4.7  Switching Off

The low flow cut-off is intended to prevent the 

display or output signal fluctuating if the flow is cut 

off.

Small differences in temperature in the duct can produce small flow fluctuations, which would be 

recorded by the sensor without the low flow cut-off.

 

(switching point OFF + hysteresis = switching point ON) 

can be defined in the input fields of the "Switching Off" 

tab.

Note:

The EE75 comes with the low flow cut-off function activated, 

with a switching point OFF of 0.1 m/s 

(20ft/min)

and  

a hysteresis of 0.05 m/s 

(10ft/min)

.

Should you require smaller flow velocities to be 

 

displayed, deactivate the low flow cut-off (switching 

point OFF + hysteresis = 0 m/s or ft/min.).

 

4.8  Media Correction

The EE75 measures air velocity [m/s] temperature-

independent, but pressure-dependent and is 

standardised to 45 % relative   humidity  and  air 

pressure of 1013 mbar at the factory.

If e.g. the media pressure is significantly different, the actual values can be defined in the input field 

on the "Mediacorr." tab to obtain the best possible measuring results.

4.9 

 

Calibration

Velocity and temperature calibration is not only possible using the buttons on the integrated display, 

the EE75 can also easily be calibrated / adjusted using the configuration software.

Note:

The configuration software automatically distinguishes between the low and high calibration points.

- If the selected calibration point is BELOW the centre of the measuring range, it is automatically  

  recognised as the "low calibration point" (CAL LOW).

- If the selected calibration point is ABOVE the centre of the measuring range, it is automatically  

  recognised as the "high calibration point" (CAL HIGH). 

 

Example:

EE75 T3***HV23: Measuring range = 0 - 2 m/s 

(0 - 400 ft/min)

 -> centre of  

 

measuring range = 1 m/s 

(200 ft/min)

- 0.5 m/s 

(100 ft/min)

 -> calibration point lies below 1 m/s 

(200 ft/min) 

-> CAL LOW

- 1.6 m/s 

(300 ft/min) 

-> calibration point lies above 1 m/s 

(200 ft/min) 

-> CAL HIGH

Switching point 

OFF and 

Hysteresis:

switching point OFF

active

hysteresis

switching point ON

Содержание EE75

Страница 1: ...BA_EE75 v14 Modification rights reserved 192310 User Manual EE75 Air Gas Velocity Sensor Hardware and Software...

Страница 2: ...and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that inte...

Страница 3: ...Calibration 10 6 1 2 General Information on 2 point v T Calibration 11 6 2 Velocity Calibration 11 6 2 1 Calibration Procedure Using Configuration Software 11 6 2 2 Calibration Procedure Using Button...

Страница 4: ...ctions Excessive mechanical stress and improper use must be avoided As the sensor element is sensitive to electrostatic discharge ESD appropriate protective measures should be taken when touching it I...

Страница 5: ...rt of the enclosure is fitted using 4 screws not included Max screw diameter 4 5 mm 0 18 for example 4 2 x 38 mm 0 17 x 1 5 DIN 7983H screws 4 Connecting the sensor see chapter 4 Electrical Connection...

Страница 6: ...e may get stuck Before installing the sensing probe make sure it is free from any impurities such as grease or dirt Installing the probe There should be a shut off valve on both sides of the probe ins...

Страница 7: ...centre of the velocity measuring slot middle of the sensor The scaling on the probe has an offset of 30mm 1 2 This allows for the insertion depth X distance between middle of sensor and mounting plat...

Страница 8: ...ssignment USB Interface Cable Colour of wire Signal Terminal no Green D 11 White D 12 Red Vbus 13 Black USB GND 14 Shielding Description Connection assignment VCC 5 GND 4 GND 3 OUT2 2 OUT1 1 Descripti...

Страница 9: ...ing jumpers Jumper position Also see chapter 5 1 Circuit Board Response time No jumper 1 5 s Jumper at pos 1 2 s factory setting Jumper at pos 2 4 s factory setting Jumper at pos 3 10 s factory settin...

Страница 10: ...ted 6 Status Line The status line indicates the sensor s current operating status no indication Normal operating mode measurement in progress MIN or MAX See point 4 MIN MAX function CAL LOW V or T cal...

Страница 11: ...mited working ranges 2 point v T calibration With 2 point calibration precise measuring results can be obtained over the entire v T measuring range The more complicated 2 point calibration procedure i...

Страница 12: ...described in chapter 6 1 1 If calibration point 50 of measuring range select V CAL HIGH and confirm the selection If calibration point 50 of measuring range select V CAL LOW and confirm the selection...

Страница 13: ...adjusted measuring value 10 In the case of 1 point T calibration the procedure is now complete 11 For 2 point T calibration repeat steps 6 2 9 with the high calibration point 6 4 Resetting to Factory...

Страница 14: ...120 C 40 248 F Accuracy typ 2 0 5 C 0 9 F in air at 25 C 77 F Response time t90 typ 10 s Temperature dependency electronics typ 0 005 of mv K deviating from 25 C 77 F mv measured value v or T Temperat...

Страница 15: ...The permanent connection between EE75 and PC via the USB interface in normal operation may cause a malfunction and does not meet the CE criteria 2 Installation NOTE Administrator authorisations may be...

Страница 16: ...ntroller on your PC s Control Panel See Start Settings Control Panel System Hardware Device Manager 6 The configuration software can now be opened by double clicking the EE75 icon on your desktop 7 Sp...

Страница 17: ...Start Settings Control Panel System Hardware Device Manager Closes the configuration software 3 2 Help Provides general information on the configuration software 4 EE75 Configurator 4 1 Start The Sta...

Страница 18: ...nput field Single line display Two line display factory setting Backlight on check box Activated ON Not activated OFF 4 4 Response Time As described under Hardware chapter 5 2 Jumpers for Setting the...

Страница 19: ...ld If the duct has a different shape or the cross sectional area is already known the value can of course also be entered directly in the Cross sectional area field in m or ft 4 6 Probe Cable The leng...

Страница 20: ...he media pressure is significantly different the actual values can be defined in the input field on the Mediacorr tab to obtain the best possible measuring results 4 9 Calibration Velocity and tempera...

Страница 21: ...HIGH should be around 1 8 m s 1 4 2 4 9 3 V Calibration Procedure Using the Configuration Software 1 Position the sensor head in the middle of the reference system wind tunnel 2 Set the required calib...

Страница 22: ...particularly useful for checking sensors which do not have the optional display module 4 11 Information The Information tab contains general information on the sensor It also saves the date of the la...

Страница 23: ...22 Configurations Software...

Страница 24: ...pluse fr E E Elektronik Germany Obere Zeil 2 61440 Oberursel Tel 49 6171 69411 0 E mail info epluse de E E Elektronik India 801 Sakhi Vihar Road 400072 Mumbai Tel 91 990 440 5400 E mail info in epluse...

Отзывы: