28
C
ONFIGURA
TION
Attribute
Attribute
Attribute
Attribute
Attribute
Access
Access
Access
Access
Access
Description
Description
Description
Description
Description
Dat
Dat
Dat
Dat
Data
a
a
a
a T
TT
TType
ype
ype
ype
ype
V
V
V
V
Value
alue
alue
alue
alue
ID
ID
ID
ID
ID
Rule
Rule
Rule
Rule
Rule
(Decimal)
(Decimal)
(Decimal)
(Decimal)
(Decimal)
11
Get
Gain
UINT
Factory use only
12
Get
Unity Gain Reference
UINT
(UGR) Decimal scale
factor used to convert
PV to “real world”
pressure. Pressure =
PV / UGR. Note that the
UGR is fixed for each
transducer range.
13
Get
AlarmTripPointHigh
UINT
Valid Range:
(ATPH) If AlarmEnable
is set and PV >= ATPH,
(WTPH - Alarm Hysteresis)
TripAlarmHigh is set
<= ATPH <= Overrange
(see Attr 05).
TripAlarmHigh is cleared
once PV <= ATPH –
AlarmHysteresis
(see Attr 15)
14
Get/Set
AlarmTripPointLow
UINT
Valid Range:
(ATPL) If AlarmEnable
is set and PV <= ATPL,
Underrange <= ATPL <=
TripAlarmLow is set
(WTPL - AlarmHysteresis)
(see Attr 05).
TripAlarmLow is cleared
once PV >= ATPL +
AlarmHysteresis (see Attr 15).
15
Get/Set
AlarmHysteresis
UINT
Valid Range:
The amount by which
PV must recover to clear
AlarmHysteresis <=
either TripAlarmHigh or
(ATPH - WTPH) or
TripAlarmLow.
(WTPL - ATPL)
16
Get/Set
AlarmSettlingTime
UINT
Units are in milliseconds
The time that the PV
must exceed the trip point
before TripAlarmHigh or
TripAlarmLow is set.