background image

- 3 - 

Interior Connections

 

1.   Open the unit by removing the four (two per side) Phillips head screws to remove the cover. 
 
2.  Push the end of the cable through the control wire feed 

through on the rear of the unit. 

 
3.  Three wire connections for the wire are made on the 

green header (G-1-2). Loosen each terminal screw until it 
is near flush with the top of the connector block as shown 
to the right. 

 
4.  Strip approximately 1/4" insulation from the three 

conductor wire ends. 

 
5.  Connect each wire to a terminal (G-1-2) by sliding the wire completely into the wire connection 

hole. Using a small flat blade screwdriver, tighten the associated screw until the wire is firmly 
gripped in place as shown below. 

 
 
 

 

 
 
  

 
 
Take caution to ensure just the wire is clamped in place, not the wire's insulation which would cause an open 
or intermittent connection. Do not over tighten the screw so much that the wire is cut instead of being firmly 
gripped. Use the included Ty-Wrap on the inside of the unit to hold the cable from pulling outward as shown 
above. 
 
Control lines normally use good quality CAT5e cable (3 twisted pairs of 24 AWG wire) for runs up to 1000 
feet.  Typical DX Engineering control lines requirements are +12 VDC at 25 milliamps. Depending on the 
number of control lines needed (usually 3) you can double up the twisted pairs of CAT5e cable, or use 
control wire that is at least 22 AWG, allowing runs up to 1500 feet. If you use a cable with more conductors, 
it is a good idea to tie the unused conductors to ground. For longer runs of control cable, use a line loss 
calculator to ensure you supply the proper control levels needed. 
 
Approximate BCD Control Line Lengths. 

 

Minimum Copper 

Wire Gage (AWG) 

Length 

24 

1,000 feet 

22 

1,500 feet 

20 

2,000 feet 

 

When connecting the cable to the DX Engineering Dual Vertical Array system, ensure your cable is wired 
the same way at the other end to avoid un-necessary troubleshooting (G-1-2). Use the chart on the next page 
to record which color wire is connected to each terminal connection.  
 

 

Отзывы: