![E-one Extreme Series Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/e-one/extreme-series/extreme-series_typical-installation-instructions-and-warranty-information_3060562012.webp)
12
E/One Grinder Pump Station Ballast Calculations
Sample Calculation, DH272/DR272
C. Subtract the buoyant force from the ballast force to determine the final condition
Final Condition
= Ballast Force - Buoyant Force
= 5973.0 lb – 2165.4 lb
=
3807.6
lb
The approach outlined above may be used to calculate the ballast requirements listed below.
Chart 1
Station
Height (in)
Wetwell
Volume
(cu ft)
FNet-
Buoyant
(lb)
Station
Weight
(lb)
Fballast
(lb)
Volume
Concrete
(cu ft)
Weight
Concrete
in Air (lb)
97 inches
46
2165.4
705
5973
NA
NA
129 inches
46
2140.4
730
9438
NA
NA
160 inches
46
2100.4
770
14,311
NA
NA