3
//
Max. frequency against input voltage
0.01
0.1
1
10
100
0.001
0.01
0.1
1
10
100
1000
10000
100000
Frequency [Hz]
Input v
o
lt
a
g
e
[V
e
ff]
Trigger: 500mVpp
Trigger: 20mVeff
O.K.
NOT O.K.
3.2 Inputs
3.2.1 Analog Sensor connection (Sign)
Frequency range (-3dB)
0.01 Hz / 35 kHz
Input impedance
30 K
Input voltage
•
Max.
80V
rms
•
Signal voltage [V
pp
] 0.5 1 2.5 5 10 20
Min. pulse width [µs]
2000
667
333
200
166
125
Minimum positive pulse
width - digital signals Input
voltage
Integrated pull-up
820 Ohm to +V of the sensor supply (with Jumper J1)
Trigger level
adaptive Trigger level.
Configurable with Jumper J2:
•
250mV … 6.5V (>500mVpp) [Factory configuration]
•
28mV … 6.5V (>20mV
rms
)
Screen
A terminal is provided for the sensor cable screen. This terminal is connected to
the sensor supply 0V. (0VS)
Sensor monitoring
1 of 3 settings may be configured via software:
•
No Sensor Monitoring
•
Monitoring of powered sensors
[Also for 2 wire sensors supplied via the Pull-up resistor (Jumper J1) ].
Æ
The sensor is considered to be defective if the sensor current
consumption falls outside of I
min
and I
max
.
I
min.
= 0.5…25 mA
I
max.
= 0.5…25 mA
•
Monitoring of non powered sensors
[For 2 wire sensors such as electromagnetic sensors.]
Æ
The sensor is considered to be defective if the circuit is disconnected.