![E2S AlertAlight AL105N Series Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/e2s/alertalight-al105n-series/alertalight-al105n-series_instructions-service-manual_3263383004.webp)
E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com D218-00-251-IS Issue 2 01/09/2021
2821
S36282
Construction Product Regulation
•
AL105NXDC024 & AL105NXDC048 are compliant to EN54-3:2001+A1+A2 & EN54-23:2010
•
VAD for use in fire detection and fire alarm systems installed in and around buildings
•
Alarm devices – Sounder & Beacon
•
Type 3R / 13, IP66, Independently tested to EN60529:1991, (IP33C Compliant to EN54-3)
•
Type B Product, For Indoor & Outdoor use
•
Observe Precautions for handling electrostatic devices
•
-
25°C to +55°C compliant to EN54-3 & EN54-23
•
Cable Glands must be suitably sealed and meet minimum IP33 for EN54-3 applications
•
Storage Temperature: -40°C to +70°C
•
Maintenance – None
•
Units can be mounted using 2-off ø7mm holes or through the back of the housing using the
supplied gasket
Approved Tones for EN54-3 Applications:
•(Alternating Tone) 800/1000Hz @ 2Hz Alternating Tone 44
•(Rising Tone) 500/1200Hz @ 0.26Hz (3.3s on, 0.5s off) Tone 8
•(Fainting Tone) 1200/500Hz @ 1Hz Tone 2
•(Continuous Tone) 800Hz Tone 21
•(Pulsed Tone) 660Hz (150mS on, 150mS off) Tone 31
Order Code: AL105NXDC024
Voltage Range: 20-28Vdc
Nominal Voltage: 24Vdc
Max Sounder Current: P1: 125mA @ 28Vdc
Max Beacon Current: 271mA @ 20Vdc
DP-2821-CPR-0109
21
2821
S36282
21
Order Code: AL105NXDC048
Voltage Range: 42-52Vdc
Nominal Voltage: 48Vdc
Max Sounder Current: 125mA @ 52Vdc
Max Beacon Current: 160mA @ 42Vdc
DP-2821-CPR-0109
AL105NXDC024 / AL105NXDC048 @ 1m
Horizontal Sound Output Max Voltage
(60 Vdc) LAFmax,T dB(A)
Horizontal Sound Output
Min Voltage (18 Vdc) LAFmax,T dB(A)
Angle
Tone
44
Tone
8
Tone
2
Tone
21
Tone
31
Tone
5
Tone
44
Tone
8
Tone
2
Tone
21
Tone 31
Tone 5
15°
93.9
94.6
93.7
94
91
91.8
90.8
91.2
90.5
90.9
88
89.1
45°
99.6
101.4
100.1
99.7
96.6
98.2
96.5
98.3
96.9
96.6
93.5
95.7
75°
102.5
103.9
103.5
102.6
102
100.6
100
101.1
100.6
100.1
98.7
98
105°
102.5
103.9
103.4
102.7
102
100.6
100
101.1
100.6
100.3
98.8
98.2
135°
99.5
101.4
100.1
99.7
96.4
98.1
96.4
98.2
96.9
96.6
93.5
95.5
165°
94.1
94.8
93.7
94.1
90.6
91.8
91.1
91.5
90.5
91.1
87.6
89.2
Vertical Sound Output Max Voltage
(60 Vdc) LAFmax,T dB(A)
Vertical Sound Output Min Voltage
(18 Vdc) LAFmax,T dB(A)
Angle
Tone
44
Tone
8
Tone
2
Tone
21
Tone
31
Tone
5
Tone
44
Tone
8
Tone
2
Tone
21
Tone 31
Tone 5
15°
93.8
94.7
93.5
94.3
90.2
91.8
90.7
91.5
90.2
91.2
87.3
89.2
45°
99.6
101.4
100.1
100
96.4
98.3
96.5
98.4
97
96.9
93.4
95.7
75°
103
104.2
103.7
103.2
101.5
100.6
99.8
101.1
100.5
100.1
98.5
98.1
105°
102.6
104.2
103.4
102.6
101.8
100.5
100
101
100.6
100
99
98
135°
99.5
101.4
100.1
99.8
96.4
98.3
96.3
98.2
97
96.6
93.5
95.7
165°
94.3
94.5
93.6
94.6
89.8
91.6
91.2
91.2
90.4
91.5
96.8
88.8
The units have been tested and approved to DNVGL-CG-0339 & EN54-3:2014 incl. A1:2019
for the installation on ships in the following locations:
Temperature:
A, B, C & D (Machinery spaces, control rooms, accommodation,
bridge, inside cubicles, desks, etc..., pump rooms, holds, rooms
with no heating, Open deck, masts)
Humidity:
A & B (All locations)
Vibration:
A (Bulkheads, Beams, Deck, Bridge)
EMC:
A (All locations except Bridge & open deck)
Enclosure:
A, B & C, IP66 (Control rooms, accommodation, bridge, engine
room, open deck masts, below floor plates in engine room)
The units comply with Solas 74 Chapter II-2, Regulation 7 & Chapter X,
Regulation 3 for installation on ships in the following locations:
Temperature:
D (Location -25° to +70°C)
Vibration:
A (General Applications)
EMC:
A (General Power Distribution Zone)
Enclosure:
IP66, Salt mist