CLASS 3200 METER
62-0390-02
12
6.0 METER INSTALLATION
6.1 Mounting the Class 3200 Meter
Use appropriately sized mounting hardware to fasten the Class 3200 enclosure to the
selected mounting surface. The four housing mounting holes are centered 6.75” H x 4”
W. When the meter is provided in the 4X rated enclosure, the hub must be mounted to
the conduit first before connecting it to the enclosure.
NOTE: Units housed in UL type 1 enclosures must only be installed in indoor loca-
tions, where they will not be affected by the elements.
6.2 Main Power Board Connections
1. Installing a temporary ground for ESD protection: With all circuits de-energized,
connect a temporary protective earth ground connection for ESD protection.
Prior to performing any unit wiring, be sure to discharge any static on your per-
son.
2. Installing the Class 3200 protective earth ground: Connect an earth ground wire
to the Class 3200 (Type 1 enclosure) protective earth ground lug with a torque of
7 N-m.
WARNING
Failure to attach the protective earth ground wire securely to the meter creates
a potential shock hazard. Do not loosen or remove the screw securing the
ground lug.
Fig. 4. Main Power Board Connections.