background image

INSTALLATION INSTRUCTIONS FOR EMERGENCY LIGHTING FIXTURES

IMPORTANT SAFEGUARDS 

When using electrical equipment, basic safety precautions 
should always be followed including the following:

SAVE THESE INSTRUCTIONS!

ELECTRICAL CONNECTIONS

 WALL MOUNTING

CEILING MOUNTING WITH SURFACE CONDUIT FEED

1. To avoid the possibility of electric shock, turn off power supply before
    installation or servicing.
2. Review the diagrams thoroughly before installation.
3. All electrical connections must be in accordance with the NEC and local codes. 
    A qualified electrician should do all the work.
4. Do not let power supply cords touch hot surfaces.
5. Do not mount near gas or electric heaters.
6. Equipment should be mounted in locations where it will not be readily subject to tampering by unauthorized personnel.
7. The use of accessory equipment not recommended by the original manufacturer may cause an unsafe condition.
8. Do not use this equipment for other than intended use.
9. All servicing should be performed by qualified personnel only.

 

1. Verify the power is off before installation.
2. Connect ground (Green) lead to suitable ground. 
3. Connect fixture Neutral (White) lead to supply neutral (White) lead.
4. Determine supply voltage for fixture. Connect hot lead (Black for 120V or Red or Orange for 277V) to supply hot lead. 
    Cap unused fixture lead with wire nut.

 

1. Separate front cover from back plate with a flat blade screwdriver. Open from top slot first and then from side slots gently. 
   (See Figure1)
2. Remove knock out hole in the center of the back plate. Remove knock out slots on the back plate that correspond 
    to the size of the junction Box.
3. Feed AC supply leads through the center hole in the back plate. Then make the proper electrical connections. See electrical 
    connections section for proper instructions. Cap off unused hot lead.
4. Mount back plate to junction box with provided #8-32×0.875” screws. (See Figure 2 or Figure 4)
5. Attach battery connector and power connector.
6. Attach front cover to back plate. (Should snap right in)
7. Supply power and test the unit.

 

1. Separate front cover from back plate with a flat blade screwdriver. Open from top slot first and then from side slots gently. 
   (See Figure1)
2. Unscrew the pipe plug from top of back plate.
3. Secure back plate screw on the conduit. (See Figure 3 or Figure 5)
4. Make the proper supply lead connections. See Electrical connections section for proper instructions. Cap off unused hot lead.
5. Attach battery connector and power connector.
6. Attach front cover to back plate.
7. Supply power and test the unit.

NOTE: Allow battery to charge for 24 hours before first use.

 

OPENING FRONT COVER

Figure 1

Flat blade
screwdriver

 

Open from top slot first then side slot

 

Side slot

 

Top slot

 

Page 1 of 4

NOTICE-Use flat blade screwdriver to open. Insert screwdriver in the
slot (one on the top, two on the sides) and gently pry off the cover.

 

Содержание E-XML4 Series

Страница 1: ...wire nut 1 Separate front cover from back plate with a flat blade screwdriver Open from top slot first and then from side slots gently See Figure1 2 Remove knock out hole in the center of the back plate Remove knock out slots on the back plate that correspond to the size of the junction Box 3 Feed AC supply leads through the center hole in the back plate Then make the proper electrical connections...

Страница 2: ... female White Neutral Red or Orange for 277V Printed Circuit Board Transformer power Connector male Battery Connector Front cover assembly Frame Black for 120V White Neutral Red or Orange for 277V Screw 8 32 0 875 Transformer power Connector male Back plate 120VAC 0V NEUTRAL 277VAC GROUND GREEN Green Ground wire Page 2 of 4 PCBA BAT Transformer Power Connector Transformer LED Front Cover LED Modul...

Страница 3: ...k for 120V White Neutral Red or Orange for 277V Screw 8 32 0 875 Heater power connector male Transformer power Connector male Back plate JUMPER Heater power connector female Printed Circuit Board Note 1 2pcs short circuit connector in the accessory bag 2 For 120Vac input connection short circuit connector insert in female connector marked JUMPER in slots 1 and 2 3 For 277Vac input connection short...

Страница 4: ...lf testing and a 90 minute discharge once every 365 days after AC power has been supplied for a minimum of 24 hrs SERVICE INDICATION MANUAL TESTING WARNING The unit also provides for manual testing by pushing the test button in a specific pattern n o i t a c i d n I D E L n o i t c a e R n o i t c A Push test button Once within 2 seconds 30 second test FLASHING Green Push test button Twice within ...

Отзывы: