3.2. Determining Installation Site
•
The installation site should be easy accessible and free of vibrations and shocks.
•
Observe at least 260 mm (10.24 inch) clearance above the housing with the signal conditioning, in
order to be able to remove the sensing probe if necessary.
•
The ambient temperature should not exceed the value as stated in the specifications (see page
20) – consider heating by radiation.
•
Air purity on the installation site according to ISO 8573-1:2010: at least class 3.4.4
•
The fluid should not condense at the installation site. Condensation on the tip of the sensing probe
must be avoided.
•
In compressed air systems, the installation must be downstream of the dryer. If there is no dryer, at
least steam trap and suitable filter must be present.
•
Observe the direction of the flow by the installation (see page 10).
•
Observe the recommended straight pipe lengths up and downstream, in order to warrant the speci-
fied measurement accuracy.
•
The flow sensor should be installed as far as possible from any flow disturbance. Valves or check-
valves should be installed in a respective distance from the flow sensor.
3.3. Installation Position
Make sure that the arrow on the tip of the sensing probe is pointing in the direction of the flow.
++ ... recommended installation position
+ ..... not recommended if there is vibration on the pipeline
- ...... not recommended
Model
Vertical Mounting
Compact
Remote
+
++
Horizontal Mounting, sensor upwards
++
++
Horizontal Mounting, sensor downwards
-
-
Horizontal Mounting, sensor across
+
++