1.0 INTRODUCTION
The Model 150P Valve Positioner is a cam characterized, double-acting, pneumatic valve positioner
that accepts a 3-15 or 3-27 psig input signal and converts it to a pneumatic output to position a con-
trol valve actuator. The Positioner can be used with either rectilinear or rotary, single or double acting
actuators. A selection of cam profiles is available.
A high-gain, piloted spool valve is used to load the actuator for positioning in response to an input sig-
nal. Mechanical feedback is provided by a characterized cam.
No additional parts are necessary to change between single or double acting actuators or
direct/reverse action.
1.1 MODEL DESIGNATION
Each Positioner has a nameplate identifying the model number. The following decodes the model num-
ber on the nameplate. Before installing or servicing a Positioner, review the nameplate information.
TYPE
150N Pneumatic Valve Positioner
ACTION
L Rectilinear
R Rotary
CAM PROFILE
1 Standard Linear
2 Standard Rotary
INPUT
1 3 to 15 PSIG
2 3 to 27 PSIG
150N L 1 1 SAMPLE MODEL NUMBER
9/94
BULLETIN F-56
PAGE 3
Bulletin F-56 6/27/05 9:37 AM Page 3
Содержание W.E. Anderson 150N Series
Страница 7: ...BULLETIN F 56 PAGE 7 FIGURE 2 1 Cam and Associated Hardware Bulletin F 56 6 27 05 9 37 AM Page 7...
Страница 13: ...BULLETIN F 56 PAGE 13 FIGURE 2 3 Standard Cam Characteristics Bulletin F 56 6 27 05 9 37 AM Page 13...
Страница 14: ...PAGE 14 BULLETIN F 56 FIGURE 2 4 Cam Installation A Side Example Bulletin F 56 6 27 05 9 37 AM Page 14...
Страница 15: ...BULLETIN F 56 PAGE 15 FIGURE 2 5 Cam Installation B Side Example Bulletin F 56 6 27 05 9 37 AM Page 15...
Страница 17: ...BULLETIN F 56 PAGE 17 FIGURE 3 1 Calibration Bulletin F 56 6 27 05 9 37 AM Page 17...
Страница 21: ...BULLETIN F 56 PAGE 21 FIGURE 4 1 Schematic Bulletin F 56 6 27 05 9 37 AM Page 21...