COIL RESISTANCE CHECK

REMOVE THE
MAGNET COIL
CONNECTOR
FROM THE 
CIRCUIT BOARD TO
PERFORM THE COIL TEST

PROPER COIL RESISTANCE SHOULD BE 

FROM POINTS 1 TO 3, ~ 53 OHMS
FROM POINTS 2 TO 4, ~ 53 OHMS

ELECTRICAL SPECIFICATIONS

OPERATING VOLTAGES

12 OR 24 VAC / VDC

CURRENT CONSUMPTION, ALL MODELS

12 VAC / VDC - 0.44 A 
24 VAC / VDC - 0.22 A

Notes:

1. 

This lock may accept any one of 4 different input voltages and be furnished 

 

with a combination of options.  Refer to page 1 for option location and 

 

pages 2 and 3, fi gure A thru E, for wiring instructions that apply to

 your 

specifi c installation.

2. 

For additional system wiring information, refer to the installation 

 

documentation furnished with the external hardware and / or

 

peripheral devices (I.E. power supply, station controls, keypad, card

 

readers, etc.) supplied by DynaLock and / or others.

3000 / 2000 TD OPTION
(TIME DELAY)

    

12 / 24 

    VAC / VDC
    INPUT

NORMALLY CLOSED STATION CONTROL(S), 
I.E. PUSHBUTTONS, KEYSWITCHES, ETC.
WIRE MULTIPLE CONTROLS IN SERIES AS 
SHOWN.

FIG. E

TIME DELAY OPERATION
1. 

PUT A JUMPER ACROSS TERMINALS 3 & 4.

2. 

MOMENTARILY OPENING THE CONTACT(S) AND

 

INTERRUPTING THE POWER ON 1 & 2 UNLOCKS THE DOOR.

 

THE DOOR WILL RELOCK AFTER THE DURATION OF THE TD.

3. 

SEE PAGE ONE FOR THE LOCATION OF THE TIMER 

 ADJUSTMENT 

CONTROL.

4. 

TIME ADJUSTMENT RANGE IS ONE (1) TO EIGHTY (80) SECONDS.

3

 

ADD

JUMPER

1

     2     3      4         5     6      7     8     9     10

Содержание 3000 Series

Страница 1: ...Rating SPDT 0 5A DYNASTAT CONNECTOR TIME DELAY ADJ CW to increase Range 1 80 seconds see fig E 3000 2000 series mag lock accepts 12 24 VAC DC Circuit board shown fully loaded with every option ATS SWITCH LED 3 Pin Plug LOCK HOUSING Wht Wht 2 Pin Plug not polarized COIL CONNECTOR PLUG The Coil Connector is not polarized and may go on in either direction Blk Blk Wht Wht 4 Pin Plug COIL PLUG RECEPTAC...

Страница 2: ...ICATORS NOT INCLUDED 12 24 VAC INPUT NORMALLY CLOSED STATION CONTROL S I E PUSHBUTTONS KEYSWITCHES ETC WIRE MULTIPLE CONTROLS IN SERIES AS SHOWN NORMALLY CLOSED STATION CONTROL S I E PUSHBUTTONS KEYSWITCHES ETC WIRE MULTIPLE CONTROLS IN SERIES AS SHOWN FIG D 3000 2000 DYNASTAT OPTION 3000 2000 DSM OPTION DOOR SECURE DOOR UNSECURE NOTES 1 DYNASTAT CONTACTS RATED 1A MAXIMUM 2 INDICATORS NOT INCLUDED...

Страница 3: ... installation 2 For additional system wiring information refer to the installation documentation furnished with the external hardware and or peripheral devices I E power supply station controls keypad card readers etc supplied by DynaLock and or others 3000 2000 TD OPTION TIME DELAY 12 24 VAC VDC INPUT NORMALLY CLOSED STATION CONTROL S I E PUSHBUTTONS KEYSWITCHES ETC WIRE MULTIPLE CONTROLS IN SERI...

Страница 4: ...L CONTACT BETWEEN THE MATING SURFACE OF THE LOCK AND ARMATURE MAGNET OVERHEATS LOCK SET FOR 12V WITH VERIFY THAT JUMPERS MATCH AND OR DRAWS EXCESS 24V APPLIED INPUT VOLTAGE SEE TOP OF PAGE 2 CURRENT POSSIBLE SHORTED COIL PERFORM THE COIL RESISTANCE CHECK REFER TO BOTTOM OF PAGE 3 DYNASTAT BOND SENSOR INSUFFICIENT SUPPLY VOLTAGE CHECK SUPPLY FOR PROPER INPUT NOT INDICATING DOOR VOLTAGE SHOULD BE WI...

Страница 5: ...ngle models and 0 32 Amps for double models Damage may occur if input voltage exceeds 16V AC DC Do not attempt operation at higher voltages GENERAL INFORMATION BASIC INPUT POWER WIRING 3000 2000 x LP BASIC 12 VDC INPUT 12VDC INPUT FIG A NORMALLY CLOSED STATION CONTROL S I E PUSHBUTTONS KEYSWITCHS ETC WIRE MULTIPLE CONTROLS IN SERIES AS SHOWN 1 2 3 4 5 6 7 8 9 10 3000 2000 x LP BASIC 12 VAC INPUT 1...

Страница 6: ...ION NOTE TO PROTECT OTHER ELECTRONIC DEVICES IN SYSTEM CONNECT THE SUPPLIED MOV ACROSS THE LEADS AS SHOWN ABOVE NOTE TO PROTECT OTHER ELECTRONIC DEVICES IN SYSTEM CONNECT THE SUPPLIED MOV ACROSS THE LEADS AS SHOWN ABOVE JUMPER WIRING INSTRUCTIONS DynaLock 705 Emmett Street Bristol CT 06011 2728 Phone 860 582 4761 Fax 860 585 0338 SERIES 2000 3000 x LCB ELECTROMAGNETIC LOCK ...

Отзывы: