The RED4 is a 4-zone panel that can control gas/

electric, hydronic, electric and both conventional 

and dual fuel heat pumps with multi-stage heating 

and cooling. Low cost heat/cool thermostats can 

be used in all zones.  Optionally, a heat pump 

type thermostat can be used in Zone1.

Selecting Equipment Options

DIP switches 1, 2 and 3 select the type of HVAC system 

that is being used. the panel is factory set for a Gas-Electric 

system with Gas Fan operation.

Selecting a Gas-Electric or a Heat Pump System

the panel will operate with gas-electric, oil, hydronic and 

electric HVAC systems when DIP switch #1 is in the OFF 

position.  the  panel  will  operate  with  heat  pump  systems 

when DIP switch #1 is in the On position.

Selecting  Conventional  or  Dual  Fuel  Heat 

Pump System

When DIP switch #1 is set to select heat pump operation, 

DIP switch #2 selects a conventional heat pump or a dual 

fuel heat pump. For conventional heat pumps the panel will 

activate  stage  one  and  two  compressors  (Y1  and  Y2).  In 

third stage heating the panel will activate both compressors 

and the auxiliary heating (W2). For dual fuel heat pumps 

only  the  auxiliary  heating  (W2)  is  activated  during  third 

stage heating calls.

Selecting Gas or Electric Fan Operation

DIP switch #3 selects Gas or Electric Indoor Fan operation. 

In Gas mode the fan is not turned on by the panel during 

a  heating  call.  A  sensor  or  timer  in  the  furnace  will 

automatically turn the fan on.

In  Electric  operation,  the  panel  turns  the  fan  on  during 

heating calls. Selecting a heat pump system will automatically 

turn the fan on during heating calls. If a dual fuel heat pump 

is used, DIP switch #3 selects whether the fan is operated 

during calls using the auxiliary fuel system for heating.

In both Gas-Electric and Heat Pump Systems, the indoor fan 

is activated during cooling calls.

Selecting the Type of Thermostat in Zone1

DIP switch #4 selects the type of thermostat being used in 

Zone1. For heat pump systems, a heat pump thermostat may 

be selected for Zone1 to provide emergency heat control on 

the thermostat. When using a heat/cool thermostat for heat 

pump systems the emergency heat can be controlled by the 

Emergency  Heat  slide  switch  on  the  panel  or  an  external 

switch. Do not use the panel switch or the external switch 

DuroZone

 

RED4 - InStALLAtIOn InStRUCtIOnS PAGE 3

INSTALLATION INSTRuCTIONS

if Dip switch #4 is set to HP.

Selecting Purge Control

DIP  switch  #5  selects  whether  the  heated  or  cooled  air 

stored in the system at the end of a heating or cooling cycle 

is purged by the panel. If purge is controlled by the panel, 

the indoor fan will be operated for 90 seconds at the end of 

the call to purge the system. During purge the dampers will 

remain in the position just before purge and purged air goes 

to the last zone calling.

Selecting Capacity Limit Control

DIP switch #6 selects whether multi stage heating or cooling 

will be inhibited if only half or less of the zone(s) are calling 

for heating or cooling.

Selecting Outdoor Temperature Limit Control

DIP  switch  #7  selects  whether  multi  stage  heating  will  be 

inhibited if the outdoor temperature is above the temperature 

set on the ODt Limit potentiometer. note: For dual fuel 

heat  pumps,  switch  #7  must  be  off  (in  the  nO  position) 

if  the  heat  pump  automatically  switches  to  the  auxiliary 

heating system when the outdoor temperature drops below 

the temperature set on the ODt Limit potentiometer.

Selecting Opposite System Service

the panel will normally service heating or cooling based on 

whether there are more heating or more cooling calls. 

If Opposite System service is selected using DIP switch

#8 , the panel will switch to the opposite system after calling 

continuously for 20 minutes even though there may be only 

one zone calling for the opposite system.

RED4 InstrManual-7-1-10.indd   3

7/9/2010   5:34:40 PM

Содержание 35234

Страница 1: ... MODEL RED 4 ZONE CONTROL SYSTEM PART 35234 Corporation DuroZone is a division of DuroZone DuroZone RED4 InstrManual 7 1 10 indd 1 7 9 2010 5 34 36 PM ...

Страница 2: ...he use of external thermostats or relays Compatible with low cost heat cool thermostats Compatible with automatic change over thermostats allowing any zone to call for heating or cooling Second and third stage startup controlled by a timer located on the panel A heat pump thermostat can be used in Zone1 for emergency heat control An optional purge cycle at the end of heating or cooling call Limit ...

Страница 3: ...ng calls Selecting the Type of Thermostat in Zone1 DIP switch 4 selects the type of thermostat being used in Zone1 For heat pump systems a heat pump thermostat may be selected for Zone1 to provide emergency heat control on the thermostat When using a heat cool thermostat for heat pump systems the emergency heat can be controlled by the Emergency Heat slide switch on the panel or an external switch...

Страница 4: ...ometer the Third Stage Heating will be activated provided it is not inhibited by a limit Selecting Use of Zone4 Damper Dip switch 9 selects whether Damper4 is being used as Zone4 damper or as a fresh air damper When it is used as a fresh air damper the minutes per hour of fresh air is set on the panel Selecting One Zone Operation The panel can be operated as a single one zone system The panel will...

