E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH    [email protected]        e2s.com                                            D218-00-251-IS Issue 2 01/09/2021  

 

2821 

S36282 

Construction Product Regulation 

• 

AL105NXDC024 & AL105NXDC048 are compliant to EN54-3:2001+A1+A2 & EN54-23:2010 

• 

VAD for use in fire detection and fire alarm systems installed in and around buildings  

• 

Alarm devices – Sounder & Beacon 

• 

Type 3R / 13, IP66, Independently tested to EN60529:1991, (IP33C Compliant to EN54-3) 

• 

Type B Product, For Indoor & Outdoor use 

• 

Observe Precautions for handling electrostatic devices 

• 

-

25°C to +55°C compliant to EN54-3 & EN54-23 

• 

Cable Glands must be suitably sealed and meet minimum IP33 for EN54-3 applications 

• 

Storage Temperature: -40°C to +70°C 

• 

Maintenance – None 

• 

Units can be mounted using 2-off ø7mm holes or through the back of the housing using the 
supplied gasket 

 

Approved Tones for EN54-3 Applications: 

 

•(Alternating Tone) 800/1000Hz @ 2Hz Alternating Tone 44 

•(Rising Tone) 500/1200Hz @ 0.26Hz (3.3s on, 0.5s off) Tone 8 

•(Fainting Tone) 1200/500Hz @ 1Hz Tone 2 

•(Continuous Tone) 800Hz Tone 21 

•(Pulsed Tone) 660Hz (150mS on, 150mS off) Tone 31 

Order Code: AL105NXDC024 

Voltage Range: 20-28Vdc 

Nominal Voltage: 24Vdc  

Max Sounder Current: P1: 125mA @ 28Vdc  

Max Beacon Current: 271mA @ 20Vdc 

DP-2821-CPR-0109 

21 

2821 

S36282 

21 

Order Code: AL105NXDC048 

Voltage Range: 42-52Vdc 

Nominal Voltage: 48Vdc  

Max Sounder Current: 125mA @ 52Vdc  

Max Beacon Current: 160mA @ 42Vdc 

DP-2821-CPR-0109 

AL105NXDC024 / AL105NXDC048 @ 1m 

 

Horizontal Sound Output Max Voltage 

(60 Vdc) LAFmax,T dB(A) 

Horizontal Sound Output 

Min Voltage (18 Vdc) LAFmax,T dB(A) 

Angle 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 

31 

Tone 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 31 

Tone 5 

15° 

93.9 

94.6 

93.7 

94 

91 

91.8 

90.8 

91.2 

90.5 

90.9 

88 

89.1 

45° 

99.6 

101.4 

100.1 

99.7 

96.6 

98.2 

96.5 

98.3 

96.9 

96.6 

93.5 

95.7 

75° 

102.5 

103.9 

103.5 

102.6 

102 

100.6 

100 

101.1 

100.6 

100.1 

98.7 

98 

105° 

102.5 

103.9 

103.4 

102.7 

102 

100.6 

100 

101.1 

100.6 

100.3 

98.8 

98.2 

135° 

99.5 

101.4 

100.1 

99.7 

96.4 

98.1 

96.4 

98.2 

96.9 

96.6 

93.5 

95.5 

165° 

94.1 

94.8 

93.7 

94.1 

90.6 

91.8 

91.1 

91.5 

90.5 

91.1 

87.6 

89.2 

 

Vertical Sound Output Max Voltage 

(60 Vdc) LAFmax,T dB(A) 

Vertical Sound Output Min Voltage 

(18 Vdc) LAFmax,T dB(A) 

