Dwyer Instruments DHII Digihelic II Series Скачать руководство пользователя страница 20

MSP1

 and 

MSP2

 (Maintenance Set Point 1 & 2) SUB MENUS

Adjust for the desired maintenance set points when the unit is placed in the maintenance 

mode. The deadband is fixed at 2% of full scale. To enter or leave the maintenance mode, 

press and hold the        for 8 seconds.

ADDR

 (Modbus

®

 Address ) SUB MENU

Modbus

®

communication instrument address. Set from 1 to 247. This number must match the 

address number used by the host computer. 

To obtain the Digihelic

®

II Controller Modbus

®

register list please visit www.dwyer-inst.com

See page 4 for wiring diagram.

WR

 (Modbus

®

 Write Protect) SUB MENU

d.S

- Disables write commands from Modbus

®

. Modbus

®

can only read information from the 

instrument.

En

- Enable write commands from Modbus

®

. Modbus

®

can read information from and write 

information to the instrument. 

ZERO

 and 

SPAN

 (Calibration of Zero and Span) SUB MENUS

The lower display reads 

CAL

in this mode.

ZERO

 Calibration

Note:

For accurate calibration, DO NOT apply any pressure when performing this function.

With the display reading 

ZERO

, press the ENTER key. The upper display will blink. Press 

ENTER again to complete the zeroing of the instrument or press the 

MENU

key to cancel.

SPAN

 Calibration

With the display set to 

SPAN

, apply full scale pressure to the unit. Press the ENTER key. The 

upper display will blink. Press ENTER again to complete the calibration or press the 

MENU

key 

to cancel.

SP/AL

S

SP

SP/

SP/A

SP/AL

   

 

RST

PAGE 1 OF 12

8

RST

PAGE 1 OF 12

8/

RST

PAGE 1 OF 12

8/2

RST

PAGE 1 OF 12

8/25

RST

PAGE 1 OF 12

8/25/

RST

PAGE 1 OF 12

8/25/0

RST

PAGE 1 OF 12

8/25/03

©Copyright 2017 Dwyer Instruments, Inc. 

Printed in U.S.A. 6/17

FR# 443434-00 Rev. 4

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание DHII Digihelic II Series

Страница 1: ...etin B 31 Series DHII Digihelic II Differential Pressure Controller Specifications Installation and Operating Instructions www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Страница 2: ...TING HOLE PATTERN 1 5 16 33 3 17 64 83 4 1 8 105 WIRING TERMINAL ACCESS 4 23 32 120 3 7 16 87 12 1 45 64 43 18 1 17 32 38 61 4 23 32 120 45 64 17 78 4X Ø3 16 4 76 CLEARANCE HOLES FOR MOUNTING MOUNTING HOLE PATTERN 1 5 16 33 1 15 16 48 97 25 32 21 18 2 31 32 75 39 1 5 32 29 59 4 9 64 105 17 5 7 32 132 54 BRACKETS ARE OPTIONAL 4 1 8 105 3 17 64 83 8 LOCK WASHER 8 36 SLOTTED MACHINE SCREW OPTIONAL A ...

Страница 3: ...put Signal 4 20 mA DC into 900 ohms max Zero Span Adjustments Accessible via menus Response Time 250 ms dampening set to 1 Display 4 digit backlit LCD 0 6 height LED indicators for set point and alarm status Electrical Connections Euro type removeable terminal blocks with watertight conduit fittings for 1 2 watertight conduit Process Connections 1 8 female NPT Enclosure Rating Designed to meet NEM...

Страница 4: ...SWITCH Device receiving 4 20mA signal Check specific REMOTE RESET SWITCH Device receiving 4 20mA signal Check specifica REMOTE RESET SWITCH Device receiving 4 20mA signal Check specificat REMOTE RESET SWITCH Device receiving 4 20mA signal Check specificati REMOTE RESET SWITCH Device receiving 4 20mA signal Check specificatio REMOTE RESET SWITCH Device receiving 4 20mA signal Check specification RE...

Страница 5: ... MAY BE DAISY CHAINED THE 120 OHM RESISTOR IS USUAL DIGIHELIC RS485 WIRING TO DAISY CHAIN INSTRUMENTS ON THE RS485 BUSS UP TO 128 UNITS MAY BE DAISY CHAINED THE 120 OHM RESISTOR IS USUALL DIGIHELIC RS485 WIRING TO DAISY CHAIN INSTRUMENTS ON THE RS485 BUSS UP TO 128 UNITS MAY BE DAISY CHAINED THE 120 OHM RESISTOR IS USUALLY ONLY DIGIHELIC RS485 WIRING TO DAISY CHAIN INSTRUMENTS ON THE RS485 BUSS UP...

Страница 6: ...SOME VELOCITY AND FLOW MULTIPLIER DESCRIPTOR VISIBLE WITH SOME VELOCITY AND F MULTIPLIER DESCRIPTOR VISIBLE WITH SOME VELOCITY AND FL MULTIPLIER DESCRIPTOR VISIBLE WITH SOME VELOCITY AND FLO MULTIPLIER DESCRIPTOR VISIBLE WITH SOME VELOCITY AND FLOW RANGES MULTIPLIER DESCRIPTOR VISIBLE WITH SOME VELOCITY AND FLOW R MULTIPLIER DESCRIPTOR VISIBLE WITH SOME VELOCITY AND FLOW RA MULTIPLIER DESCRIPTOR V...

