E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com D218-00-251-IS Issue 2 01/09/2021
INSTRUCTION & SERVICE MANUAL
AL105NX AlertAlight Combined Sounder Xenon Beacons
floor area covered by the VAD.
maximum length of the sides of the square
mounting height from the floor and y is the
Wall mounted, where x is the maximum
Category W-x-y (Wall mounted):
V=55.3m
³
V=62.5m
³
11W
Power
14W
AL112NXDC024 & AL112NXDC048 LIGHT OUTPUT
Note: CPR aproved units must be
positioned sounder on top,
beacon below.
table are VdS Approved)
(Only units in the following
Coverage Area According to EN54-23
AL112NXDC024
AL112NXDC048
Category W
Unit
W-2.4-4.8
W-2.5-5
x
y
y
AL105NXDC024 & AL105NXDC48 LIGHT OUTPUT
Approved Beacon for EN54-23 Applications:
Clear lenses are compliant with EN54-23
AL105NXDC024
AL105NXDC048
•
All models are approved for use as Audible Signal and Visual Appliance
for use as General Signaling: UL464A & CSA C22.2 No 205-17
•
Type 4 / 4X / 3R / 13, IP66 independently tested to EN60529:1991
•
-
40°C to +66°C / -40°C to +151°F
General Signaling Canada:
AL105NXDC: -40°C to +55°C / -40°F to +131°F
AL105NXAC: -40°C to +40°C / -40°F to +104°F
•
To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
•
Mounting - Units can be mounted using 2 of the 4-off ø7mm holes in the mounting lugs or through the back of the housing using the
supplied gasket.
•
EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve & -ve terminals of the PCBA. Please ensure that the device
legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible
control panel specification for EOL device values and ratings
Model
Nominal
Voltage
Voltage Range
Nominal Operating Current*
Max Operating RMS
#
Beacon
Sounder
Beacon
Sounder
AL105NXDC012
12V dc
11.5-14Vdc
500mA
17mA
531mA
125mA
AL105NXDC024
24V dc
20-28Vdc
250mA
33.5mA
271mA
AL105NXDC048
48V dc
42-52Vdc
170mA
113mA
170mA
AL105NXAC024
24V ac
24-28Vac 50/60Hz
300mA
42.5mA
426mA
42.5mA
AL105NXAC048
48V ac
42-54Vac 50/60Hz
250mA
42mA
360mA
AL105NXAC115
115 Vac
103.5-126.5Vac
50/60Hz
70mA
25mA
101mA
AL105NXAC230
230 Vac
207-253Vac
50/60Hz
35mA
17mA
58mA
*Nominal Voltage, 1Hz Flash Pattern & Tone 12; #Worst-case input voltage and worst case flash pattern
Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70 or CSA 22.1 Canadian Electrical
Code, Part I, Safety Standard for Electrical Installations, Section 32. / L'installation doit exclusivement être réalisée par du personnel qualifié, conformé
ment au code national d'électricité américain, NFPA 70 ou CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux
installations électriques, Section 32