background image

6

Note: Diagrams & Illustrations Are Not to Scale. 

Be careful when passing through the damper 

not  to  damage  the  flex  liner.    One  person 

should feed the liner through the chimney, 

and another person should pull the liner 

from the bottom, using the rope to guide the 

liner through to the chimney bottom. Note: If 

additional lengths of Flex Liner are needed to 

span the chimney height, use a Flex Coupler 

to connect the pieces of Flex Liner together. 

Connect the flex to the coupler by using four 

sheet metal screws for each side (see Figure 

3).  Apply high temperature sealant on the 

exhaust side.

5.  After carefully feeding the Flex Liner down 

the chimney to the bottom, form an angle to 

line up the Flex Liner with the vent opening 

on the appliance. Important: Do not let the 

Flex Liner sag below the level at which it will 

connect to the appliance or connector.  This 

could allow hot gas to become trapped and 

potentially become a fire hazard.  The Flex 

Liner path should always be sloped up toward 

the Co-Linear Cap.

Figure 2

Flex Liner

Pull-Down

Rope

Figure 3

Flex Liner

Sheet Metal 

Screws

Flex Liner

Flex Coupler

Figure 4

6. Remove the Flex Pull-Down from the Flex 

Liner and temporarily secure the Flex Liner 

at the top of the chimney. Be sure to leave 

2-3 inches of flex above the existing chimney 

to allow for connection to the Co-Linear Cap 

(see Figure 5). 

7. Repeat the above steps for the second 

length of flex.

Содержание DIRECT-TEMP Co-Linear Insert Kit

Страница 1: ...n Instructions Venting System For Direct Vent Co Linear Gas Inserts LISTED MH27778 Co Line ar Insert Kit Selkirk Direct Vent System 2022 DIRECT TEMP Form No L950_820019494 Installation Instructions 11 08 2022 Printed in U S A ...

Страница 2: ...tions of certification and may affect your homeowner s insurance and safety listing of your appliance APPLICATION This instruction applies to the Selkirk Direct Temp termination system and is intended as a supplement to the applicable Direct Temp Instructions This termination and venting system in combination with the gas appliance has been tested and listed by an accredited test agency Check the ...

Страница 3: ...3 MH27778 Note Diagrams Illustrations Are Not to Scale CERTIFICATION LABEL ...

Страница 4: ...ght as possible avoid unnecessary bending Due to possible snagging which may result in some Failure to follow the installation instructions could cause FIRE CARBON MONOXIDE POISONING OR DEATH If you are unsure of installation requirements call the Phone Number listed on the instructions or visit www selkirkcorp com WARNING Selkirk DIRECT TEMP Colinear Insert Kit provides a Vertical Cap with a buil...

Страница 5: ...nstructions surface damage caution must be observed when lowering liner lengths into the masonry flue The top section of the masonry must be water tight to prevent moisture from entering the ma sonry chimney and causing damage Consult the local building authority for more information on how to seal the damages or unused masonry section Masonry Chimney Installation 1 Measure the distance between th...

Страница 6: ...lly feeding the Flex Liner down the chimney to the bottom form an angle to line up the Flex Liner with the vent opening on the appliance Important Do not let the Flex Liner sag below the level at which it will connect to the appliance or connector This could allow hot gas to become trapped and potentially become a fire hazard The Flex Liner path should always be sloped up toward the Co Linear Cap ...

Страница 7: ...o Linear High Wind Cap Baseplate Sheet Metal Screws Figure 7 10 Apply a bead of silicone sealant to the top of the masonry chimney prior to securing the baseplate of the Co Linear High Wind Cap to the masonry chimney Secure Co Linear High Wind Cap to masonry chimney with suitable fasteners one at each corners and cover the heads with silicone sealant Figures 6 7 11 Connect both of the flex directl...

Страница 8: ...ppear as rust spots or streaks and in extreme cases holes These compo nents should immediately be replaced 2 Remove the cap and remove any bird nests or other foreign material 3 Check for evidences of excessive con densate such as water droplets forming in the liners and subsequently dripping out at joints Continuous condensate can cause corrosion of caps liners and fittings It may be caused by ha...

Страница 9: ...tion pour les encastrables colinéaire à gaz d évacuation directe Kit colinéair e pour encastrab le Système d évacuation directe de Selkirk HOMOLOGUÉ MH27778 2022 DIRECT TEMP No Formulaire L950_820019494 Instructions d installation 11 08 2022 Imprimé aux É U ...

Страница 10: ...eut affecter votre assurance d habitation et la conformité de votre appareil aux normes de sécurité Ces directives s applique au système de terminaison Selkirk Direct Temp et destinée à compléter les instructions Direct Temp correspondantes Ce système de terminaison et d évacuation en combinaison avec l appareil à gaz a été testé et répertorié par une agence de test accréditée Vérifiez la plaque s...

Страница 11: ...3 MH27778 Note Les schémas et illustrations ne sont pas à l échelle ÉTIQUETTE DE CERTIFICATION ...

Страница 12: ...ndant gardez la gaine flexible aussi droite que possible éviter les courbures inutiles Le non respect des instructions d installation pourrait provoquer UN INCENDIE UN EMPOISONNEMENT AU MONOXYDE DE CARBONE OU LA MORT Si vous avez quelques incertitudes concernant les exigences d Installations composer le numéro indiqué dans les instructions ou consulter notre site web au www selkirkcorp com AVERTIS...

Страница 13: ...areil et pourrait en conséquence être un risque d incendie Kit encastrable 3po 3po contient 2 Longueurs 3po x 35pi 1 Capuchon colinéaire 3po 3po 1 Quincaillerie vis et colliers de serrage 1 Instructions d installation Kit encastrable 4po 3po contient 1 Longueur 4po x 35pi 1 longueur 3po x 35pi 1 Capuchon colinéaire 4po 3po 1 Quincaillerie vis et colliers de serrage 1 Instructions d installation De...

Страница 14: ...la cheminée jusqu en bas former un angle pour aligner le conduit flexible avec l ouverture de l appareil Important Ne pas laisser le conduit fléchir au dessous du niveau auquel il se reliera à l appareil ou au connecteur Ceci pourrait permettre au gaz chaud d être piégé et de devenir potentiellement un risque d incendie La route du conduit flexible devrait toujours être inclinée vers le haut en di...

Страница 15: ...on à grand vent colinéaire Plaque de base Vis à métaux Schéma 7 10 Appliquez un ruban de scellant à la silicone sur le dessus de la cheminée de maçonnerie avant de sécuriser la plaque de base du capuchon à grand vent colinéaire à la cheminée Appuyer fermement sur la plaque de base et sécuriser en place à l aide d attaches appropriées une à chaque coin et couvrez les têtes avec un silicone shémas 6...

Страница 16: ...ent im médiatement être remplacées 2 Retirer le capuchon et vérifier qu il n y a au cune obstruction pouvant empêcher la sortie des gaz ou l entrée d air Enlever tous les nids d oiseau et toute autre obstruction 3 Vérifier que l intérieur du conduit flexible ne comporte aucune infiltration d eau telles que les évidences de condensation excessive s égouttant plus tard hors des joints La con densati...

Отзывы: