41
8.6
FOLLOWER OR POTENTIOMETER SIGNAL NOT CHANGING SETPOINT
•
Verify the control is in the right mode. “AUTO” mode corresponds to an automatic follower
signal. “REMOTE” mode corresponds to a signal that is external to the keypad.
•
Check to see if any external connections into TB2 are improperly grounded. Recheck the
wiring diagrams seen in Figures 8 through 13. If multiple signals are wired into TB2, try
disconnecting signals one by one to eliminate possible issues.
•
Verify the signals are present at TB2.
8.7
UNSTABLE SPEED
•
Adjust the PID loop parameters in Menu B.
8.8
SPEED ON DISPLAY IS DIFFERENT THAN ACTUAL SPEED
•
Verify that the Tach Pulses/REV setting in Menu A, Parameter 5 matches your mechanical
unit. If unknown, try another setting and see if the displayed speed is closer to the actual
speed.
8.9
SCREEN IS FROZEN AND/OR HAS UNFAMILIAR CONTENT
•
Try resetting the EC 2000 either by pushing “SW1” on the 15
-1200-1 board or by removing
all TB2 connections and placing a jumper between TB2-32 and TB2-29.
8.10
SCREEN IS LIT, BUT NOTHING IS DISPLAYED
•
Try resetting the EC 2000. If the issues persists, check to see if the keypad cable is inserted
correctly or not damaged.
8.11
LOCAL/REMOTE KEY DOES NOT WORK
•
Check to see if “LOCAL/REM ENABLE” is enabled in Menu A, Parameter 12.
8.12
DRIVE SLOWER THAN DESIRED
•
Check to see if the clutch current limits are properly set in Menu A, Parameter 4.
Содержание EC 2000
Страница 6: ...6 Figure 2 EC 2000 Keypad Display ...
Страница 12: ...12 SECTION 5 INSTALLATION Figure 3 Standard Panel Dimensions Not to scale ...
Страница 13: ...13 Figure 4 Keypad Cutout Template to Scale Inches ...
Страница 14: ...14 Figure 5 Keypad Dimensions to Scale ...
Страница 17: ...17 Figure 8 Start Stop Jog E STOP Wiring Figure 9 Setpoint Reference Manual Auto Mode Wiring ...
Страница 18: ...18 Figure 11 Current Transformer Wiring for Torque Limiting Figure 10 Programmable Analog Outputs Wiring ...
Страница 19: ...19 Figure 13 Speed Pickup Wiring Figure 12 Preset Speeds PLC Run Wiring ...