Rear Panel Wiring 

This system setup will provide continuous power to the load and maintain the battery bank with the 
smart charger while AC power is on. There is a seamless transfer of the load to the battery when the 
AC power goes off. The LVD will disconnect the battery if the voltage drops below 10.0 VDC. The 
battery reconnects once AC power is restored and battery voltage reaches 12.5 VDC. 

20.84

mm

AC

Frame

Ground

Internet

Load

-

+

Battery

-

+

Charger

-

+

 

Figure 2: Rear panel connections of a HE1U-XX12-BBLVD-MU model. 

 

Rear Connectors 

20.84mm

+5V

G

Alarm OUT

Alarm IN

Factory
Jumper

 

Figure 3. Alarm wiring shown with factory jumper to silence alarm condition. 

B5V and Alarm IN  Output Status    Between G and Alarm OUT

 

Output Status

 

Switch Closed 

Alarm Closed 

  Alarm ON/LOW 

Shorted 

Switch Open 

Alarm Open 

  Alarm OFF/HIGH 

Open 

 

The Alarm OUT is an open drain MOSFET referenced to G. The Alarm OUT can sink a maximum 
current of 500 mA at a maximum voltage of +60 VDC. The Alarm IN, also referenced to G, is a LED 
in series with a 220 Ohm resistor internally, and can withstand 50 mA max. A factory jumper is 
installed from +5 to Alarm IN to silence the alarm. The jumper can be replaced with external wirings 
to a switch or a relay. 

 

 

Содержание HE1U Series

Страница 1: ...connect 10 0 12 5 VDC Product Dimensions 19 x 14 x 1 75 in 19 Rack Mount 1U Height Shipping Dimensions 21 x 15 x 8 in Shipping Weight 12 lbs intended to be used with external charger to support large...

Страница 2: ...Internet 6 Prerequisites 6 Determining the IP Address of the Unit 6 Using DHCP 6 Using Static IP and Network Configuration 6 Open a Web Connection to the Unit 7 Section 4 Remote Monitoring and Contro...

Страница 3: ...AC voltage power supply voltage battery voltage power supply current battery current and internal temperature as well as the ability to remotely control the power supply ON OFF state and battery conn...

Страница 4: ...Size for Current Capacity Insulated Wire Single Conductor in free air Current Level in Amperes Wire Size Requirements According to MIL W 5088B Up to 5 feet Up to 10 feet 7 AMPERES 20 AWG 18 AWG 14 AM...

Страница 5: ...model Rear Connectors 20 84mm 5V G Alarm OUT Alarm IN Factory Jumper Figure 3 Alarm wiring shown with factory jumper to silence alarm condition Between 5V and Alarm IN Output Status Between G and Ala...

Страница 6: ...ith a base address of 70 B3 D5 6B 3 Write down the IP address of the unit then proceed to the section in this manual named Open a Web Connection to the Unit Using Static IP and Network Configuration I...

Страница 7: ...n the browser see the screenshot below If you are unable to connect to the device with the browser you will need to use a terminal with a USB connection to access the device and configure the IP addre...

Страница 8: ...to remove the cover on the DuraComm unit and connect power to the battery terminals Re connect to the unit through your web browser by entering the factory supplied IP address and HTTP port see Networ...

Страница 9: ...unit Factory default username and password are as follows Admin users have full user control of the device Username admin Password admin Control users have limited control capability access all scree...

Страница 10: ...nder SNMP Traps MIB Browsers and SNMP Monitoring The MIB file for the DuraComm unit can be downloaded after you connect to it with your browser Go to the Device Setup page and log in to the unit Halfw...

Страница 11: ...com would send a text message to the Verizon user at phone number 816 555 1234 Here are the most common carrier addresses Alltel phonenumber message alltel com AT T phonenumber txt att net T Mobile p...

Страница 12: ...file size reaches 5MB Download all log files before deleting them The ability to log readings when an alarm occurs is included To turn off periodic logging enter 0 as the logging rate You can set up...

Страница 13: ...s on the left are left blank the channel will be hidden on the status screen Inputs and outputs of the DuraComm internet ready unit are wired as shown on the Sensor Setup screen The user can enter tex...

Страница 14: ...n or control user to adjust the digital outputs The digital outputs can be controlled by the buttons on the status page mobile page or via SNMP on the unit Optionally they can be automatically control...

Страница 15: ...ng and Control Status Page This screen shows the status of all analog and digital inputs A user can also download the Log file from this page AC Voltage is approximate A simplified version of the stat...

Страница 16: ...re Range 22 to 158 F 30 to 70 C Storage Temperature 40 to 185 F 40 to 85 C Safety Withstand Voltage I P O P 3 KVAC I P FG 2 KVAC O P FG 0 5 KVAC I P O P 3 KVAC I P FG 2 KVAC O P FG 0 5 KVAC I P O P 3...

Страница 17: ...uires any product needing in or out of warranty service to be returned to DuraComm All requests for warranty service must be accompanied by proof of purchase such as a bill of sale with purchase date...

Отзывы: