62
/*$PAGE*/
; ************** USER TRIPS ***************
; USER-defined TRIPs allow mapping from
; any Analog Input channels (or RPM input)
; to an additional SCANNER rly. Thus, any
; AI ch may be monitored for application-
; specific purposes in addition to monitoring
; for ALARM & SHUTDOWN conditions.
;
; Example: An exhaust temperature sensor is
; connected to Analog Input #4. It
; is set to ALARM at 400 degrees and
; to SHUTDOWN at 450 degrees. In
; addition, it is used to TRIP Spare
; Rly #1 at 175 degrees to engage an
; engine cooling fan. Thus, a USER-
; defined TRIP may be setup to map
; AI Ch #4 to User TRIP #1 for Class
; A Over with a TRIP th of 175.
;
; 63000.49=0 ; Class A Over
; 63001.49=175 ; 175 degrees
; 121.1=4 ; AI Ch #04
; 120.1=1 ; Rly #1
; USER TRIP CLASS *************************
; 0 Class A Over (dflt)
; 1 Class B Over
; 2 Class C Over
; 3 Class A Under
; 4 Class B Under
; 5 Class C Under
63000.49=0 ; <USER TRIP #01>
63000.50=0 ; <USER TRIP #02>
63000.51=0 ; <USER TRIP #03>
63000.52=0 ; <USER TRIP #04>
63000.53=0 ; <USER TRIP #05>
63000.54=0 ; <USER TRIP #06>
63000.55=0 ; <USER TRIP #07>
63000.56=0 ; <USER TRIP #08>
63000.57=0 ; <USER TRIP #09>
63000.58=0 ; <USER TRIP #10>
; USER TRIP TH ****************************
; TRIP threshold; TRIP value required to
; fault channel (in channel units).
63001.49=0 ; <USER TRIP #01>
63001.50=0 ; <USER TRIP #02>
63001.51=0 ; <USER TRIP #03>
63001.52=0 ; <USER TRIP #04>
63001.53=0 ; <USER TRIP #05>
63001.54=0 ; <USER TRIP #06>
63001.55=0 ; <USER TRIP #07>
63001.56=0 ; <USER TRIP #08>
63001.57=0 ; <USER TRIP #09>