24vdc :  10 - 30vdc

A105N APPELLO

 - Synchronised Voice Annunciation

& 10 Tone Sounder

144,00

130,00

Ø7,00

13

0,

00

13

3,

50

126,00

-

+

T2

Stage 2

For  instructions  relating to  the recording  of the  voice  messages  please see  the A105N  SYNCHRONISED
APPELLO  PROGRAMMER  instructions.

In order  for this  sounder to  remain synchronised  with other  Appello Synchronised  units, the  settings
must  be identical  (with the  exception of  volume) and  they must  be  activated  simultaneously.

DAMAGE WILL  OCCUR  TO  THE  UNIT  IF THE  SUPPLIED  VOLTAGE  IS NOT  W ITHIN THE  LIMITS
SPECIFIED.

TONE  SELECTION.

If a tone is required in addition to the voice message position connectors on pin rows 

T T

 as shown

in the tone table. (Tone 10  is Factory setting).

If a second and/or third stage tone is required there are 3 tones available for each first stage tone.
Position connectors on pin rows 

2

 and 

3

 as shown in the tone table to select one of the 3 tones for

each stage.

MESSAGE  MODE  SELECTION.

The Synchronised Appello offers a choice of 3 message mode options.

Option ‘A’ will play the selected tone, then play the message. The sequence is then repeated.
(Factory  setting)

Option ‘B’ will play the selected tone, followed by the message twice. The sequence is then
repeated.

Option ‘C’ will repeatedly play the message only.

Position connectors on pin row 

M

 to select an option.

VOLUME  CONTROL.

There are 3 levels of volume available. Potentiometer P1 may also be used for further adjustment.

Option ‘A’  :  Maximum 50mA @ 24vdc

Option ‘B’  : Maximum  80mA @ 24vdc (Factory setting)

Option ‘C’  : Maximum 130mA @ 24vdc

Position connectors on pin row 

M H

 to select an option.

Pin row ‘

L

’ is not used.

M

Option 'A'

M

Option 'B'

M

Option 'C'

M

H

M

H

M

H

Option 'A'

Option 'B'

Option 'C'

T2 -

2

Option 'A'

2

Option 'B'

2

Option 'C'

T3 -

3

Option 'A'

3

Option 'B'

3

Option 'C'

T3

Stage 3

Stage 1

Frequency

T2 & T3 Stage Options

Tone

Description

'A'

'B'

'C'

T

Tone 1

420Hz @ 0.625 sec Australian Alert

Tone 5

Tone 8

Tone 4

T
T

Tone 2

500/1200Hz @ 0.3Hz 0.5 sec Slow Whoop

Tone 10

Tone 8 Tone 12

T
T

Tone 3

2400/2900Hz @ 7Hz Sweeping

Tone 8 Tone 14 Tone 10

T
T

Tone 4

500-1200Hz 3.75sec /0.25sec. Australian Evac.

Tone 1

Tone 8

Tone 5

T
T

Tone 5

Bell

Tone 10 Tone 13 Tone 2

T
T

Tone 6

1200/500Hz @ 1Hz - DIN / PFEER P.T.A.P.

Tone 13

Tone 2 Tone 10

T
T

Tone 7

544Hz (100mS)/440Hz (400mS) - NF S 32-001

Tone 10

Tone 5

Tone 9

T
T

Tone 8

1000Hz Continuous - PFEER Toxic Gas

Tone 10 Tone 11 Tone 5

T
T

Tone 9

554Hz Continuous

Tone 5

Tone 7 Tone 12

T
T

Tone 10 800/1000Hz @ 0.25 sec Alternating

Tone 8

Tone 6 Tone 11

T

Tone 11 1000Hz @ 1Hz Intermittent
Tone 12 2400Hz Continuous
Tone 13 800Hz Continuous
Tone 14 2400/2900Hz @ 1Hz Sweeping

T
T
L

M

2
3

Factory  Setting