E.C.A. 8116450010 Скачать руководство пользователя страница 13

6

- USING THE BOILER

6

.1

.

 Switching Off the Boiler

You can switch off the boiler by holding down the ON/ OFF 

button for 3 seconds.

LCD light will be OFF after 1 minute.

Anti-freeze function remains active.

7

- CONTROL PANEL

Figure 2

Control Panel View

7

.1

.

 Functions of

 

Buttons

The

 

control

 

panel

 

consists

 

of

 

the relevant elements

 

as

 

shown

 

in figure 2

below.

A-Position

 

Selection

 

Button

The position can be changed by pressing the position selection 
button  once  to  change  between  the  winter  mode  and  the 
summer  mode.  If  the  button  is  pressed  for  3  seconds,  the 
boiler  will  switches  into  "standby"  position.  It  will  enough  to 
press the button once to get the boiler in operation position. 

B-Reset

 

Button

Main functions: 

9

 

Exit from lockout error (EXX)

9

 

ECO mode activation

9

 

Comfort mode activation

When your boiler fails, the error code will start flashing on the 

display. There are 2 types of errors, lockout (EXX) and blocking 

(FXX) error. When a lockout error condition occurs (EXX), the 

error must first be corrected so that the error code can be 

removed from the LCD screen. After pressing the "Reset" key 

once, the boiler can switch back to normal operation state. As 

for a blocking error, the fault cannot be removed from the LCD 

display pressing the "Reset" button (FXX). When this error is 

corrected, error code is automatically disappears from LCD 

screen. The first time the boiler starts, it will start working in 

Comfort mode. 

$

&

'

(

)

%

Once the Reset button is pressed when operating in 
Comfort mode, the boiler

 

will switch to Eco mode. 

Then when Reset button is pressed again, the unit will 
switch to Comfort mode.

C-Domestic Hot Water Increase Temperature
Button

The temperature of the domestic water can be 
increased up to 65 °C thanks to the domestic 
water 

temperature increase button.

D-Central Heating Water Increase
Temperature Button

The temperature of the heating water can be increased 
up to 80 °C thanks to the heating water temperature 

increase button.

E- Domestic Hot Water Decrease
Temperature Button

The temperature of the domesti

c water can be 

decreased down to 30 °C thanks to the domestic 
water 

temperature decrease button.

F-Central Heating Water Decrease
Temperature Button

The temperature of the heating water can be 
decreased down to 30 °C thanks to the heating 
water 

temperature decrease button.

7

.2

LCD Screen

LCD screen display icons described here below.

Solar Panel Mode 

Comfort Mode 

ECO Mode 

CH Mode ON 

RESET 

DHW Mode ON 

Temperature 
Value 

Flame 
Symbol 

Parameter 
Settings 

Pressure 
Display 

Figure 2

. Description of Symbols

7

.2.1

.

Flame Icon:

 

When operating between 0% and 

50% capacity range, the icon is displayed on the LCD 
screen  as  single  bar,  whereas  it  is  displayed  as  two 
bars  when  operating  between  50%  -100%  capacity 
range.

7

.2.2

.

Pressure  Indicator:

The  LCD  display  shows 

0-0,5-1-1,5-2-2,5-3  bar  water  pressure  values.  The
values  other  than  these  ones  are  not  displayed.

 

Only

when filling after F37 (Low water pressure error) fault,
the  pressure  value  is  displayed  in  the  temperature
value section.

13

Содержание 8116450010

Страница 1: ...3527 86 35 0 0 67 3527 86 35 0 21 16 1 2 5 23 5 7 1 167RUCTIONS ...

Страница 2: ...ombi Boiler in Terms of Safety and Energy Consumption 3 2 Clogging in Installation 3 3 Cleaning of Boiler 3 4 Boiler Features 3 5 Additional Recommendations by ECA to Customer To Have High Heating Performance 4 4 TECHNICAL DATA 5 5 ERP TECHNICAL DATA 5 1 PACKAGE LABEL CALCULATIONS 10 6 6 USING THE BOILER 13 6 1 Switching Off the Boiler 13 7 7 CONTROL PANEL 13 7 1 Functions of Buttons 13 7 2 LCD Sc...

