background image

12

When an existing boiler is removed from a common 

venting system, the system is likely to be too large for the 

proper venting of the appliances sill connected to it.  If 

this situation occurs, the following test procedure must be 

followed:

1. 

Vent pipe must slope upward from the boiler not 

less then ¼ inch for every 1 foot (21mm/m) to vent 

terminal.

2. 

Horizontal portions of venting system shall be 

supported rigidly every 5 feet and at elbows. No portion 

of vent pipe should have dips or sags.

3. 

This boiler series is classified as a Category I. Vent 

installation shall be in accordance with "Venting of 

Equipment," of the National Fuel Gas Code, ANSI 

Z223.1/NFPA 54,  or applicable provisions of the local 

building codes.

4. 

Inspect chimney to make certain it is constructed 

according to NFPA 211. The vent or vent connector 

shall be Type B or metal pipe having resistance to heat 

and corrosion not less than that of galvanized sheet 

steel or aluminum not less than 0.016 inch thick (No. 

28 Ga).

5. 

Connect flue pipe from draft hood to chimney. Bolt or 

screw joints together to avoid sags. Flue pipe should 

not extend beyond inside wall of chimney. Do not 

install manual damper in flue pipe or reduce size of 

flue outlet except as provided by the latest revision of 

ANSI Z223.13. Protect combustible ceiling and walls 

near flue pipe with fireproof insulation. Where two or 

more appliances vent into a common flue. Consult 

NFPA 54 for common flue sizing. Alternatively, the area 

of the common flue must be at least equal to the area 

of the largest flue plus 50 percent of the area of each 

additional flue.

VENT INSTALLATION

VENT SYSTEM MODIFICATION

REMOVAL OF BOILER FROM VENTING SYSTEM

At the time of removal of an existing boiler, the following 

steps shall be followed with each appliance remaining 

connected to the common venting system placed in 

operation, while the other appliances remaining connected 

to the common venting system are not in operation.

1. 

Seal an unused opening in the common venting 

system.

2. 

Visually inspect the venting system for proper size and 

horizontal pitch and determine there is no blockage or 

restriction, leakage, corrosion and other deficiencies 

which could cause an unsafe condition.

3. 

Insofar as is practical, close all building doors and 

windows and all doors between the space in which the 

appliances remaining connected to the common venting 

system are located and other spaces of the building. 

Turn on clothes dryers and any other appliance not 

connected to the common venting system. Turn on 

any exhaust fans, such as range hoods and bathroom 

exhausts, so they operate at maximum speed. Do 

not operate a summer exhaust fan. Close fireplace 

dampers.

4. 

Place in operation the appliance being inspected. Follow 

the lighting instructions. Adjust thermostat so appliance 

will operate continuously.

5. 

Test for spillage at draft hood relief opening after 5 

minutes of main burner operation. Use the flame of a 

match or candle, or smoke from a cigarette, cigar or 

pipe.

6. 

After it has been determined each appliance remaining 

connected to common venting system properly vents 

when tested as outlined above, return doors, windows, 

exhaust fans, fireplace dampers and any other gas 

burning appliances to their previous condition of use.

7. 

Any improper operation of the common venting system 

should be corrected so the installation conforms with 

the National Fuel gas Code, ANSI Z223.1/NFPA 54.  

When re-sizing any portion of the common venting 

system, the common venting system should be re-sized 

to approach the minimum size determined using the 

appropriate tables in Chapter 13 of the National Fuel 

Gas Code, ANSI Z223.1/NFPA 54.

 WARNING

Boiler and venting installations shall be performed 

by a qualified installer in accordance with the 

appropriate manual. Installing or venting boiler 

or other gas appliance with improper methods or 

materials may result in serious injury or death due 

to fire or to asphyxiation from poisonous gases 

such as carbon monoxide with is odorless and 

invisible.

!

     

 WARNING

Do not connect boiler to any portion of mechanical 

draft system operating under positive pressure.

!

     

 P/N 

240009041

, Rev. C  [04/30/2017]

Содержание DXL-125

Страница 1: ...201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com DXL SERIES II CAST IRON GAS FIRED BOILERS FOR FORCED HOT WATER INSTALLATION OPERATION MAINTENANCE MANUAL Models DXL 50 DXL 75 DXL 100 DXL 125 DXL 150 DXL 170 DXL 200 Tested For 100 psi ASME Working Pressure ...

Страница 2: ...Gas Inlet Dimensions Pump size Supply Return Tappings A B C D E F 50 11 5 4 30 36 6 1 75 15 7 5 30 36 6 1 100 15 7 6 30 37 6 1 125 18 9 6 30 37 6 1 150 18 9 7 30 37 7 1 170 22 11 7 30 38 7 1 200 22 11 8 30 38 8 1 4 4 1 Return B C F 14 4 1 Supply 2 A E D 3 27 5 3 Figure 1 Dimensions ...

