Testing
Turn the LUX adjuster fully clockwise (SUN); turn the TIME adjuster fully anti-clockwise to the
minimum (10s).
•
Switch on the AC supply and after a 30sec warm-up period
the sensor will now be in test mode
•
Walk test the sensor, when the sensor receives a valid
trigger signal within its detection area the lamp will turn
on. If the sensor does not receive any other valid trigger
signal then the light should switch off 10sec (±3sec).
•
While the lamp is on and if the sensor receives additional
valid trigger signal then the timer will re-start and the light will remain on.
•
Adjusting SENS adjuster for desired the detection range.
•
Walk test immediately outside the area to ensure no detection or activation through walls and
floors to minimize unwanted activations.
•
After testing the sensor ensuring the required area can be detected, Turn the LUX adjuster to the
required light operational level, adjust the TIME adjuster clockwise to the required time for the light
duration to be on.
Troubleshooting
The load does switch on:
o
Please check the connections, and the AC mains supply is on
o
Please check if the load is operational
o
Please check the adjustment settings and make the necessary adjustments if required