CONDUCTOR PRETREATMENT 
 

All kinds of copper conductors can be clamped without treatment. DO NOT solder tin stranded conductors. The solder yields 

and fractures under high pressure. The result is increased contact resistance and excessive temperature rise. Additionally, corrosion 

has been observed due to the fluxes. Notch fractures at the transition from the rigid tinned part to the flexible conductors are also 

possible. Ferrules can be used as a protection when wiring stranded conductors. Copper ferrules prevent the current transfer from 

being influenced by dissimilar metals and remove the risk of corrosion. Always use the correct tool to crimp the ferrule. 

 
RECOMMENDED COPPER WIRE SIZE FOR CURRENT CAPACITY 

 

(Insulated Wire, Single Conductor in free air) 

 

Current Level in Amperes 

<7 AMPERES 

Wire Size 

20 AWG Up to 5 feet 

18 AWG Up to 10 feet 

14  AMPERES 

18 AWG Up to 5 feet 

16 AWG Up to 10 feet 

20  AMPERES 

16 AWG Up to 5 feet 

14 AWG Up to 10 feet 

30  AMPERES 

14 AWG Up to 5 feet 

12 AWG Up to 10 feet 

40  AMPERES 

12 AWG Up to 5 feet 

10 AWG Up to 10 feet 

50  AMPERES 

10 AWG Up to 5 feet 

8  AWG Up to 10 feet 

70  AMPERES 

8 AWG Up to 5 feet 

6 AWG Up to 10 feet 

100 AMPERES 

6 AWG Up to 5 feet 

4 AWG Up to 10 feet 

 

 
 

 
 
 

 

 

 

 
 

 
 

 
 
 

 
 

 

 

 

Содержание HE1U-5012-MU

Страница 1: ...um Power continuous 750 Watts Maximum Ripple and Noise 150 mV p p max Input Voltage Switch Selectable 110 or 220 VAC Input Frequency Range 47 63 Hz Maximum AC Current 8 2 Amps 115 VAC 3 9 Amps 230 VAC...

Страница 2: ...d or SNMP Logging Rate 1 minute resolution 1 minute to 1 hour Log Download Format Comma Separated Values CSV File SNMP MIB File Download from Device Setup Page 5V Supply Maximum Current 300 mAmps INST...

Страница 3: ...oltage of 60 VDC for the revision 2 monitoring hardware included with the HE1U 5012 MU The Alarm Input Ain is referenced to G and is a LED in series with a 220 Ohm resistor internally and can withstan...

Страница 4: ...dress of 70 B3 D5 6B 3 Write down the IP address of the HE1U 5012 MU then proceed to the section in this manual named Open a Web Connection to the HE1U 5012 MU Using Static HE1U 5012 MU IP and Network...

Страница 5: ...fox internet Explorer etc and enter the IP address of the power supply on your network into the URL box on the browser see the screenshot below If you are unable to connect to the device with the brow...

Страница 6: ...ogin Enter the user name and password Factory default username and password are as follows Admin Users have full control of the device Username admin cannot be changed Password admin Control users hav...

Страница 7: ...7 of 20 December 18 2015 NETWORK SETUP...

Страница 8: ...arch for training material online under SNMP Traps MIB Browsers and SNMP Monitoring The MIB file for the HE1U 5012 MU can be downloaded from the HE1U 5012 MU after you connect to it with your browser...

Страница 9: ...9 of 20 December 18 2015 EMAIL SETUP Email Setup Enter the required email setup parameters given to you by your System Administrator You can also send a test email from this screen...

Страница 10: ...10 of 20 December 18 2015 DEVICE SETUP...

Страница 11: ...d data so that the source of the card can be identified after it removed from the HE1U 5012 MU SNMP MIB File Download The SNMP MIB File can be downloaded from this page Date and Time Settings Configur...

Страница 12: ...12 of 20 December 18 2015 SENSOR SETUP...

Страница 13: ...g alarms are set up in the Alarm Setup screen See the Alarm Setup section for more information In the HE1U 5012 MU the Digital Output 1 is an alarm output and Digital Output 2 controls the ON OFF stat...

Страница 14: ...14 of 20 December 18 2015 ALARM SETUP...

Страница 15: ...screen above Firmware 2 0 includes additional settings for alarms This screen is where thresholds are set to define alarm conditions for the analog channels You can choose to set an email notificatio...

Страница 16: ...ld be taken when changing any of these settings NOTE To hard reset your device back to factory settings press the red button on the HE1U 5012 MU PCB and hold it for more than 30 seconds You will need...

Страница 17: ...cember 18 2015 REMOTE MONITORING AND CONTROL STATUS PAGE Status screen This screen shows the status of all analog and digital inputs A user can also download the Log file from this page AC Voltage is...

Страница 18: ...ile devices Just use the same IP address and add m for example 192 168 100 220 m HE1U 5012 MU MAINTENANCE Battery The battery on the HE1U 5012 MU is used to back up the real time clock for logging pur...

Страница 19: ...Copper ferrules prevent the current transfer from being influenced by dissimilar metals and remove the risk of corrosion Always use the correct tool to crimp the ferrule RECOMMENDED COPPER WIRE SIZE...

Страница 20: ...d prior to inclusion of such changes DuraComm requires any product needing in or out of warranty service to be returned to DuraComm All requests for warranty service must be accompanied by proof of pu...

Отзывы: