6
1.2 Specifications
1.
Input Channels
:24 Thermocouple (J,K,T, or E), 0 – 5V, or 4 – 20mA (On-Board 100
Ohm resistor provided on Channels 1 through 8).
Note: All Thermocouples have “Open-Thermocouple Detection”
2.
Channel Scan Rate
: Programmable (50mS Minimum)
3.
Relay Outputs
: 4 Relays, SPDT, rated @ 5A/24VDC, 1A/120VAC, and 0.5A/220VAC
4.
Input Power
: 9 – 38 VDC, 0.8A Max.
5.
Sensor Power Out
: +5VDC CJC Sensor Power, +8VDC RPM Sensor Power
6.
Display
: Backlit, 4 Line x 20 Character Alphanumeric Display with large 0.36”
Characters
7.
Communications
:
Hardware: RS-232
Software: Dynalink Laptop Configuration Software and Modbus RTU.
8.
Rear Connections
: All “DB - Style” Connectors on rear of unit. All field Wiring is done
via DIN-RAIL mounted Terminal Blocks.
9.
Operating Temperature Range
: -20 to +80C
10.
Certification
: CSA Class I, Div.2, Groups A, B, C, D
Содержание SC-2124
Страница 4: ...4 1 1 Packaging Front View 6 55 8 50 ...