Digital field display
10 Fault-finding
19
10.3
System messages
10.4 Fault analysis
Effect
Cause
Cure
Display
indicates:
„
#####
”
Under range. An input signal of <
3.6 mA is connected to unit input.
Please check the input signal.
Display
indicates:
„
*****
”
Over range. An input signal of >
21.0 mA is connected to unit input.
Please check the input signal.
Display
indicates:
„
(+
”
Operating parameters have been
changed. The unit requests a save
command.
Release save/do not save using the "+/-"
push buttons and acknowledge with "E".
Display
flashes:
„
(+
”
The unit is saving changes made to
the operating parameters.
Once the save sequence has been comple-
ted the unit returns to displaying the mea-
sured values.
Effect
Cause
Cure
No measu-
red value
display
There is no circuit connected.
Please check the wiring to the unit.
Unit defective.
Please exchange the unit.
Display defective.
Please exchange the unit.
The 7 seg-
ment dis-
play shows
an incor-
rect/inac-
curate mea-
sured value
Measured input incorrectly set up.
Change set up in operating menu.
Sensor calibration faulty.
Compensate error using the offset.
Offset incorrectly set up.
Check offset.