Страница 5: ...rst stage cooling The Cool LED will blink when the panel is calling for second stage cooling Heat LED The Heat LED will be lit continuously when the panel is calling for first stage heating The Heat LED will blink when the panel is calling for second stage heating Status LED The Status LED blinks continuously when the panel is powered and indicates the microprocessor is operating properly If the S...

Страница 6: ...inals marked OAS on the panel The Outdoor Air Temperature Sensor should be installed outside and in a shaded location Wiring Zone Thermostats All zones can use low cost heat cool thermostats as shown below Be sure to set DIP switch 4 to HC if a heat cool thermostat is used in Zone1 Wiring Dampers The panel can be used with any 24VAC power open power close or spring return damper Terminal M1 is 24V...

Страница 7: ...e furnace for fan speed RED4 Panel Wiring an HVAC System The panel can be used with a wide variety of HVAC systems Some of the more common configurations follow PLEASE NOTE The RED4 panel must be powered by an independent low voltage power supply and not by the equipment low voltage power supply RC RH O Y1 G W2 E W1 B G C Y2 REVERSING VALVE COOLING LINE VOLTAGE 24VAC R C RH RC JUMPER HEAT PUMP AIR...

Страница 8: ...te Step7 Damper3 Test Now the Damper3 will close and the indoor fan remains activated You should not feel airflow at Zone3 and the other zones should be open The DPR3 LED will be OFF Step 7 will run 1 minute Step8 Damper2 Test Now Damper2 will close and the indoor fan remains activated You should not feel airflow at Zone2 and the other zones should be open The DPR2 LED will be OFF Step 8 will take...

Страница 9: ...refrigeración se apaga El ventilador interior funcionará durante 2 minutos para purgar la refrigeración El indicador LED FAN parpadeará durante la purga y pasados 2 minutos el panel volverá al funcionamiento normal Prueba automática del contratista Versión 1 7 La prueba automática del contratista puede iniciarse en cualquier momento manteniendo pulsado el interruptor TIMER RESET durante 10 segundo...

Страница 10: ...ELECTRIC STRIP HEAT Wire the W1 B to heat pump if valve reverses in the heat mode RED4 Panel RC RH O Y1 G W2 E W1 B Y C Y2 REVERSING VALVE COOLING LINE VOLTAGE 24VAC R C RH RC JUMPER 52 Y1 FIRST STAGE SECOND STAGE Y2 R O W 24VAC DEFROST G FAN 7IRE THE 7 TO HEAT PUMP IF VALVE REVERSES IN THE HEAT MODE W2 W1 FIRST STAGE SECOND STAGE 3 4 RED4 Panel Heat Pump Cableado del sistema de calefacción ventil...

Страница 11: ... sombra Cableado de termostatos de zona Todas las zonas pueden utilizar termostatos de calor frío de bajo costo como se muestra a continuación Asegúrese de establecer el interruptor DIP nº 4 como HC si se utiliza un termostato de calor frío en la zona 1 Se puede utilizar un termostato de bomba de calefacción en la zona 1 para proporcionar control del calor de emergencia desde el termostato Asegúre...

Страница 12: ...licite refrigeración de primera etapa El indicador LED de refrigeración parpadeará cuando el panel solicite refrigeración de segunda etapa Indicador LED HEAT El indicador LED de calefacción permanecerá encendido cuando el panel solicite calefacción de primera etapa El indicador LED de calefacción parpadeará cuando el panel solicite calefacción de segunda etapa Indicador LED STATUS El indicador LED...

Страница 13: ...l interruptor DIP nº 9 selecciona si el compuerta de aire damper 4 se utiliza como el compuerta de aire damper de la zona 4 o como compuerta de aire damper de aire fresco Si se utiliza como compuerta de aire damper de aire fresco los minutos por hora de aire fresco se definen en el panel Selección de funcionamiento de una zona El panel puede funcionar como un sistema de una única zona El panel con...

Страница 14: ... auxiliar de calefacción En los sistemas de gas eléctrico y de bomba de calefacción el ventilador interno se activa durante las solicitudes de refrigeración Selección del tipo de termostato en la zona 1 El interruptor DIP nº 4 selecciona el tipo de termostato que se utiliza en la zona 1 En el caso de sistemas de bomba de calefacción se puede seleccionar una bomba de calefacción para la zona 1 para...

Страница 15: ...ni relés relays externos Compatible con termostatos de calor frío de bajo costo Compatible con termostatos de cambio automático que permiten que cualquier zona solicite calefacción o refrigeración Puesta en marcha de la segunda y la tercera etapa controlada por un temporizador situado en el panel El termostato de la bomba de calefacción puede utilizarse en la zona 1 para el control del calor de em...

Страница 16: ... MODELO RED 4 SISTEMA DE CONTROL DE ZONAS Nº DE PIEZA 35234 Corporation DuroZone es una división de DuroZone DuroZone RED4 InstrManual 7 1 10 indd 16 7 9 2010 5 35 12 PM ...

Отзывы: