3.4.7       RESPONSE TIME 

50 mS 

3.5     ELECTRICAL DATA 

Configuration        

4-arm Wheatstone bridge strain gauge with internal amplifier

Output Signal        

2-wire 4 - 20 mA

Saturation Levels        

3.8 mA and 20.5 mA 

Fail Safe Levels      

3.6 mA for Low Level 

> 21mA for High Level

Current Consumption  

< 25 mA 

Supply Voltage       

13 - 30 VDC for PTB ATEX IS and FM XP approved models 

13 - 32 VDC for non-approved models 

Note: Transmitter incorporates overvoltage protection and reverse

polarity protection and will not operate if inputs are reversed. 

Sense Resistor Load Line 

250 ohms minimum for HART communication 

3.6     TEMPERATURE INFLUENCE 

ELECTRONICS HOUSING 

Operating Temperature Range        

-29°C to +85°C

Compensated Temperature Range 

-17°C to +65°C

Содержание SPX228

Страница 1: ...lab to production providing a window into the process 1 Intrinsically safe and Explosion proof pressure transmitters with integrated amplifier for use in hazardous environments Operating Manual SPX P...

Страница 2: ...at this time Allow time for the transmitter temperature to equalize to the process temperature This will help eliminate thread galling and ease removal later There should be NO pressure applied at th...

Страница 3: ...nsure on how to do this refer to Connecting the HART Handheld Communicator Figure 6 1 3 Power on HART Communicator See HART Command tree on the following page for reference 4 From the Main Menu a Ente...

Страница 4: ...3 Field Device Inf kg Sqcm 2 Rerange MPa 5 Review 1 Model 3 PV Unit KPa 2 Manufacturer 3 Dev id 4 PV Rnge unit psi 4 Distributor bar 4 PV LRV 1 PV LRV 5 Poll addr 5 PV Min span kg Sqcm 2 PV URV 6 Num...

Страница 5: ...Contents 1 GENERAL 6 2 NOTES ON SAFETY 11 3 TECHNICAL DATA 16 4 TRANSPORT DELIVERY 20 5 INSTALLATION 21 6 COMMISSIONING 23 7 MAINTENANCE 35 8 TROUBLESHOOTING 36 9 APPROVALS CERTIFICATES 37 10 APPENDIX...

Страница 6: ...ticular to the notes on safety Following the safety instructions will help to prevent accidents defects and malfunctions DYNISCO will not be held liable for any injury loss or damage resulting from fa...

Страница 7: ...o safety Risk of destruction or damage to equipment machines or installations General danger to life or limb Specific danger to life or limb Related to ATEX Intrinsic Safety requirements Related to Fa...

Страница 8: ...criptor EEPROM Electrically Erasable Programmable Read Only Memory FS Full Scale HART Highway Addressable Remote Transducer LRV Lower Range Value PT Pressure Transmitter PV Primary Variable Pressure S...

Страница 9: ...the balance of the bridge The amount of imbalance is directly proportional to the applied pressure This completes the translation of pressure applied to the diaphragm into a usable electrical signal T...

Страница 10: ...es Over voltage protection shall be implemented as mentioned in EN 60079 14 When planning machinery and using one of the units from the SPX Family follow the safety and accident prevention regulations...

Страница 11: ...ction of the PT must be done by specialists with EMC training following all applicable regulations and in pressure less voltage free intrinsically safe condition with the machine switched off The mach...

Страница 12: ...pressure transmission fluid below the measuring diaphragm See Figure 1 1 This temperature can be verified by measuring the surface temperature at the base of the electronics housing For category 1 Zo...

Страница 13: ...sive devices like switches or resistors may be connected between the RCAL and RCAL signals Connection of any active electronic circuits or voltage or current sources is not allowed Certain configurati...

Страница 14: ...2 Open Gage 3 Input over a predefined customer selectable at time of order threshold The Guardian Series transducer has been designed to provide a protective measure This has been done by the avoidanc...

Страница 15: ...transducer that is over the safe level but less than the maximum pressure Verify that the protective measure is initiated to take the machine to a safe operating condition Use of qualified personnel...

Страница 16: ...228 0 25 Gage Pressure PSI Non Approved 1 8 27 NPTF Internal PT02A 10 6P Connector Standard Wiring PSI Option Code 4 20mA HART Comms 5000 228 1 N G A AA 0 P 21 B XXXX Note s 1 Review section 3 4 Perf...

Страница 17: ...del Range Accuracy of FS 2280 15 72 500 PSI 0 50 2281 15 72 500 PSI 0 25 2282 5 10 000 PSI 0 15 3 4 2 RESOLUTION 0 035 full scale 50 F S average resolution 3 4 3 REPEATABILITY 0 10 of full scale 3 4 4...

Страница 18: ...afe Levels 3 6 mA for Low Level 21mA for High Level Current Consumption 25 mA Supply Voltage 13 30 VDC for PTB ATEX IS and FM XP approved models 13 32 VDC for non approved models Note Transmitter inco...

Страница 19: ...0 02 FS F max 0 04 FS C max 3 7 EMC REQUIREMENTS The SPX Conforms to CE in accordance with EMC directive See Declaration of Conformity for more details 3 8 MATERIALS Standard Diaphragm 15 5PH Mat No 1...

Страница 20: ...precautions 4 1 TRANSPORT PACKING TRANSPORT DAMAGE Do not let the SPX be damaged by other items during transit Use only the original packaging Report transport damage to DYNISCO immediately in writin...