Страница 3: ...nstalled in accordance with national and local requirements gas safety regulations relevant standarts and this manual by gas safe engineer 9 The boiler must be mounted against a closed wall 9 The boiler can not be positioned having direct contact to steam detergent or gases 9 Any change of flue position must not be made without consulting gas safe engineer 9 Sunlight can cause color change on the ...

Страница 4: ...t centralheating co uk or installersfirst co uk for more information PRODUCT NAME PRODUCT CODE GC NUMBER PROTEUS PREMIX 14 HM NG ERP UK 8116941010 47 814 30 PROTEUS PREMIX 20 HM NG ERP UK 8116944010 47 814 29 PROTEUS PREMIX 24 HM NG ERP UK 8116450010 47 814 01 PROTEUS PREMIX 28 HM NG ERP UK 8116451010 47 814 02 PROTEUS PREMIX 30 HM NG ERP UK 8116452010 47 814 03 PROTEUS PREMIX 35 HM NG ERP UK 8116...

Страница 5: ...tial start up of the boiler Instructions are given below 9 Check Operating Instructions Installation and Maintenance Instructions and follow instructions before installation 9 Carry out installation in compliance with the prevailing legislation and standarts 9 Be sure that the system is flushed and inhibitor added 9 Only gas safe engineer must operate the boiler 9 Explain the user about installati...

Страница 6: ... unauthorized service or staff 3 4 Boiler Features Control panel is ergonomic and easy to use The Proteus Premix condensing boiler with elegant plastic control panel and advanced LCD screen provides ease of use and service On a LCD display with black instrument panel you can see the operating state icons heating circuit and operating water adjustment values the fault failure codes and the heating ...

Страница 7: ...5 Seasonal Space Heating Energy Efficiency 91 11 91 4 92 2 92 4 92 92 9 Water Heating Energy Efficiency 83 6 83 6 83 6 83 9 82 8 82 8 Sound Power Level db A 49 49 49 49 49 49 Efficiency at Rated Heat Output At High Temperature Regime ƞ4 87 9 87 9 87 9 87 9 87 9 87 9 Efficiency at 30 of rated Output At Low Temperature Regime ƞ1 97 97 97 2 97 4 97 97 9 At Full Load elmax kW 0 028 0 035 0 04 0 051 0 ...

Страница 8: ...D Expansion Vessel lt 8 Weight Net kg 28 5 28 5 28 5 30 30 32 Weight Net only for HCH model kg 22 5 22 5 22 5 24 24 26 Dimesions HxWxD mm 678 410 288 Flue Lenghts C13 60 100 Max m 10 10 10 10 10 10 C13 80 125 Max m 20 20 20 20 20 20 C33 60 100 Max m 10 10 10 10 10 10 C33 80 125 Max m 20 20 20 20 20 20 C43 60 100 Max m 10 10 10 10 10 10 C53 60 100 Max m 10 10 10 10 10 10 C83 80 80 Max m 28 28 28 28...

Страница 9: ...B 49 Specific precautions for assembly installation and maintanence All specific precautions for installation assembly and maintanence are described in the installation and service manual Proteus Premix Boiler ERP Units HCH 67 MODEL Supplier s name or trademark E C A Proteus Proteus Proteus Proteus Proteus Proteus Supplier s model identifier Premix Premix Premix Premix Premix Premix 14 20 24 28 30...

Страница 10: ...ion from fiche of solar device III The value of the mathematical expression 294 11 Prated whereby Prated is related to the preferential space heater IV The value of the mathematical expression 115 11 Prated whereby Prated is related to the preferential space heater 1 If tank rating is above A use 0 95 1 T Class I 1 Class II 2 Class III 1 5 Class IV 2 Class V 3 Class VI 4 Class VII 3 5 Class VIII 5...

