1.5 Three Position Selection Switch Wiring

An optional mode selection switch is available with the weatherproof
enclosure. With this switch the user may select either continuous
cleaning, on-demand cleaning, or off. This switch is supplied factory wired
as shown in Figure 4. The switch has a front and rear section. The front
section, consisting of two independant contacts, controls the power to the
board. These contacts must be wired in parallel as shown in the diagram.
The rear section controls the manual override, which when closed will
force the system into a continuousmuct be reconneccted, follow the wiring
diagram. 

Caution:

Do not interconnect the low voltage manual override

leads with the power leads. This will destroy the control board
as well as pose a serious shock hazard

2.0 Programming the DCT1000DC Master Controller

We’ve made it easy to navigate the DCT1000DC.  Menu items can be
accessed simply by pressing the “SELECT” button.  The menu item that
you are currently accessing is indicated by the illumination of an LED.  To
change menu items, all you have to do is push “UP” to increase a value
or push “DOWN” to decrease a value.  There are no keystrokes that you
need to memorize, special combinations, or passwords that are required.

The master controller is equipped with an on board display and
programming information center.  The controller will power-up with the
process indicator illuminated.  If a pressure module is installed, the display
will indicate the measured pressure in inches of water (w.c.); otherwise it
will normally be blank.  

2.1  • Last Output

The Last Output setup selects the last channel to be activated. When first
selected, the display will flash the last output available in the system. With
single board installations, this will be the number of channels installed,
typically 6, 10 or 22. This value becomes more important when multiple
modules are installed. The last output value flashed will be the sum of all
channels available in the system. 

After the last available channel indication has completed, the currently
programmed last channel value is displayed. This value may be changed
using the “UP” and “DOWN” buttons. The minimum value is one while the
maximum value is the maximum number of installed channels, including
all expansion modules.
The default value is the maximum number of channels. Pressing
“SELECT” will change the setup mode to Time Off Setup.

2.2  • Time Off (Sec.)

Time off defines the period of time between solenoid activations when no
channels are enabled. This may be set between one second and 255
seconds. The factory default is 10 seconds. The display will show the
current time off setting when the time off setup mode is entered. The value
may be changed using the Up and Down buttons. Pressing both “UP” and
“DOWN” simultaneously and holding for approximately four seconds will
restore the default value of 10. 

2.3 • Time On (msec)

Time On Setup sets the solenoid on time. The display will indicate the
currently programmed time on setting. This is measured in milliseconds.
Using the “UP” and “DOWN” buttons, the value may be changed. The
value may be set between 10 msec and 600 msec in 10 msec increments.
Pressing the “UP” and “DOWN” buttons simultaneously for approximately
four seconds will restore the factory default value of 100 msec. Pressing
the “SELECT’ button will advance the setup mode to the High Limit setup
if the pressure module is installed. With no pressure module, it will step to
Cycle Delay Setup.

2.4 • High Limit [Only available when DCP connected]

The High Limit Setup, available only with a pressure module installed,
sets the pressure at which the cleaning cycle will begin. This value may
be between zero and the pressure module full scale pressure. Normally,
the High Limit should be above the Low Limit. If, however, the High Limit
pressure is set below the Low Limit, the cleaning cycle will begin when the
High Limit is exceeded and stop when the pressure falls below the High
Limit. The Low Limit in this case will have no effect. Pressing “SELECT”
will change the system to the Low Limit Setup mode.

HIGH

LIMIT COM

LOW

LIMIT

TB3

COM

ALARM

MODE

MAN

OVR

DT

CLN

ALARM

RESET COM

TB2

L1

+

L2

-

SOL

COM

1

2

3

4

5

6

7

8

9

10

(INTERNALLY CONNECTED)

TB1

(10 CHANNEL SHOWN)

DCT1000DC

MASTER CONTROLLER

DAISY

CHAIN

OUT

DAISY

CHAIN

IN

MODE SELECTION SWITCH

REAR

SECTION

FRONT

SECTION

CONTINUOUS

OFF

ON DEMAND

OUTPUTS (3A MAX)

L1 L2

LINE INPUT

4-20 MA
OUTPUT

TB4

4-20 MA

SOURCE

EXTERNAL

INTERNAL ALARM

CONT

ACTS

TB5

Figure 4

Three Position Selection Switch Wiring

(+) (-)

E-97DC:e-97DC  10/5/10  8:27 AM  Page 6

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание DCT1010DC

Страница 1: ...t control applications The contents inside this installation and operating manual will guide you through the features of the DCT1000DC and how they can be applied to get the most out of your dust control requirements SPECIFICATIONS DCT1000DC Timer Controller Output Channels 6 10 22 channels Power Requirements 10 30 VDC Solenoid Supply 3A maximum per channel Fuse 3A 250 VAC Temperature Limits 40 to...

Страница 2: ...ble in 10 w c 2 49 kPa or 20 w c 4 98 kPa ranges which allow for differential process pressure measurement as indicated on the display of the master controller An isolated 4 20 mA readout channel is provided for remote pressure display The 4 20 mA output may be wired either for use with an external power supply and indicator or using the isolated on board 24 volt power supply to power the loop SET...

Страница 3: ... The terminal block is a Euro style connector system that clamps the wire within the connector body The connector will accept wire sizes from 14 to 22 AWG The wire should be stripped to no more than 0 25 inches to avoid shorts To assist you in determining the proper strip length a strip gauge is provided at the lower right corner of the board The connector system used on the DCT1000DC is specified...

Страница 4: ...nstruments Inc in various lengths These are connected to the telephone style connectors at the upper right side of the controller boards One board in the system is designated as the master Subsequent units become slave boards The master controller is the board at the head of the chain having no connection to its daisy chain connector Connect the cable from the daisy chain out connector on connecto...

Страница 5: ... Always install and service this device with the power off and a lockout installed if required Hot plugging the pressure module into an operating system may damage the system or cause the calibration parameters to be erased When installing or removing the module make sure to orient the module straight with board Installing or removing the module at any angle may break the alignment pins Caution Do...

Страница 6: ...he maximum number of installed channels including all expansion modules The default value is the maximum number of channels Pressing SELECT will change the setup mode to Time Off Setup 2 2 Time Off Sec Time off defines the period of time between solenoid activations when no channels are enabled This may be set between one second and 255 seconds The factory default is 10 seconds The display will sh...

Страница 7: ... have also included a number of features that will aid maintenance personnel in diagnosing problems or verifying that the system is operating 3 1 Restoring Factory Defaults The DCT1000DC has been programmed with factory default values that meet most industry operating conditions In the event that you want to restore all of the parameters to the original factory default values 1 Return the master c...

Страница 8: ...ond to the request of the master controller Communication error in the daisy chain interface This will only appear when the master controller is used in conjunction with a slave board The master controller has detected a change in module configuration or a fault in one of the modules If the fault described in Err 4 is not corrected the master controller will reconfigure the modules that are respon...

Отзывы: