6
© 2011 DURAN ELECTRONICA S.L.
All rights reserved · www.duranelectronica.com
2. RELAY MODULE FUNCTIONING
The stand-alone detectors STANDGAS HC and STANDGAS HC PRO are provided of a relay output with the following
parameters:
1
Idle mode relay. It allows to select an activated relay without alarm, or a deactivated relay.
2
Relay disconnection type. It allows to select the instantaneous disconnection of the relay once alarm condition is over or
if retard selected is used.
3
Relay disconnection retard. It allows to select a retard or the instantaneous disconnection since the level selected has
disappeared as an alarm condition. It has no effect if INSTANTANEOUS was previously selected.
4
Relay alarm activation level. It allows to select, in between two, the relay actuation level, local and independently.
PROGRAMMING DEFAULT:
Activated, instantaneous –no retard-
20% LEL alarm
3. CONNECTIONS
SW1
ON position
OFF position
Programming
1
Activated
Deactivated
Initial status: Idle mode relay
1
2
Instantaneous
Retarded
Relay disconnection type
2
3
5min. retard
15m retard
Relay disconnection retard
3
4
Alarm 20% L.E.L.
Alarm 50% L.E.L.
Relay alarm activation level
4