Страница 11: ...r in this fiche may not correspond to its actual energy efficiency once installed in a building as this efficiency is influenced by further factors such as heat loss in the distribution system and the dimensioning of the products in relation to building size and characteristics Package Fiche Combination Heaters Boilers or Heat Pumps Water heating energy efficiency of combination heater Declared lo...

Страница 12: ...e dimensioning of the products in relation to building size and characteristics I The value of the water heating energy efficiency of the combination heater expressed in II The value of the mathematical expression 220 Qref Qnonsol where Qref is taken from Regulation EU 811 2013 Annex VII Table15 and Qnonsol from the product fiche of the solar device for the declared load profile M L XL or XXL of t...

Страница 13: ... Comfort mode Once the Reset button is pressed when operating in Comfort mode the boiler will switch to Eco mode Then when Reset button is pressed again the unit will switch to Comfort mode C Domestic Hot Water Increase Temperature Button The temperature of the domestic water can be increased up to 65 C thanks to the domestic water temperature increase button D Central Heating Water Increase Tempe...

Страница 14: ...domestic hot water is heating request the tap symbol flashes 1 time sec In this mode the domestic hot water temperature can be adjusted between 30 65 C 7 3 5 Comfort Mode The standard operating mode of the boiler is Comfort mode By pressing the Reset button Eco Comfort modes can be switched When Comfort mode is active Comfort icon is displayed on the LCD screen Comfort mode is only for radiator he...

Страница 15: ... is still present or persists after reset notify gas safe engineer 1 Press reset button 2 If the error is still present or persists after reset notify gas safe engineer 1 Check that water valves of boiler installation are open 2 If the combi boiler triggers this error in winter mode check that at least 1 radiator is open 3 Press reset button 4 If the error is still present or persists after reset ...

Страница 16: ...when the temperature of the flue gas exceeds 95 o C F07 1 Notify gas safe engineer F13 Repeated Reset Fault Pressing of Reset button more than 5 times in an hour 1 Notify gas safe engineer F25 Electronic Card Fault Electronic Card Firmware Fault 1 Notify gas safe engineer F34 Low Supply voltage It occurs when the supply voltage falls below 170V 1 Notify gas safe engineer 1 Press reset button 2 If ...

Страница 17: ...lue gas The flue gas temperature sensor is in short or open circuit state F53 1 Notify gas safe engineer Flue Gas Lock Out at High Temperature If it gives an error F07 twice in 1 month this error will occur F58 1 Notify gas safe engineer F81 Temperature sensor deviation test delay Temperature sensors might be defective 1 Notify gas safe engineer Table 1 Error Code Table 1 Check water pressure in h...

Страница 18: ...any third party who undertakes any work carried on the product or fits parts unless approval is given by the means mentioned in point 5 such work in advance of it being carried out 7 The boiler has to be installed at an accessible area where Engineers can perform servicing without health and safety risk 8 Cupboard installations must provide minimum working clearances as detailed in the installatio...

Страница 19: ...then be debited from your account i You are required to provide telephone contact numbers to enable us to contact you in the course of arranging and fulfilling your appointment In the course of arranging and fulfilling your appointment we may choose to contact you via phone text fax or e mail Charges xServicing and Commissioning appointments are charged at a fixed price inclusive of VAT with the p...

Страница 20: ...gesi 3 Kısım Mustafa Kemal Bulvarı No 13 45030 MANİSA 90 236 213 00 21 SALES TECHNICAL SUPPORT Call Center Tel 44 800 640 9988 Office Tel 44 203 978 1212 FWඈYDWඈQJ RXU TXDUDQWHH ඈV TXඈFN DQG VඈPSOH EXW UHDOO ඈPSRUWDQW 5HJඈVWHU DW www ecaboilers co uk warranty registration complate and return in the envelope provided 45 FRGH VFDQ PH ...