Configuration
33
© 2012 DynaGen Technologies Inc.
TOUGH Series User Manual
4.4.1
Auxiliary Sensors
The following section relates to the functionality of Auxiliary Sensors 1 and 2. These sensors have
advanced functions and customization.
SETTING
DESCRIPTION
Signal Source
Determines the port the sensor is connected to.
Mode Select
Determines how the controller will act depending on the reading of the
sensor. See below for more information.
Trim Offset
Use this setting to add or subtract units from the reading of the sensor
in the case that there are errors in the readings.
Mode Settings
Settings that relate to the specific mode. See below.
Setpoints
Configures the points at which the controller will detect a warning or
failure based on the sensor reading.
Mode Select Options
Mode Select determines how the controller will interpret and act upon the Aux Sensor data. The
controller can monitor for faults, turn on outputs, or start the engine. Refer to the 'Scenarios' section on
the next page for further information on how these settings function.
SETTING
DESCRIPTION
Fault Monitor
Monitors for warnings and failures.
Output on Low
If readings drops below Start Level, turn on switched output.
Output on High
If readings rises above Start Level, turn on switched output.
Start on Low
If readings drops below Start Level, auto start the engine.
Start on High
If readings rises above Start Level, auto start the engine.
WARNING
: When using a mode other than 'Fault Monitor' , the controller will not detect
warnings and failures for this sensor.