Angle 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 

31 

Tone 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 31 

Tone 5 

15° 

93.8 

94.7 

93.5 

94.3 

90.2 

91.8 

90.7 

91.5 

90.2 

91.2 

87.3 

89.2 

45° 

99.6 

101.4 

100.1 

100 

96.4 

98.3 

96.5 

98.4 

97 

96.9 

93.4 

95.7 

75° 

103 

104.2 

103.7 

103.2 

101.5 

100.6 

99.8 

101.1 

100.5 

100.1 

98.5 

98.1 

105° 

102.6 

104.2 

103.4 

102.6 

101.8 

100.5 

100 

101 

100.6 

100 

99 

98 

135° 

99.5 

101.4 

100.1 

99.8 

96.4 

98.3 

96.3 

98.2 

97 

96.6 

93.5 

95.7 

165° 

94.3 

94.5 

93.6 

94.6 

89.8 

91.6 

91.2 

91.2 

90.4 

91.5 

96.8 

88.8 

The units have been tested and approved to DNVGL-CG-0339 & EN54-3:2014 incl. A1:2019 
for the installation on ships in the following locations: 
Temperature: 

A, B, C & D (Machinery spaces, control rooms, accommodation, 

 

 

bridge, inside cubicles, desks, etc..., pump rooms, holds, rooms 

 

 

with no heating, Open deck, masts) 

Humidity: 

 

A & B (All locations) 

Vibration: 

 

A (Bulkheads, Beams, Deck, Bridge) 

EMC: 

 

A (All locations except Bridge & open deck) 

Enclosure:   

A, B & C, IP66 (Control rooms, accommodation, bridge, engine  

 

 

room, open deck masts, below floor plates in engine room) 

The units comply with Solas 74 Chapter II-2, Regulation 7 & Chapter X, 
Regulation 3 for installation on ships in the following locations: 

Temperature: 

D (Location -25° to +70°C) 

Vibration: 

 

A (General Applications) 

EMC: 

 

A (General Power Distribution Zone) 

Enclosure:   

IP66, Salt mist 

Содержание AlertAlight AL105N Series

Страница 1: ...power source before installation or service to prevent electric shock Attention D branchez le de la source d alimentation avant l installation ou l entretien pour viter tout choc lectrique Achtung Vo...

Страница 2: ...218 00 251 IS Issue 2 01 09 2021 DC See D218 06 201 AC See D218 06 205 A B C E N L E N L S2 S3 S2 S1 S2 S1 N L E E S3 S2 N L Default S2 Tone 1 Default S1 Tone 44 ON 1 OFF 0 AC DC See D221 95 001 A B C...

Страница 3: ...oad Acton London W3 7QH sales e2s com e2s com D218 00 251 IS Issue 2 01 09 2021 INSTRUCTION SERVICE MANUAL AL105NX AlertAlight Combined Sounder Xenon Beacons 6x 1Nm 20mm 145 5 71in 60 3 2 37in 35 92 1...

Страница 4: ...ne 2 Tone 21 Tone 31 Tone 5 15 93 9 94 6 93 7 94 91 91 8 90 8 91 2 90 5 90 9 88 89 1 45 99 6 101 4 100 1 99 7 96 6 98 2 96 5 98 3 96 9 96 6 93 5 95 7 75 102 5 103 9 103 5 102 6 102 100 6 100 101 1 100...

Страница 5: ...off 7mm holes in the mounting lugs or through the back of the housing using the supplied gasket EOL Monitoring DC Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please...

Страница 6: ...orientation Factory finishes are not intended to be modified Attention Installation must be carried out by an electrician in compliance with the National Electrical Code NFPA 70 and the National Fire...

Страница 7: ...2 3 dB A 148 3 dB A 33 3 dB A 153 6 dB A 28 6 dB A 151 5 6 dB A 29 6 dB A 180 87 2 dB A 0 87 dB A 180 87 2 dB A 0 86 4 dB A S2 S3 S2 S1 AL105NXDC024 Sounder PCBA 100 0 L 10 14 VDC AC 20 28 VDC AC 42 5...

Страница 8: ...ING DIAGRAMS NTS 1 WIRING LINKING BEACON SOUNDER FACTORY FITTED 2 R1 R1 S2 S3 R1 S2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM...

Страница 9: ...ve OUT ve OUT R1 R1 S2 R1 S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MIN...

Страница 10: ...SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D218 06 205 R S RAIT B ISARD R N POTTS OF SOUNDER XENON WIRING DI...

Страница 11: ...ATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D218 06 205 R S RAIT B ISARD R N POTTS OF NTS 2 SW...

Страница 12: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Отзывы: