background image

 - 6 -

4 Accessories

4.1 Description

The ESX10-T features an integral power distribution system. The 

following wiring modes are possible with various pluggable current 

and signal busbars:

• 

LINE +(DC 24 V)

• 

0 V 

 

Caution: The electronic devices ESX10-T require a  

 

0 V connection

• 

signal contacts

• 

reset inputs

4.2 Accessories

Use original E-T-A accessories only!

l

 

Busbars for LINE+ and 0 V 

 

max. load with one line entry

 

(recommended: centre line entry)

 

max. load with two line entries

 

grey insulation, length: 500 mm

 

X 222 611 02

l

 

Busbars for LINE+ and 0 V

 

grey insulation

 

max. number of plug-on operations 10:

 

X 222 611 22 

 

(2-unit-block ESX10-T), length: 22 mm

 

X 222 611 34

 

(3-unit-block ESX10-T), length: 34.5 mm

 

X 222 611 47,

 

(4-unit-block ESX10-T), length: 47 mm

 

X 222 611 59

 

(5-unit-block ESX10-T), length: 59.5 mm 

 

 

X 222 611 72

 

(6-unit-block ESX10-T), length: 72 mm

 

X 222 611 97

 

(8-unit-block ESX10-T), length: 97 mm

 

X 222 611 12

 

(10-unit-block ESX10-T), length: 122 mm

l

 

Signal busbars for signal contacts and reset inputs

 

suitable for signal busbar ESX10-TB-...

 

max. load with one line entry

 

with one series connection of signal contacts    Imax 

 

grey insulation, length: 500 mm

 

X 222 005 03

 

l

 

Jumpers for signal contacts

 

suitable for jumper ESX10-TB-...

 

grey insulation, length: 21 mm

 

X 222 005 13    

 

l

 

Insulated wire bridge

 

optional as jumper for ESX10-TB-101...

 

for group signalisation (series connection)

 

X 223 108 01

l

 

Connector bus link –K10

 

suitable for auxiliary contacts (series connection)

 

X 210 589 02  (1.5 mm2, brown) 

3  Informationen on UL-approvals/
 CSA-approvals

ESX10-TA / -TB

UL2367

Non-hazardous use 

UL File # E306740

UL 508

Non-hazardous use 

UL File # E322549

E322549 

INDUSTRIAL CONTROL EQUIPMENT

ESX10-TA / -TB

 

ISA 12.12.01-2015

UL File # E320024 

Operating Temperature Code T4

-   This equipment is suitable for use in Class 

, Division 2,  

Groups A, B, C and D or non-hazardous locations only. T4 A / 0 

°C to 50 °C

WARNING:

-   Exposure to some chemicals may degrade the sealing properties 

  of materials used in the following device: relay (K1)

  Sealant Material:

   

Generic Name:  Modified diglycidyl ether of bisphenol A

   

Supplier: 

Fine Polymers Corporation

   

Type: 

Epi Fine 4616L-160PK

  Casing Material:

   

Generic Name:  Liquid Crystal Polymer

   

Supplier: 

Sumitomo Chemical

   

Type: 

E4008, E4009, or E6008

 

RECOMMENDATION:

-  Periodically inspect the device named above for any degradation 

  of properties and replace if degradation is found

WARNING – EXPLOSION HAZARD:

AVERTISSEMENT – RISQUE D’EXPLOSION

-    Do not disconnect equipment unless power has been removed or the 

area is known to be non-hazardous.

-   Avant de deconnecter l’equipment, couper le courant ou s’assurer 

que l’emplacement est designe non dangereux.

-   Substitution of any components may impair suitability for Class 

,     

Division 2.

La substitution de composants peut rendre ce materiel inacceptable 

pour les emplacements de class 

, division 2.

This device is OPEN type equipment that must be used within a suitable 

end-use system enclosure, the interior of which is accessible only 

through the use of a tool. The suitability of the enclosure is subject 

to investigation by the local Authority Having Jurisdiction at the time 

of installation.

Wiring to or from this device, which enters or leaves the system enclosu-

re, must utilize wiring methods suitable for Class 

, Division 2 Hazardous 

Locations, as appropriate for the installation.

 

ESX10-TA / -TB

 

CSA C22.2 No: 14 -   File # 016186

 

CSA C22.2 No: 142 -  File # 016186

 

CSA C22.2 No: 213  

 (Class 

, Division 2) -  File # 016186

Class 2

Meets requirement for Class 2 current limitation

(ESX10-T...-0.5 A / 1 A / 2 A / 3 A)

Содержание ESX10-TA-DC 24 V

Страница 1: ...P 54 is achieved after installation in a UV protected fully enclosed room control cabinet IEC EN60079 0 and IEC EN 60079 14 have be observed for installation Safety This device is not protected agains...

Страница 2: ...rcuit external free wheeling diode recommended with inductive load Several load outputs must not be connected in parallel Status output SF ESX10 T 114 124 127 Electrical data plus switching signal out...

Страница 3: ...ESX10 TB 6 A l Electronic current limitation ILimit occurs at typically 1 8 x IN which means that under all overload conditions independent of the power supply and the resistance of the load circuit t...

Страница 4: ...0 TB 124 Load Load Load 22 1 LINE RE SF 23 22 1 LINE RE SF 23 22 1 LINE RE SF 23 Reset button 3 0V 3 0V 3 0V 24 V 0 V 0 5 A ESX10 TA 100 1 LINE 1 LINE 1 LINE 1 LINE 2 LOAD 2 LOAD 2 LOAD 2 LOAD 3 0V 3...

Страница 5: ...or jumper X22200513 grey remove protection against brush contact from bottom side 12 5 x n 3 length of busbars 0 5 e g 12 5 x 5 3 59 5 0 5 insert protection against brush contact continuous busbar 50...

Страница 6: ...MENT ESX10 TA TB ISA 12 12 01 2015 UL File E320024 Operating Temperature Code T4 This equipment is suitable for use in Class Division 2 Groups A B C and D or non hazardous locations only T4 A 0 C to 5...

Страница 7: ...7...

Страница 8: ...nly In the interest of improved design performance and cost effectiveness the right to make changes in these specifications without notice is reserved Product markings may not be exactly as the orderi...

Отзывы: