheres - Equipment. General requirements 

 

EN60079-1:2007 / IEC60079-1:2007 (Ed 6):  
Explosive Atmospheres - Equipment protection by flameproof 
enclosures "d" 

 

EN 60079-31:2014 / IEC60079-31:2013 (Ed 2):  
Explosive Atmospheres - Equipment dust ignition protection 
by enclosure "t" 

 

4) Installation 

Requirements

 

 

The hootronic sounder must only be installed by suitably 
qualified personnel in accordance with the latest issues of the 
relevant standards: 

 

EN60079-14 / IEC60079-14: Explosive atmospheres - 
Electrical installations design, selection and erection 

 

EN60079-10-1 / IEC60079-10-1: Explosive atmospheres - 
Classification of areas. Explosive gas atmospheres 

 

EN60079-10-2 / IEC60079-10-2: Explosive atmospheres –  
Classification of areas. Explosive dust atmospheres 

 

The installation of the hootronic sounder must also be in 
accordance with any local codes that may apply and should 
only be carried out by a competent electrical engineer who 
has the necessary training. 

 

5)  Special Conditions of Use 

 

Repair of the flamepath / flameproof joints is not permitted. 

 

The enclosure is non-conducting and may generate an 
ignition-capable level of electrostatic charges under certain 
extreme conditions (such as high-pressure steam). The user 
should ensure that the equipment is not installed in a location 
where it may be subjected to external conditions that might 
cause a build-up of electrostatic charges on non-conducting 
surfaces. 

 

Additionally, cleaning of the equipment should be done only 
with a damp cloth

 

6)  Location and Mounting

 

 

The location of the hootronic sounder should be made with 
due regard to the area over which the warning signal must be 
visible. They should only be fixed to services that can carry 
the weight of the unit. 

 

The BEx hootronic sounder should be secured to any flat 
surface using the three 7mm fixing holes on the stainless 
steel U shaped mounting bracket. See Figure 1. The required 
angle can be achieved by loosening the two large bracket 
screws in the side of the unit, which allow adjustment of the 
hootronic sounder in steps of 18°. On completion of the 
installation then two large bracket adjustment screws on the 
side of the unit must be fully tightened to ensure that the unit 
cannot move in service. 

 

Fig. 1 Fixing Location for Hootronic sounder Flare 

 

Fig. 1 Fixing Location for Hootronic sounder Radial 

 

7)  Access to the Flameproof Enclosure

 

 

 

 

To access the Ex d chamber, remove the four M6 hexagon 
socket head screws and withdraw the flameproof cover taking 
extreme care not to damage the flameproof joints in the 
process. M6 cover screws are Class A4-80 stainless steel 
and only screws of this category can be used for the 
enclosure. 

 

Fig. 2 Accessing the Explosion proof Enclosure. 

 

On completion of the installation, the flameproof joints should 
be inspected to ensure that they are clean and that they have 
not been damaged during installation. 

 

Check that the earth bonding wire between the two castings 
is secure and the ‘O’ ring seal is in place. When replacing the 
flameproof cover casting ensure that it is square with the 
flameproof chamber casting before inserting. Carefully push 
the cover in place allowing time for the air to be expelled. 
Only after the cover is fully in place should the four M6 
Stainless Steel A4-80 cover bolts and their spring washer be 
inserted and tightened down. If the cover jams while it is 
being inserted, carefully remove it and try again. Never use 
the cover bolts to force the cover into position. 

Warning – Hot surfaces. External surfaces 
and internal components may be hot after 
operation, take care when handling the 
equipment. 

Warning – High voltage may be present, 
risk of electric shock. DO NOT open when 
energised, disconnect power before 
opening. 

(Appropriate cable glands 
to be customer supplied)

Flameproof cover  

M6 Cover 
Screws 

M6 Spring 
Washer 

Содержание BExH120D

Страница 1: ...ate No KEMA 99ATEX6312X IECEx KEM 10 0003X The units can be installed in locations with the following conditions Area Classification Gas Zone 1 Explosive gas air mixture likely to occur in normal oper...

Страница 2: ...The location of the hootronic sounder should be made with due regard to the area over which the warning signal must be visible They should only be fixed to services that can carry the weight of the un...

Страница 3: ...topping plugs cannot be fitted onto adapters only directly onto the M20 entries Any other adapters used must be suitably rated and ATEX IECEx certified adapters 10 Earthing Both AC and DC hootronic so...

Страница 4: ...nd N supply terminals see fig 4 12 2 2 AC Units Second and Third Stage Tone Selection To select the second and third stage tones on the BExH120 AC hootronic sounder Stage two S2 Operation Power L and...

Страница 5: ...Header Pins alters stage 2 tone Stage three S3 Operation Power ve and ve link a ve supply line to the S3 terminal Header pins alters stage 3 tone 2 3 S top 1 2 3 S2 S3 Stop ve ve Fig 7 DC Terminals 1...

Страница 6: ...The sounders can then be switched to sound second and third stage alarm sounds The sounds are selected by pin headers on the pcb for both DC and AC units The sound table below shows the pin header pos...

Страница 7: ...y suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosiv...

Отзывы: