Dynamic Flow Computers
SFC332L Manual
Quick Start
— 1-25
Date: 8/1/2019
RS-232 Connection:
The RS-232 is not located on the terminal board. The RS-232 is a green 5-pin terminal block with screw
type connector located on the display side of the enclosure. Go to
Wiring
|
RS-232.
Termination
jumpers for the RS-232 are located at the top corner of the board on the same side of the RS-232 connector.
The two jumpers at the top are for terminating the transmit line and below it is the receive line.
The RS-232 port can be used for printing reports, Modbus communication, or interfacing
to the configuration program. If the port is configured as printer port in the flow
computer Note: Twisted shielded cable is required.
WARNING: When the RS-232 terminal is used with a modem, external protection on the
phone line is required. Jumper DTR to DSR, RTS to CTS, and disable software
handshake on the modem RS232 connection