Страница 21: ...hould be NO pressure applied at this time Always use a torque wrench applied to the designated wrench flats while screwing the transmitter in and out Do not apply the tool to the housing or housing se...

Страница 22: ...on 5 3 CONNECTION ASSIGNMENTS The device must be connected to a certified power supply Each unit will include a primary 4 20mA output The unit may also have one of the options listed in the table bel...

Страница 23: ...ver Sections 6 3 through 6 8 and 6 11 may be skipped 6 1 WHY A TRANSMITTER MUST BE REZEROED The transmitter output must be nulled at zero pressure after installation when the machine has stabilized at...

Страница 24: ...r the transmitter span can be adjusted via the Span actuator This is performed by applying a known calibrated full scale pressure to the transmitter and depressing the Span actuator in a certain seque...

Страница 25: ...ure has stabilized and the SPX electronics housing has been permanently installed When the zero trim function is selected HART Quick key 1 2 5 1 3 1 the output will be corrected to reflect zero pressu...

Страница 26: ...imum of 250 Ohms resistance must be present in the loop The HART Communicator does not measure loop current directly The HART Communicator can interface with the SPX anywhere along the 4 20 mA cable a...

Страница 27: ...1 2 5 1 3 2 Output should now equal full scale pressure 11 If Transmitter Output Damping is required set PV Damping Fast Key 1 3 5 to the appropriate value 12 Press the left arrow key until the HART...

Страница 28: ...lue of the analog output NOT the value the transmitter would have if the sensor had not detected the failure Special Conditions and the Corresponding Analog Output Condition Alarm Value fail safe EEPR...

Страница 29: ...for the 4 mA and 20 mA points LRV and URV respectively to be adjusted so that output resolution can be improved A Re range or Turndown ratio of 6 1 is possible Accuracy specifications remain dependent...

Страница 30: ...ound in Fast Key 1 4 1 5 Rerange LRV By Applying Pressure 1 2 5 1 1 1 1 This is done by applying a known pressure and initiating the procedure so that the transmitter adopts the pressure as the 4 mA p...

Страница 31: ...of Full Scale FS After selecting a new pressure unit all entries for pressure are recalculated to the new unit using the following conversion rules 1 psi 0 068947 Bar 0 0068947 MPa 0 070309 kgf cm Tag...

Страница 32: ...ode includes Pressure Variable Analog Output value Pressure in of range Access to other information can still be obtained through normal HART Comms 6 9 RESETTING TO FACTORY DEFAULT SETTINGS The factor...

Страница 33: ...larm Level to its value at shipment 4 Remove all Pressure Damping 5 Clear all Sensor and Analog Output Trim values 6 Clear Burst Mode 7 Restore the Address to Zero 8 Restore the Rcal option to its val...

Страница 34: ...Trim 1 2 5 1 3 2 Perform Upper Sensor Trim 1 2 5 1 3 3 Recall Factory Trim 1 2 5 3 Set Rcal 1 2 5 1 4 1 Set Tag 1 3 1 Set PV Unit 1 3 2 Set Lower Range Value LRV PV 1 3 3 1 Set Upper Range Value URV...

Страница 35: ...OR STEEL WIRE BRUSHES ETC DO NOT CLEAN THE SCREWED IN SECTION OF THE SPX WITH HARD OBJECTS THIS WILL DAMAGE THE SPX ALWAYS USE A TORQUE WRENCH APPLIED TO THE DESIGNATED WRENCH FLATS DO NOT APPLY THE...

Страница 36: ...is Low or High 1 Check Test Equipment 2 Check Port Pipe for Blockage or Solidified Plastic 3 Perform Full Sensor Trim Pressure Variable Reading is Erratic 1 Check Port Pipe for Blockage or Solidified...

Страница 37: ...ndow into the process 37 9 APPROVALS CERTIFICATES 9 1 CE DECLARATION OF CONFORMITY 388 9 2 EC TYPE EXAMINATION CERTIFICATE 400 9 3 EX FM CERTIFICATE OF COMPLIANCE 445 9 4 SAFETY INTEGRITY AND PERFORMA...

Страница 38: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 38 9 1 CE DECLARATION OF CONFORMITY...

Страница 39: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 39...

Страница 40: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 40 9 2 EC TYPE EXAMINATION CERTIFICATE...

Страница 41: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 41...

Страница 42: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 42...

Страница 43: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 43...

Страница 44: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 44 9 3 EX FM CERTIFICATE OF COMPLIANCE...

Страница 45: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 45...

Страница 46: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 46...

Страница 47: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 47...

Страница 48: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 48...

Страница 49: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 49 9 4 Safety Integrity and Performance Level Applications...

Страница 50: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 50...

Страница 51: ...button Enable Enable RW Enabled Disabled Factory Default LRV 0 RO Lower Sensor Limit 0 04 full scale of SPX T RO Message Text HTTP WWW DYNISCO COM RW PV Minimum Span Value Factory Default PV_URV divi...

Страница 52: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 52 11 APPENDIX 2 Menu Tree Software Revision 100 Menu Tree for software revision 100...

Страница 53: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 53...

Страница 54: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 54...

Страница 55: ...P N 974153 Rev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 55...

Страница 56: ...ev 072016 ECO 46503 www dynisco com From lab to production providing a window into the process 56 12 DYNISCO CONTACT INFORMATION Please visit our website for up to date contact information www dynisco...

Отзывы: