B-5
P O W E R R E Q U I R E M E N T S A N D I N S T A L L A T I O N
Excluding North America and Japan
Version 4
Above Ground Model 250i Motorcycle Dynamometer Installation Guide
EXCLUDING NORTH AMERICA AND JAPAN
The dyno (excluding North America and Japan) requires a dedicated wall receptacle
which must be wired for operation and is included with the dyno or may be shipped in
advanced in a separate package. The dyno is equipped with a twenty-five foot power
cord with a twist lock plug pre-wired on the end.
The dyno requires a dedicated 240VAC
single-phase
power outlet rated for 30A for
proper operation.
Failure to follow these instructions could result in
personal injury or damage to the dyno.
Connecting the dyno to the incorrect
voltage will void the dyno warranty. Contact Dynojet with any questions.
The dedicated wall receptacle is a three-pin IEC grounded 30A type and must be wired
in accordance with local building codes and requirements. Installation may require a
licensed electrician to conform to applicable safety standards.
If you are installing your dyno in a location other than North America or
Japan and the dyno is not equipped with a three pin IEC grounded plug,
contact Dynojet before attempting to connect the dyno.
Local and national electrical codes will require that the box containing the receptacle
is grounded.
• This circuit should have a dedicated 30A double-pole circuit breaker.
• The dyno should be the only device connected to this circuit.