Страница 3: ...ot Use appropriate personal protection equipment to include safety glasses and gloves when installing or servicing this boiler Failure to follow these instructions could result in minor or moderate injury DANGER Indicates a hazardous situation which if not avoided WILL result in death or serious injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious in...

Страница 4: ...ler Jacket Cast Iron Boiler Battery Combination High Limit Low Water Cutoff Control Intermittent Electric Ignition Pilot System Vent Damper Relay Temperature Pressure Gauge Circulator With Return Piping To Boiler Main Gas Burners Gas Control Includes Automatic Gas Valve Gas Pressure Regulator Intermittent Pilot Safety Shutoff Pilot Flow Adjustment Pilot Filter A S M E Relief Valve Drain Valve Spil...

Страница 5: ...and right side for servicing and cleaning 8 When installed in utility room door should be wide enough to allow largest boiler part to enter or to permit replacement of another appliance such as water heater 9 FOR INSTALLATION ON NON COMBUSTIBLE FLOORS ONLY For installation on combustible flooring special base must be used See Replacement Parts Section Boiler can not be installed on carpeting Minim...

Страница 6: ...t Opening Method Provide opening commencing within 12 inches of top and second opening commencing within 12 inches of bottom enclosure Direct communication with outdoors or communicating through vertical ducts Provide minimum free area of 1 in2 per 4 Mbh of total input rating of all appliances in enclosure Communicating through horizontal ducts Provide minimum free area of 1 in2 per 2 Mbh of total...

Страница 7: ...an that of the relief valve outlet over the entire length of discharge line have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug or place any obstruction in discharge line terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing allow complete drainage of the valve and the discharge line be independently ...

Страница 8: ...ot water boilers and system must be filled with water and maintained to a minimum pressure of 12 psi 6 Bypass piping is an option which gives the ability to adjust the supply boiler water temperature to fit the system or the condition of the installation This method of piping however is not typically required for baseboard heating systems Typical installations where bypass piping is used are as fo...

Страница 9: ... For further piping information refer to AHRI Installation and Piping Guide 8 Install discharge piping from safety relief valve See Warning Page 7 SUPPLY AND RETURN PIPING Figure 5 Bypass Piping Automatic Mixing Valve Figure 6 Bypass Piping Fixed Low Temp Only Manual Mixing Valve MANUAL MIXING vALVE MANUAL MIXING VALVE WARNING Burn and scald hazard Safety relief valve could discharge steam or hot ...

Страница 10: ...10 SUPPLY AND RETURN PIPING Figure 7 Single Zone System With DHW Priority Figure 8 Multi Zone System With Circulators And DHW Priority P N 240009041 Rev C 04 30 2017 ...

Страница 11: ...PLY AND RETURN PIPING Figure 9 Multi Zone System With Zone Valves And DHW Priority With Circulator Figure 10 Multi Zone System With Zone Valves And DHW Priority With Zone Valve P N 240009041 Rev C 04 30 2017 ...

Страница 12: ...g in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condition 3 Insofar as is practical close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting syst...

Страница 13: ...nce of not less than 6 inches 152mm between Vent Damper and combustible material must be maintained Additional clearance should be allowed for service of Vent Damper 3 Vent Damper must be in the open position when appliance main burners are operating 4 Vent Damper position indicator must be in visible location following installation 5 Thermostat s heat anticipator must be adjusted to match total c...

Страница 14: ...PIPE IN CUBIC FEET OF GAS HOUR Gas Pressure 0 5 psig or less Pressure Drop 5 in w c Table 4 Pipe Sizes Length of Pipe Feet Nominal Iron Pipe Size 1 1 10 175 360 680 1400 20 120 250 465 950 30 97 200 375 770 40 82 170 320 660 60 66 138 260 530 80 57 118 220 460 100 50 103 195 400 For additional information refer to the National Fuel Gas Code Handbook Table 5 Gas Pressure Natural Gas Propane Min Sup...

Страница 15: ... Do not install a thermostat where it will be affected by drafts hot or cold pipes sunlight lighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering thermostat setting as required to start and stop the burners 5 Instructions for the final adjustment of the thermostat are packaged with the thermostat adjusting heating anticipator calibration etc WA...

Страница 16: ... Figure 14 Intermittent Electronic Ignition Control 240009076 WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life P N 240009041 Rev C 04 30 2017 ...

Страница 17: ...17 WIRING DIAGRAM INTERMITTENT IGNITION Figure 15 Intermittent Electronic Ignition Control 240009076 P N 240009041 Rev C 04 30 2017 ...

