For example when the speed is disconnected it takes approximately 2.5 s for the speed sensing to record 0 RPM when the speed
sensing is set to a magnetic input at a speed of 3200Hz/1800RPM. This is 4.5 s including the 2 s for the false restart delay. So if
the desired monitoring period is 10 s, the False Check setting should be set to 15 s.
4.5.1.3 OFF Button Function
The OFF button on the front panel of the controller can be configured to function in 3 different ways while the engine is running. The
table below describes each of these functions:
Function
Description
Cooldown
This function causes the controller to go into cooldown. Pressing the OFF button
again will cause the engine to shut down.
Shutdown
This function bypasses Cooldown and causes the engine to shut down.
Force Cooldown
This function causes the controller to activate the cooldown process. Pressing the
OFF button will have no affect as the controller is forcing the engine to perform a full
cool down.
WARNING
: If the controller receives a command to start from the remote start or front panel run button while in
Cooldown, it will leave the Cooldown mode and go back to Running mode.
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...