11. Attach the vent pipe extension with the 2” vent coupling, bringing the vent well above grade.

12. Clean all dirt and debris from top four corrugations on tank. Install the 24” coupler O-ring on the tank 

between the top two corrugations with the white or yellow line facing out and on top.

13. Lube extension coupler and coupler O-ring with pipe lube or dish soap.

14. Manually press coupling evenly over lubricated O-ring. If additional force is needed, place a plywood 

cover over the accessway and apply gentle mechanical pressure to the coupler. 

Note: Care must be used 

when pushing down on the coupler. Excessive force or impact may result in damage and leakage.

15. Frequent visual inspections during installation must be performed to determine when the tank has fully 

engage the coupler.

INSTALL REPLACEMENT COVER ASSEMBLY

 (Fig. 10)

16. Clean top corrugation on accessway extension and 

mating surface of replacement shroud with acetone.  

17. Liberally apply the silicone sealer provided to the 

under side of the replacement shroud where it will come in 

contact with the accessway extension.  

18. Lube wet well vent grommet and vent pipe extension 

with pipe lube, non-grit hand cleaner or dish soap and 

slide vent pipe through grommet until tank shroud seats to 

accessway.

19. Place SS band clamp around top corrugation and the 

replacement shroud. Tap with a mallet around clamp to help 

seat the clamp. Torque stud assembly on band clamp to a 

maximum 125 inlb. 

20. Reinstall the supply cable, EQD**, tank lid and 

electrical shroud and tighten cable connector. (**See “EQD 

wiring order,” Table 1)

21. Follow start-up procedures to ensure proper pump operation (you will 

find the start-up instructions in our service manual or the station installation 

instruction guide).

 

PIN # 

COLOR

 1 

Brown 

 2 

Red 

 3 

Black 

 4 

Grn/Yellow

 5 

Yellow

 6 

Blue 

**EQD wiring order

Table 1

NOTE: IF EXISTING 

ACCESSWAY HAS ONLY 2 

CORRUGATIONS

 (Fig. 11)

- If the coupler will not 

engage completely because the 

discharge piping is in the way, 

and it doesn’t have a cut out, 

you will need to cut a slot in the 

coupler.

- Using a hand, reciprocating 

or hole saw, cut an arch in the 

coupler; the cut-out is not to 

exceed 5.50” tall or 5.00” wide.

Figure 11

Figure 12

   

  

Table 2

Figure 10

NC0028

DESCRIPTION 

PART NO.

Simplex station 

NC0022G15

Simplex, flood plain config 

NC0022G16

Duplex station 

NC0022G17

Duplex, flood plain config 

NC0022G18

Содержание Extreme Series

Страница 1: ...1 DH272 DR272 DH502 DR502 Typical Installation Instructions Warranty Information Duplex Stations 270 Gal 500 Gal Capacities...

Страница 2: ...M grommet 4 5 ID For DWV pipe 8 WET WELL VENT 2 0 tank vent supplied by factory in units with accessways 9 GRAVITY SERVICE LINE 4 DWV 4 5 OD Supplied by others 9a STUB OUT 4 X 5 Long watertight stub o...

Страница 3: ...3 FAILURE TO COMPLY WITH INSTALLATION INSTRUCTIONS WILL VOID WARRANTY SEAL CONDUIT PER NEC SECTION 300 5 300 7 Figure 1a...

Страница 4: ...r level then the inlet the inlet must be sleeved with an 8 tube before pouring If your unit is a model taller than 93 it may be shipped in two sections requiring field assembly See Field Joint Assembl...

Страница 5: ...The units are supplied with a vent pipe from the wetwell to the top of the accessway Failure to properly vent the tank will result in faulty operation and will void the warranty 7 ELECTRICAL CONNECTIO...

Страница 6: ...de of the station reaching down into the burial depth Attach the small fiberglass guard protective shroud provided with the station to protect the exposed cable where it enters the station Four self t...

Страница 7: ...T260 panels Reset is not required Protect Panel Turn pump and alarm breakers off and back on simultaneously Protect Plus Panels Perform a cold start from the Initialize System menu Any user setting th...

Страница 8: ...tank making sure to align the vent port in the lid with the vent pipe in the tank Once aligned lower the upper section onto the mating flange using the three bolts to guide it to the proper position...

Страница 9: ...t to be poured in place If the concrete anchor is to be poured while the station is in place lift the unit by securing straps to the eyebolts supplied on the lower flange as shown below Keep station o...

Страница 10: ...onsulting engineer must revise the calculations as shown in this document Physical Constants 1 Density of Water 62 4 lb cu ft 2 Density of Concrete 150 lb cu ft in air 3 Density of Concrete 87 6 lb cu...

Страница 11: ...e net buoyant force acting on the station Fnet buoyant is equal to the buoyant force Fbuoyant minus the weight of the grinder pump station Fnet buoyant 2870 4 lb 705 lb 2165 4 lb B Ballast Force 1 Det...

Страница 12: ...Force Buoyant Force 5973 0 lb 2165 4 lb 3807 6 lb The approach outlined above may be used to calculate the ballast requirements listed below Chart 1 Station Height in Wetwell Volume cu ft FNet Buoyant...

Страница 13: ...13...

Страница 14: ...onsulting engineer must revise the calculations as shown in this document Physical Constants 1 Density of Water 62 4 lb cu ft 2 Density of Concrete 150 lb cu ft in air 3 Density of Concrete 87 6 lb cu...

Страница 15: ...et buoyant force acting on the station Fnet buoyant is equal to the buoyant force Fbuoyant minus the weight of the grinder pump station Fnet buoyant 5697 1 lb 845 lb 4852 1 lb B Ballast Force 1 Determ...

Страница 16: ...Buoyant Force 12606 0 lb 4852 1 lb 7753 9 lb The approach outlined above may be used to calculate the ballast requirements listed below Chart 2 Station Height in Wetwell Volume cu ft FNet Buoyant lb S...

Страница 17: ...17...

Страница 18: ...at grade discard existing welded on shroud and attached corrugations shroud is not to be reused Caution Be careful not to cut either the vent pipe or the pump breather cable 6b Clamped on shroud Remo...

Страница 19: ...ension 18 Lube wet well vent grommet and vent pipe extension with pipe lube non grit hand cleaner or dish soap and slide vent pipe through grommet until tank shroud seats to accessway 19 Place SS band...

Страница 20: ...20...

Страница 21: ...21 Environment One Corporation 2773 Balltown Road Niskayuna New York 12309 1090 Voice 01 518 346 6161 Fax 518 346 6188 www eone com NA0064P01 Rev J 07 23 A Precision Castparts Company...

Страница 22: ...Sanitary napkins or tampons Cigarette butts Caution Kitchen garbage disposals do not keep grease oil out of the plumbing system In addition you must never introduce into any sewer Explosives Strong c...

Страница 23: ...provided the product is properly installed serviced and operated under normal conditions and according to manufacturer s instructions Repair or parts replacement required as a result of such defect wi...

Отзывы: