Instruction Manual

Electronic Circuit Protector ESX10-TA/-TB-DC 24 V

Warning

This device is only suitable for operation at 24 VDC (safety 

extra-low voltage). Direct connection of this device to a 110 V, 

230 V or 400 V power system, or to power systems with a higher 

voltage, may consequently result in death, severe personal injury 

or substantial property damage. Only qualified personnel should 

work on or around this equipment. The product will function 

correctly and safely only if it is transported, stored, set up and 

installed as intended.

Caution

Electrostatic sensitive devices (ESD) – the device must be opened 

only by the manufacturer.

Disposal guideline

Packaging and packing aids can be recycled and should always 

be returned to use.

Note

More detailed information can be obtained from local E-T-A subsidiaries 

or from the homepage www.e-t-a.de. The product is subject to techni-

cal modifications. In case of doubt the German text takes precedence.

If used under Ex conditions, this device must only be actuated of the 

immediate environment is verifiably not classified as a hazardous area.

Automatic start-up of machinery after shut down must be prevented (Ma-

chinery Directive 2006/42/EG and EN 60204-1). In the event of a short 

circuit or overload the load circuit will be disconnected electronically by 

the ESX10-TA-/TB.

Installation instructions

The type ESX10-TA-/TB can be snapped onto symmetrical rail EN 60715. 

Please observe the marking of the ESX10-T signal inputs and outputs, 

connection diagrams etc. Before power up the cables have to marked 

so as to prevent reverse polarity. The user should ensure that the cable 

cross sections of the relevant load circuit are suitable for the current ra-

ting of the ESX10-T used. In the event of Ex applications it has to be 

ensured that protection class IP 54 is achieved after installation in a UV-

protected, fully enclosed room / control cabinet. IEC/EN60079-0 and IEC/

EN 60079-14 have be observed for installation.

Safety

This device is not protected against reversed polarity of the input 

voltage. It has to be protected against overvoltage > 32 V. 

Danger of explosion: Incorrect connection of cables can cause 

ignition. The output and the device are protected by an internal, 

non-exchangeable blade fuse. Use in aggressive mixed media was 

not tested. When mounted side-by-side without convection, the 

devices should not carry more than 80 % of its rated load with  

100 % ON duty due to thermal effects. 

Table

Specifications:

Current rating (A)

0.5

1

2

3

4

6

8

10

12

Max. load (A)

0.5

1

2

3

4

5

7

9

10.8

Protection class

to EN60529

housing IP20, terminals IP20

EMC

emitted interference to EN 61000-6-3

noise immunity to EN 61000-6-2

Insulation  

coordination

0.5 kV / pollution degree 2, re-inforced  

insulation in operating area to 

IEC60934 / IEC60664

CE logo

to 2014/30/EU and 2014/34/EU

UL

UL 2367, File # E306740

Solid State Overcurrent Protectors

UL 508, File # E322549  

Industrial Control Equipment

ISA 12.12.01-2015, File # E320024 

CSA

CSA C22.2 No: 14 File # 016186

CSA C22.2 No: 142 File # 016186 

 

CSA C22.2 No: 213 

ATEX

IEC/EN60079-0 /-14/-15

 II 3G  Ex nA II B T4 Gc X

!

Type No.

ESX10

  Electronic Circuit Protector, with current limitation

 

Mounting and design

 

TA

  rail mounting, without signal contact

 

TB

   rail mounting, with aux. contact and hole for signal  

busbars/jumpers

  

Version

  

1

  standard, without physical isolation

 

 

  

Signal input

 

  

0

  without signal input

 

  

1

  with control input IN+ (only ESX10-T.-114)

 

  

2

  with reset input RE (only ESX10-T.-124,  

 

   

ESX10-T.-127)

 

     

Signal outputs

 

   

0

 

without signal output (only ESX10-TA) 

 

   

1

 

signal contact N/O

 

   

2

 

signal contact N/C   

 

   

4

 

status output SF (only ESX10-T.-114,  

 

    ESX10-T.-124)

 

   

7

 

inverse status output SF (only ESX10-T.-127)

 

     

Operating voltage

 

     

DC 24 V

 rated voltage DC 24 V  

 

      

Current rating

 

      

0.5...12 A

 

      

  Approvals

 

      

  E 

ATEX

ESX10 -TB-1   0  1-DC 24 V-6 A

 

-E

  Ordering information

Ordering information

Содержание ESX10-TA-DC 24 V

Страница 1: ...P 54 is achieved after installation in a UV protected fully enclosed room control cabinet IEC EN60079 0 and IEC EN 60079 14 have be observed for installation Safety This device is not protected agains...

Страница 2: ...rcuit external free wheeling diode recommended with inductive load Several load outputs must not be connected in parallel Status output SF ESX10 T 114 124 127 Electrical data plus switching signal out...

Страница 3: ...ESX10 TB 6 A l Electronic current limitation ILimit occurs at typically 1 8 x IN which means that under all overload conditions independent of the power supply and the resistance of the load circuit t...

Страница 4: ...0 TB 124 Load Load Load 22 1 LINE RE SF 23 22 1 LINE RE SF 23 22 1 LINE RE SF 23 Reset button 3 0V 3 0V 3 0V 24 V 0 V 0 5 A ESX10 TA 100 1 LINE 1 LINE 1 LINE 1 LINE 2 LOAD 2 LOAD 2 LOAD 2 LOAD 3 0V 3...

Страница 5: ...or jumper X22200513 grey remove protection against brush contact from bottom side 12 5 x n 3 length of busbars 0 5 e g 12 5 x 5 3 59 5 0 5 insert protection against brush contact continuous busbar 50...

Страница 6: ...MENT ESX10 TA TB ISA 12 12 01 2015 UL File E320024 Operating Temperature Code T4 This equipment is suitable for use in Class Division 2 Groups A B C and D or non hazardous locations only T4 A 0 C to 5...

Страница 7: ...7...

Страница 8: ...nly In the interest of improved design performance and cost effectiveness the right to make changes in these specifications without notice is reserved Product markings may not be exactly as the orderi...

Отзывы: