Evo-Lite Style CG Radiant Panels 

 

Installation Instructions 

Dunham-Bush Ltd, Downley Road, Havant, Hants PO9 2JD 

Document Ref: 

Tel: 023 9247 7700    

Email: [email protected] 

224-000-001-A 

UK:www.dunham-bush.co.uk 

Global:www.dunham-bush.com    

July 2014 

 

INSTALLER : IT IS IMPORTANT TO LIASE WITH OTHER TRADES 

WHEN  INSTALLING EVO-LITE RADIANT PANELS 

 

INTRODUCTION 

This booklet provides instructions to identify, handle, 

install and commission Dunham-Bush Evo-Lite Style 

CG radiant panels. The instructions apply to panels 

from the standard range only. Please study the 

instructions carefully before commencing any 

installation work. 

 

IDENTIFICATION 

Refer to Diagram 1. On larger or more complex 

installations, Dunham-Bush may provide a baseboard 

layout (BL) drawing which will show details of each 

panel run, dimensions and panel part numbers. If 

specified on the order, each panel will be marked with 

a unique individual stencil reference, which may also 

be shown on the BL drawing. 

 

DESCRIPTION 

Evo-Lite Style CG comprises aluminium alloy sheet 

panel bonded to an extruded aluminium channel 

profile; copper tube (carrying the hot water) is 

mechanically located inside the extruded channel with 

spring clips. Insulation is fitted to the upper side of the 

panel to prevent heat loss upwards from the panel. 

Optional accessories for hanging and pipe jointing are 

supplied loose. 

STANDARD RANGE OF PANELS AND SIZES 

Each panel type is available as two tube (2T) or four 

tube (4T) variants and are available in nine different 

panel types: 

 

EA  - standard panel 

 

EB  - end panel 

 

EC  - connection panel 

 

ED  - single (stand-alone) panel 

 

EE  - expansion panel 

 

EF 

- multi-circuit panel 

 

EG  - dummy panel 

 

EH  - flow connection panel 

 

EJ 

- return connection panel 

 

Panels are available in the following nominal lengths: 

600mm, 900mm, 1000mm, 1200mm, 1500mm, 

1800mm, 2000mm, 2100mm, 2400mm, 2500mm, 

2700mm and 3000mm 

 

Typical panel designation: 

Style CG-4T  EC1200 

 

- CG   

ceiling grid application 

 

- 4T   

four tube 

 

- EC   

connection panel 

 

- 1200  

nominal length 1200mm 

 

 

 

Diagram 1:  Evo-Lite Style CG-4T - typical panel run (2T panels similar)

 

 

Page 1 of 8 

Содержание Evo-Lite Style CG

Страница 1: ...h may also be shown on the BL drawing DESCRIPTION Evo Lite Style CG comprises aluminium alloy sheet panel bonded to an extruded aluminium channel profile copper tube carrying the hot water is mechanic...

Страница 2: ...suspected at the time of delivery Preparation Evo Lite Style CG radiant panels are intended for horizontal installation within a standard 600mm ceiling grid hence it is important to liase with other t...

Страница 3: ...Diagram 3 Typical section detail for installation Style CG 4T shown 2T similar Diagram 4 Suspension point locations for Evo Lite Style CG Page 3 of 8...

Страница 4: ...sing panel joint clips and M5 nuts provided Refer to Diagram 6 5 Expansion panels should be fitted every 6m of straight panel run and are supplied with expansion hoses fitted in place of the straight...

Страница 5: ...Diagram 6 Installation detail of Evo Lite Style CG standard joint Diagram 7 Installation detail of Evo Lite Style CG expansion joint Page 5 of 8...

Страница 6: ...s for leaks Refer to Table 2 for test and working pressures 4 Balance the water flow rate through the panel to accepted practice to achieve the specified flow rate 5 Leave this document and any layout...

Страница 7: ...el runs Refer to Diagram 2 for typical arrangements in a panel run Dunham Bush will prepare complete baseboard layout drawings for approval which can be used to co ordinate materials and installation...

Страница 8: ...WRITE THE DETAILS OF RADIANT PANELS HERE These details will be required when ordering spares for your Dunham Bush radiant panels STYLE AND No OF TUBES BL DRAWING OR ORDER No DATE OF INSTALLATION Spare...