Set Point 1 state : Select
dir
or
rE
.
dir
Direct Action. As the input increases the output will increase. Most
commonly used in cooling processes.
rE
Reverse Action. As the input increases the output will decrease.
Most commonly used in heating processes.
If
0ut1
(Page 21) is set for ##
tP
, #
PUL
, or
ProP
, then
S10L
and
S10L
appear. If
0ut1
is set for
0n0F
, then skip
S1rE
.
S10L
Set Point Output Low Limit. Select 0 to 100% but not greater than
S10H
.
This item limits the lowest output value. This is useful for adding a bias to
the process when needed. Factory set to 0 for outputs codes 1, 2, 3, 4,
and 8. Factory set to 20 for output code 5 (20% out put equals 4 mA
output).
S10H
Set Point 1 Output High Limit. Select 0 to 100% but not less than
S10L
for output codes 1, 2, 3, 4, or 8. Select 0 to 102% but not less than
S10L
for output code 5. This item allows setting the maximum output
limit. This is useful with processes that are over powered. Adjustment to
102% allows seeting current output to force a full on condition for output
devices which do not have bias adjustments. Factory set to 100 for all
output codes.
If
0ut1
is set for ##
tP
, #
PUL
, or
ProP
, then skip to
S1LP
below.
If
0ut1
is set to
0n0F
(in Secondary Menu), then the next three menu items can
make the
SP1
and
SP1d
settings act like a high or low alarm set point. See the
information on alarm settings and the cautions and warnings that apply to them on
Pages 30-31.
Note that when Set Point 1 Power Interrupt,
S1P
, is 0n, and Set Point 1 Reset,
S1rE
, is programmed to
HoLd
, the
SP1
output will automatically reset upon a
power failure and subsequent restoration, if the process is below
SP1
.
S1rE
Set Point 1 Reset. Select
0n0F
or
HoLd
.
0n0F
Output will automatically reset when process passes back
through
SP1d
.
HoLd
Manual Reset. Reset by simultaneously pressing the
INDEX & DOWN ARROW keys for 3 seconds.