Страница 7: ...hen Visible when Visible when mode mode mode Visible when Visible when Visible when mode mode mode CONTROL MODE C CO CON CONT CONTR CONTRO CONTROL CONTROL CONTROL M CONTROL MO CONTROL MOD CONTROL MODE CONTROL MODE CONTROL MODE C CONTROL MODE CO CONTROL MODE CON CONTROL MODE CONT CONTROL MODE CONTR CONTROL MODE CONTRO CONTROL MODE CONTROL CONTROL MODE CONTROL CONTROL MODE CONTROL M CONTROL MODE CON...

Страница 8: ...TIN SETTING SETTINGS MAIN MENUS SUB MENUS MENUS UNAVAILABLE FOR BI DIRECTIONAL RANGES AND RANGES ABOVE 25 IN W C RST PA RST PA RST PA RST PA RST PA RST PA RST PA RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG E E RST RST RST RST RST RST RST MENU M ME MEN MENU www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Страница 9: ...ETT SETTI SETTIN SETTING SETTINGS MAIN MENUS SUB MENUS RST PA RST PA RST PA RST PA RST PA RST PA RST PA RST PA RST PA RST PA RST PA RST PA RST PA RST PA E E RST RST RST RST RST RST RST MENU M ME MEN MENU www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Страница 10: ...RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG RST PAG E E RST RST RST RST RST RST RST MENU M ME MEN MENU RST RST RST RST RST RST RST www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Страница 11: ... Output Select a Single Set Point 2 Set Points or a Set Point and an Alarm mode of operation d S Display Monitor and adjust display related settings Peak Valley display resolution output and dampening AdU Advanced functions Modify advanced function parameters transmitter output scaling Modbus communication settings Maintenance Set Point settings and calibration www GlobalTestSupply com Find Qualit...

Страница 12: ...to measure pressu is presently set to measure pressur is presently set to measure pressure Units not visible is presently set to measure pressure U is presently set to measure pressure Un is presently set to measure pressure Uni is presently set to measure pressure Unit is presently set to measure pressure Units is presently set to measure pressure Units is presently set to measure pressure Units ...

Страница 13: ...For velocity measurement the following units are available SFPM Standard feet per minute M S Meters per second Table 2 Available Velocity Ranges Note Air velocity and flow readings are based upon standard dry air conditions with an ambient temperature of 70 F and a barometric pressure of 29 92 INHG INPUT RANGE INWC 0 0 1 0 0 25 0 0 5 0 1 0 2 5 0 5 0 10 0 25 SFPM RANGE 0 1266 0 2002 0 2832 0 4004 0...

Страница 14: ...be the manufacturer may specific a K Factor The adjustment range is 0 01 to 2 00 The factory setting is 1 Table 4 FLOr HI Maximum Duct Size English RANGE IN WC 0 1 0 25 0 5 1 2 5 5 10 25 SCFM RANGE 999 9 x 1K 999 9 x 1K 999 9 x 1K 999 9 x 1K 999 9 x 1K 999 9 x 1K 999 9 x 1K 999 9 x 1K MAX DUCT SIZE SQ FT 789 8 499 5 353 1 249 7 157 9 111 7 78 9 49 9 Table 5 FLOr LO Maximum Duct Size Metric RANGE I...

Страница 15: ...entered in millimeters with 1 millimeter resolution ArEA Area select CIR for a circular duct or RECT for a rectangular duct If a circular duct is selected the DIA SUB MENU will be activated If a rectangular duct is selected the XDIM and YDIM SUB MENUS will be activated DIA Diameter enter the diameter of a duct XDIM Enter the X dimension of a duct YDIM Enter the Y dimension of a duct OUt Output MAI...

Страница 16: ...t set points SPAL Single set point and alarm 1SP SP1 Reverse or Direct Acting SUB MENU DIR Direct Relay turns on with increasing pressure REV Reverse Relay turns on with decreasing pressure 0 100 Process Direct Acting Time SPH SPL Relay Inactive Relay Active www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Страница 17: ...ed as a High Alarm Low Alarm or High Low Alarm Alarm settings are all absolute and may be set to anywhere within the range of the instrument The dead bands of the alarms are fixed at 1 of full scale MIN PRESSURE MAX PRESSURE ALHI Relay OFF Relay ON HIGH ALARM FUNCTION MIN PRESSURE MAX PRESSURE ALLO Relay ON Relay OFF LOW ALARM FUNCTION MIN PRESSURE MAX PRESSURE ALLO Relay ON Relay OFF Relay ON HIG...

Страница 18: ...d S Display MAIN MENU PEAK Peak value rESO Resolution VALy Valley value Pd S Process display ZERO Zero DAMP Dampening level PEAK Peak SUB MENU The Peak feature stores the highest pressure reading the instrument has measured since the last reset or power up At power up PEAK is reset to the present pressure reading To manually reset the PEAK value press the RESET key while in the PEAK SUB MENU VALy ...

Страница 19: ...the display from instabilities due to things such as vibration and excessive pressure fluctuations The dampening setting adjusts the amount of readings that are averaged for each display update Adjust the dampening value until the display reads a stable value for the application AdU Advanced MAIN MENU POL Process output low ADDR Modbus address POH Process output high WR Modbus write enable disable...

Страница 20: ...nds from Modbus Modbus can read information from and write information to the instrument ZERO and SPAN Calibration of Zero and Span SUB MENUS The lower display reads CAL in this mode ZERO Calibration Note For accurate calibration DO NOT apply any pressure when performing this function With the display reading ZERO press the ENTER key The upper display will blink Press ENTER again to complete the z...

Отзывы: