Electronic Circuit Protector ESX10-T.-DC 24 V
1822
5
4
Electronic Circuit Protector ESX10-T.-DC 24 V
Table 2: ESX10-T – product versions
Version
Signal input
Signal output
Signal output F (signal contact)
Status output SF
ESX10-..
w/o
control input
ON/OFF +24 V
Control IN+
reset input
+24 V
RE
w/o
single signal
make contact
(normally
open NO)
single signal
break
contact
(normally
closed NC)
w/o
status OUT
+24 V = OK
status OUT
0 V = OK
-TA
-100
x
–
–
x
–
–
x
–
–
-TB/-TD
-101
x
–
–
–
x
–
x
–
–
-TB/-TD
-102
x
–
–
–
–
x
x
–
–
-TB/-TD
-114
–
x
–
–
–
–
–
x
–
-TB/-TD
-124
–
–
x
x
–
–
–
x
–
-TB/-TD
-127
–
–
x
x
–
–
–
–
x
Connection diagram ESX10-TB-6A (example)
Elect
ro
nic Cir
cuit Pr
otector
ESX10-TB-101-DC24V
-6A
13
14
GERMANY
TB-101
13
14
ok
r
e
s
e
t
on
off
6A
2 LOAD+
LINE+
1
14
13
2
LOAD+
0V
3
Table 1: Voltage drop, current limitation, max. load current
current
rating I
N
typical
voltage
drop
U
ON
at I
N
active
current
limitation
I
Limit
(typ-
ically)
max. load current at 100% ON
duty, U
B
DC 24 V
T
amb
= 40 °C T
U
= 50 °C
T
amb
= 60 °C
0.5 A
70 mV
1,8 x IN
0.5 A
0.5 A
0.5 A
1 A
80 mV
1,8 x IN
1 A
1 A
1 A
2 A
130 mV
1,8 x IN
2 A
2 A
2 A
3 A
80 mV
1,8 x IN
3 A
3 A
3 A
4 A
100 mV
1,8 x IN
4 A
4 A
4 A
6 A
130 mV
1,8 x IN
6 A
6 A
6 A
8 A
120 mV
1,5 x IN
8 A
8 A
8 A
10 A
150 mV
1.5 x IN
10 A
10 A
9.8 A
12 A
180 mV
1.3 x IN
12 A
11 A
9.8 A
[0.5/1/2
A]
70/80/
130 mV
1.4 x IN
0,5/1/2 A
0,5/1/2 A
0.5A/1A/2A
[2/3/4 A]
130/80/
100 mV
1.4 x IN
2/3/4 A
2/3/4 A
2A/3A/4A
[2/4/6 A]
130/100/
130 mV
1.4 x IN
2/4/6 A
2/4/6 A
2A/4A/6A
[6/8/10
A]
130/120/
150 mV
1.4 x IN
6/8/10 A
6/8/10 A
6A/8A/9.8A
Note:
When mounted side-by-side without convection, the devices can
only carry max. 80 % of their rated current continuously (100 % ON
duty) due to the thermal effect.
Notes
l
The user has to ensure that the cable cross section of the load
circuit in question complies with the current rating of the ESX10-T
used.
l
In addition special precautions have to be taken in the system or
machinery to exclude automatic re-start (e.g. by using a safety PLC)
(cf. Machinery Directive 2006/42/EG und EN 60204-1, Safety of
Machinery). In the event of a failure (short circuit/overload) the load
circuit will be disconnected electronically by the ESX10-T.