User Manual EE260 Heated Humidity and Temperature Probe for Meteorological Applications

5  Setup and Adjustment

The EE260 is ready to use and does not require any configuration by the user. The factory setup of 

EE260 corresponds to the type number ordered. Please refer to the data sheet at 

www.epluse.com/

EE260

. The user can change the factory setup with the help the EE-PCS Product Configuration Software, 

the  Modbus  configuration  adapter  (order  code  HA011018)  and  the  EE260  configuration  cable  (order 

code HA011020).
Besides the measurand selection of the analogue and digital outputs and their scaling, the digital 

interface settings may be changed. The RH and T measurement is offset and 2-point adjustable. It is 

possible to enable or disable the sensing element and the probe heating (separated from each other; 

factory setting for both: enabled) and the NAMUR error indication (factory setting: disabled). For the 

purpose of pressure compensation, the barometric air pressure at the operating site may be set.

Please note:

 The EE260 may not be connected to any additional power supply when using the Modbus 

configuration adapter HA011018.

PC

Fig. 5 

Configuration

5.1  EE-PCS Product Configuration Software

To use the software for performing adjustments and changes in settings, please proceed as follows: 

1. Download the EE-PCS Product Configuration Software from 

www.epluse.com/configurator

 and  

install it on the PC.

2. Connect the EE260 to the PC using the Modbus configuration adapter and the EE260 configuration 

cable. 

3. Start the EE-PCS software. 

4. Follow the instructions on the EE-PCS opening page for scanning the ports and identifying the 

connected device.

5. Click on the desired setup or adjustment mode from the main EE-PCS menu on the left and follow 

the online instructions of the EE-PCS

5.2  Digital Interface RS485 with Modbus RTU Protocol

Item

Factory settings

Selectable values (via EE-PCS)

Baud rate

9 600

9 600, 19 200, 38 400, 57 600, 76 800, 115 200

Data bits

8

8

Parity

Even

None, odd, even

Stop bits

1

1, 2

Slave address

235

1...247

Tab. 2 

Digital interface default settings

The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1.

The EE260 represents 1 unit load on an RS485 network.
Device address, baud rate, parity and stop bits can be set via:

1.  EE-PCS Product Configuration Software, the Modbus configuration adapter HA011018 and the 

EE260 configuration cable HA011020. 

The EE-PCS can be downloaded free of charge from 

www.epluse.com/configurator

2.  Modbus protocol in the register 60001 (0x00) and 60002 (0x01).  

See Modbus Application Note AN0103 (available at 

www.epluse.com/EE260

)

The serial number as ASCII-code is located in the register addresses 0x00...0x07 (16 bits per address).

The firmware version is located in the register address 0x08 (bits 15...8 = major release; bits 7...0 = 

minor release). The sensor name is located in register address 0x09. The beforementioned registers can 

be read out with function code 0x03 or 0x04.

HA011018

HA011020

Содержание EE260

Страница 1: ...BA_EE260 v1 1 Modification rights reserved User Manual EE260 Heated Humidity and Temperature Probe for Meteorological Applications...

Страница 2: ...equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmf...

Страница 3: ...and Adjustment 9 5 1 EE PCS Product Configuration Software 9 5 2 Digital Interface RS485 with Modbus RTU Protocol 9 5 3 Modbus Register Map 11 5 4 Modbus Message Example 12 6 Maintenance and Service...

Страница 4: ...Safety Instructions 1 2 1 General Safety Instructions The device and mainly the filter cap shall not be exposed to unnecessary mechanical stress When replacing the filter cap make sure not to touch t...

Страница 5: ...connections shall be thoroughly checked by authorized staff before putting the device into operation Do not install or start up a device supposed to be faulty Make sure that such devices are not acci...

Страница 6: ...umidity related parameters Dew point temperature Td Frost point temperature Tf Wet bulb temperature Tw Water vapour partial pressure e Mixing ratio r Absolute humidity dv Specific enthalpy h The RH an...

Страница 7: ...cho Puls 25 18 25 Fig 2 Dimensions in mm of optional radiation shield ordering code HA010511 3 3 Electrical Connection Pin number Function Wire colors for accessories Connection cable HA010322 23 24 2...

Страница 8: ...he HA010511 data sheet for more information Fig 3 EE260 mounted within the optional radiation shield HA010511 4 2 Wall Mount Pole Mount The probe may be installed on a wall or a pole with the help of...

Страница 9: ...nd install it on the PC 2 Connect the EE260 to the PC using the Modbus configuration adapter and the EE260 configuration cable 3 Start the EE PCS software 4 Follow the instructions on the EE PCS openi...

Страница 10: ...ction code 0x06 Slave ID Modbus address 1 0x00 Modbus protocol settings3 2 0x01 1 Register number starts from 1 2 Protocol address starts from 0 3 For Modbus protocol settings see Application Note Mod...

Страница 11: ...d C 1105 0x450 F 1107 0x452 K 1147 0x47A Wet bulb temperature Tw C 1109 0x454 F 1111 0x456 K 1145 0x478 Absolute humidity dv g m 1113 0x458 gr ft 1115 0x45A Mixing ratio r g kg 1121 0x460 gr lb 1123 0...

Страница 12: ...sure above water ew mbar 100 4111 0x100E psi 100 4112 0x100F Saturation vapor pressure above ice ei mbar 100 4113 0x1010 psi 100 4114 0x1011 Ice bulb temperature Ti C 100 4119 0x1016 F 100 4120 0x1017...

Страница 13: ...the user see the E E cleaning instructions 6 2 Filter Replacement In a dusty or polluted environment it might be necessary to replace the filter cap or the filter membrane respectively once in a whil...

Страница 14: ...emperature Please contact your sales representative for assistance Please note When the calibration adjustment procedure with the help of EE PCS starts both heating modes of the EE260 are disabled aut...

Страница 15: ...ure with the help of EE PCS starts both heating modes of the EE260 are disabled automatically if they have on status At the end of the procedure the heating comes back to on automatically The temperat...

Страница 16: ...EE260 configuration cable1 HA011020 E E Product Configuration Software Download www epluse com configurator EE PCS M12x1 cable connector 8 pole socket HA010704 Connection cable 8 pole M12x1 socket fre...

Страница 17: ...ID 235 General Supply voltage 7 30 V DC Power consumption typ 300 mW 25 mA 12 V DC heating included Electrical connection M12x1 8 poles stainless steel 1 4404 Filter PTFE membrane stainless steel body...

Страница 18: ...lin 69130 Ecully Tel 33 4 74 72 35 82 E mail info epluse fr E E Elektronik Germany Sch ne Aussicht 8 C 61348 Bad Homburg Tel 49 6172 13881 0 E mail info epluse de E E Elektronik Italy Via Alghero 17 1...

Отзывы: