8 Parameters
8.1 P1x General parameters
Parameter
P1x
Designation
Description
Setting / Examples
P17
Parameter record:
Record ID
This parameter indicates the
record ID defined in the parameter
record stick. This allows to distin-
guish several parameter record
versions of a customer.
0 means "No parameter record
found" or "Startup (state 2) not yet
carried out".
The behaviour is the same as de-
scribed in P16.
P18
Operating mode
PWM outputs
Using this parameter, the behav-
iour of the outputs PWM2 and
PWM3 can be changed in order to,
for ex., activate analogue outputs
correctly.
The external function activated by
PWM2 and PWM3 are defined by
the plugged-in extension module
which allows to activate each of
the two outputs by a digital signal
(PWM for fan, frequency converter,
...) or by an analogue signal with
0...10 V or 4...20 mA.
The correct setting for P18 is indicated in the following table
Setting P18
Configuration PWM2 as:
Configuration PWM3 as:
0
OFF
OFF
1
OFF
PWM signal
2
OFF
Analogue 0...10 V
3
OFF
Analogue 4...20 mA
4
PWM signal
OFF
5
PWM signal
PWM signal
6
PWM signal
Analogue 0...10 V
7
PWM signal
Analogue 4...20 mA
8
Analogue 0...10 V
OFF
9
Analogue 0...10 V
PWM signal
10
Analogue 0...10 V
Analogue 0....10 V
11
Analogue 0...10 V
Analogue 4....20 mA
12
Analogue 4...20 mA
OFF
13
Analogue 4...20 mA
PWM signal
14
Analogue 4...20 mA
Analogue 0...10 V
15
Analogue 4...20 mA
Analogue 4...20 mA
P18 Example: The extension mod-
ule MPA-EM1/3 is equipped with a
conversion from PWM2 to 0...10 V
and with a conversion from PWM3 to
4...20 mA. The correct setting results
from:
P18 = 11 ( for MPA-EM1/3)
P18 Note
If the configuration "4...20 mA" is
selected for a voltage output, this
corresponds to a voltage output of
2...10 V.
If the configuration "0...10 V" is
selected for a current output, this
corresponds to a current output of
0...20 mA.
Содержание MPA 5111