Страница 18: ...iance and to replace any part of control system and any gas control which has been under water NOTICE Before lighting any type of pilot burner standing or intermittent verify the hot water boiler and system are full of water to minimum pressure of 12 psi in the system also verify system is vented of air Set operating control of thermostat to below normal setting Refer to following appropriate ligh...

Страница 19: ... if necessary Remove vent pipe at base of chimney or flue and using a mirror check vent for obstruction and verify vent is in good working order Boiler flue gas passageways may be inspected by a light and mirror Remove burner door See Figure 17 Place trouble lamp in flue collector through draft relief opening With mirror positioned above burners flue gas passageways can be checked for soot or scal...

Страница 20: ...ure to replace cover screw after adjustment to prevent possible gas leakage See Figure 16 Page 19 Check burners and pilot for signs of corrosion rust or scale buildup Area around boiler must be kept clear and free of combustible materials gasoline and other flammable vapors and liquids Free flow of combustion and ventilating air to boiler and boiler room must not be restricted or blocked Inspect f...

Страница 21: ... inches water column from specified pressure Primary air adjustment is not necessary therefore air shutters are not furnished as standard equipment CHECK SAFETY CONTROL CIRCUIT Test ignition system safety shutoff device after placing boiler in operation 1 Pilot With main burner operating turn pilot gas adjusting screw clockwise until pilot gas is turned off Within 90 seconds main gas control close...

Страница 22: ... Feature should be turned OFF to insure boiler supplies adequate temperature to heat the indirect tank Decimal Point Indicates heat call High Temperature Limit Setting 130 220 F Factory 190 F Economy Dial OFF or LO 1 2 3 4 5 HI Jumper B Dynamic Display Water Temperature and Real Time Verification of Setting Adjustments Differentials are automatic and will vary based on control settings and boiler ...

Страница 23: ...add water until boiler has fully cooled Failure to follow these instructions could result in death or serious injury T STAT Illuminates whenever there is a call for heat from any thermostat zone device or indirect TARGET HI LIMIT Illuminates when boiler temperature has reached target temperature or high limit setting When economy feature is active the control utilizes thermal targeting technology ...

Страница 24: ...t This metal clip must be in contact with the inside of the copper well in order for control to sense presence of water Check well does not have excessive build up of heat transfer grease that may interfere with clip contacting well 2 Remove well and examine for excessive residue build up Clean and re install WARNING Burn and scald hazard Do not add water until boiler has fully cooled Failure to f...

Страница 25: ...ons Failure to do so could result in death or serious injury Energize module and listen for audible sparking noise When operating normally there should be a buzzing noise that turns on and off twice per second for duration of 1 7 seconds depending on model STEP 4 Verify pilot and main burner lightoff Initiate call for heat Turn thermostat above room temperature Ignition sequence may be delayed by ...

Страница 26: ...ee Figure 19 Page 20 Figure 20 Troubleshooting Pilot Flame Recheck ignition sequence as follows Reconnect main valve wire Adjust thermostat above room temperature Verify ignition sequence at burner If spark does not stop after pilot lights replace module P N 240009041 Rev C 04 30 2017 ...

Страница 27: ... 24 volts should be present i IF NOT source of the problem is not in damper check line voltage and 24 volt supply ii If 24 volts is present across brown and black continue to step iii iii Reconnect thermostat wires and turn up heat setting iv Check voltage across black and orange wires in Molex plug 24 volts AC should be present IF NOT source problem is not the damper If 24 volts is present contin...

Страница 28: ...O POWER Between 4 1 1 Off on limit 120VAC 2 Bad transformer 3 Loose or broken connections 4 Blown fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into receptacle 1 turn limit on 2 Replace transformer 3 Tighten repair or replace connection 4 Replace fuse or reset circuit breaker 5 Turn switch on 6 Plug harness in NO POWER Between 4 2 POWER Between 4 1 When calling for heat 1 T...

Страница 29: ...on 2 Restore to damper pipe to round verify not binding 3 Correct the condition Damper Rotates Continuously 1 Defective damper motor assembly 1 Replace damper motor assembly Note For troubleshooting only Verify damper is in open position Use service switch to keep damper in open position Place jumper between 2 3 If appliance fires remove jumper and plug receptacle back into damper controller plug ...

Страница 30: ...30 P N 240009041 Rev C 04 30 2017 NOTES ...

Страница 31: ...TU HR input____________ Installation instructions have been followed Checkout procedure and adjustments performed Maintenance and Service issues reviewed with owner maintenance person Installation booklet affixed on or adjacent to boiler Installer Company Address Phone Installer s Name Signature ...

Страница 32: ...THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases This boiler is not used for any space heating This boiler is part of a modular or multiple boiler system having a total input of 300 000 BTU hr or greater This boiler is equipped with a tankl...

Отзывы: