EE600 with RS485 Interface

BACnet

Modbus

Factory settings

Selectable values

Factory settings

Selectable values

Baud rate

As ordered per type number

9600, 19200, 38400, 57600, 76800

As ordered per type number

9600, 19200, 38400

Data bits

8

8

8

8

Parity

None

None

Even

None, odd, even

Stop bits

1

1

1

1, 2

Address

43

0...127

43

1...247

BACnet Protocol

The bus termination shall be realized with 120 Ω resistor (slide switch on board).

1) Register number starts from 1    2) Protocol address starts from 0    3) 1xx is scale. E.g. for 1:100, reading of 2550 is equivalent to 25.5

Modbus Protocol

The EE600 PICS (Product Implementation Conformance Statement) is available on the website at 

www.epluse.com/ee600

.

The recommended settings for multiple devices in a BACnet MS/TP network are 38400, 8, None, 1.

Address and Baud rate can be set via:

1.  PCS10, Product Configuration Software and the USB configuration adapter cable HA011066.

2.  BACnet protocol, see the PICS.

The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1.

Address, Baud rate, parity and stop bits can be set via:

1.  PCS10, Product Configuration Software and the USB configuration adapter cable HA011066.

2.  Modbus protocol in the register 60001 (0x00) and 60002 (0x01). 

 

 

See Application Note Modbus AN0103 (available on 

www.epluse.com/ee600

).

The measured parameters are saved as a 32 bit floating point value and as 16 bit signed integer value, see the Modbus register map below.

Modbus Register Map

FLOAT32

Parameter

Unit

Register number

1)

 

[DEC]

Protocol Address

2)

 

[HEX]

Read register: function code 0x03 / 0x04

Differential pressure

mm H

2

O

1211

0x4BA

Differential pressure

mbar

1213

0x4BC

Differential pressure

Pa

1215

0x4BE

Differential pressure

kPa

1217

0x4C0

Differential pressure inch WC

1219

0x4C2

Air velocity

m/s

1041

0x410

Air velocity

ft/min

1043

0x412

Volume flow

m

3

/h

1055

0x41E

Volume flow

l/s

1057

0x420

Volume flow

m

3

/s

1059

0x422

Volume flow

ft

3

/min

1181

0x49C

Filter monitoring

%

1075

0x432

Level indicator

cm

1077

0x434

Level indicator

inch

1079

0x436

Communication Settings

INT16

Parameter

Unit

Scale

3)

Register number

1)

 

[DEC]

Protocol Address

2)

 

[HEX]

Read register: function code 0x03 / 0x04

Differential pressure

mm H

2

O

10

4106

0x1009

Differential pressure

mbar

100

4107

0x100A

Differential pressure

Pa

1

4108

0x100B

Differential pressure

kPa

1000

4109

0x100C

Differential pressure inch WC

100

4110

0x100D

Air velocity

m/s

100

4021

0xFB4

Air velocity

ft/min

1

4022

0xFB5

Volume flow

m

3

/h

1

4028

0xFBB

Volume flow

l/s

1

4029

0xFBC

Volume flow

m

3

/s

1000

4030

0xFBD

Volume flow

ft

3

/min

1

4091

0xFFA

Filter monitoring

%

10

4038

0xFC5

Level indicator

cm

10

4039

0xFC6

Level indicator

inch

10

4040

0xFC7

Push buttons for 

 

span and zero point adjustment

Address switch

Status LED

USB configuration adapter

Display

Termination resistor 120 Ω slide switch: 1=ON, 0=OFF

Supply and

 

RS485 terminals

Address Setting

0 0 0 0 0 0 0 0

1 1 0 0 0 0 0 0

1
0

1
0

Address setting via Software

All DIP switches at position 0 → address has to be set via Software (via PCS10 Product Configuration Software 

or via protocol BACnet / Modbus). Default address 43.

Example: Address is set via configuration software.

Address setting via Dip-Switch

Setting the DIP switches to any other address than 0, overrules the default address (43) or the address set via 

Software.

Example: Address set to 3 (0000 0011 binary).

0 0 0 0 0 0 0 0

1 1 0 0 0 0 0 0

1
0

1
0

Electronics Board Layout