3
Jumper for setting the analogue output:
Current
Voltage
- 0-1V
0-20mA 0-5V
4-20mA 0-10V
Jumper for setting the response time:
fast response time
slow response time
Example:
Jumper "Output Range" set to 0...10V.
Jumper "Fast/Slow" set to "Fast"
Analog-Output
Modbus-Interface
HARDWARE SETTINGS
Dipswitch for modbus settings
S1, S2
baud rate
S3 stopbit
S4 parity
S5 - S10 addresse of the converter
Jumper for terminator settings
active/inactive
Example:
Dip-switch S1 and S2 "Baud rate" set on 19200
Dip-switch S3
"Stopbit" set on "one"
Dip-switch S4
"Parity" set on "even"
Dip-switch S5 - S10
"Address" set on "13" (activate S5/S7/S8)
Jumper "Terminator"
set on "No"
MODBUS MAP
Register
address
Parameter name
Protocol
address
0x00
SN Hardware
0
0x01
1
0x02
2
0x03
3
0x04
4
0x05
5
0x06
6
0x07
7
0x08
FW Version
8
0x09
Partname of Transmitter
9
0x0A
10
0x0B
11
0x0C
12
0x0D
13
0x0E
14
0x0F
15
0x10
16
0x11
Serialnumber E2 Transmitter
17
0x12
18
0x13
19
0x14
20
0x15
21
0x16
22
0x17
23
0x18
24
Register
address
Parameter name
Protocol
address
0x19
Measured value 1
25
0x1A
26
0x1B
Measured value 2
27
0x1C
28
0x1D
Measured value 3
29
0x1E
30
0x1F
Measured value 4
31
0x20
32
0x21
Gain Spannung
33
0x22
34
0x23
Offset Spannung
35
0x24
36
0x25
Gain Strom
37
0x26
38
0x27
Offset Strom
39
0x28
40
0x29
Measrange low
41
0x2A
42
0x2B
Measrange high
43
0x2C
44
0x2D
Analog Output low (V)
45
0x2E
46
0x2F
Analog Output high (V)
47
0x30
48
0x31
Slow or Fast
49
0x32
50
ASCII
ASCII
ASCII
FLOA
T
HIGH BYTE - main version
LOW BYTE - sub version