BACnet Communication Protocol Objects
Device Object
Analog Input - Pressure
This object represents the current pressure reading in the selected unit of measure.
The pressure unit is set via the units property and is independent of the display unit.
Supported pressure units:
• inches-of-water(58)
• feet-of-water*(530)
• millimeters-of-water(206)
• centimeters-of-water(57)
• pounds-force-per-square-inch(56)
• inches-of-mercury(61)
• millibars(134), pascals(53)
• hectopascals(133)
• kilopascals(54)
• ounce-force-per-square-inch*(531)
*Non-standard unit
Analog Value - Velocity
This object represents the current velocity reading in the selected unit measure. The
velocity unit is set via the units property and is independent of the display unit.
Supported velocity units:
• feet-per-minute(77)
• meters-per-second(74)
Analog Value - Flow
This object represents the current flow reading in the selected unit measure. The flow
unit is set via the units property and is independent of the display unit.
Supported flow units:
• cubic-feet-per-minute(84)
• cubic-meters-per-hour(135)
Analog Value - Peak
This object represents the maximum process value measured since the last power
cycle or reset. The unit of measure matches the selected process value. This value
cannot be reset remotely.
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
System Status
Vendor Name
Vendor Identifier
Model Name
Firmware Version
Application Software
Version
Location
Description
Protocol Version
Protocol Revision
Protocol Services
Supported
Protocol Object Types
Supported
Object List
Maximum APDU Length
Accepted
Segmentation Supported
APDU Timeout
Number of APDU Retires
Max Master
Max Info Frames
Device Address Binding
Database Revision
Property List
Serial Number
607127
“DHC 607127”
Device
Operational
“Dwyer
Instruments, LLC.”
607
“DHC-xxx-xxx”
“x.x”
“x.x.x”
“”
“”
1
16
See PICS
See Table Above
See Table Above
480
No Segmentation
0
0
127
1
{}
0
This Table
“xxxxxx”
BACnet Object Identifier
Character String(32)
BACnet Object Type
BACnet Device Status
Character String
Unsigned
Character String
Character String
Character String
Character String(32)
Character String(32)
Unsigned
Unsigned
BACnet Services
Supported
BACnet Object Types
Supported
BACnet Array
Unsigned
BACnet Segmentation
Unsigned
Unsigned
Unsigned
Unsigned
BACnet Address
Binding
Unsigned
BACnet Array[N] of
BACnet Property
Identifier
Character String
Read/Write
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read
Read
Read
Read
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Units
AI1
“Pressure”
Analog Input
Current Reading
{0,0,0,0}
Normal
No Fault Detected
FALSE
*Model Specific
BACnet Object Identifier
Character String
BACnet Object Type
Real
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
BACnet Engineering Units
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Units
AV1
“Velocity”
Analog Value
Current Reading
{0,0,0,0}
Normal
No Fault Detected
FALSE
*Model Specific
BACnet Object Identifier
Character String
BACnet Object Type
Real
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
BACnet Engineering Units
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Units
AV2
“Flow”
Analog Value
Current Reading
{0,0,0,0}
Normal
No Fault Detected
FALSE
Process Value Unit
BACnet Object Identifier
Character String
BACnet Object Type
Real
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
BACnet Engineering Units
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Units
AV3
“Peak”
Analog Value
Current Reading
{0,0,0,0}
Normal
No Fault Detected
FALSE
Process Value Unit
BACnet Object Identifier
Character String
BACnet Object Type
Real
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
BACnet Engineering Units
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read