background image

2 … 4

WIRING

WARNING: Overriding the imput signal will drive the 
actuator to the mechanical end of travel. 

 

WARNING: Do not apply line voltage to terminals 
“X”, 2,3,4,7or 8 or the motor will be permanently 
damaged.

Inspect unit before installing, look for broken parts or leaks.
Use NEMA TYPE 4 compatible type connectors. 

Observe the barrier that separates the line voltage terminals 
from the low voltage which operates the actuator motor. All 
connections to the line voltage side of the barrier (L1 and L2, 
1, 5 and 6 terminals) must be made with Class 1 wiring; con-
nections to the remaining terminals can be Class 2 thermostat 
cable if desired.

Allow 6 inches (152mm) clearance above the actuator wiring 
compartment.

INSTALLATION

• Disconnect all power to the valves before wiring to
   prevent electrical shock and equipment damage.
• Do not exceed the electrical ratings given in the 
   specifications and on the actuator.

• Attach a flexible 1/2” NPT conduit to the actuator.
• Route the wires through the conduit.
• Use 14 or 16 guage wire for at least 105˚C (221˚F).
• Connect the wiring to the appropriate terminals.

Do not adjust the limit switch beyond 90° unless the standard 
slidewire has been replaced with a 180° slidewire; do not adjust 
beyond 180° for proportioning control.

In some applications, a Flame Safeguard (FSG) may have 
one or two overriding circuits.  One being a low fire purge 
start and the other a high fire pre-purge.  The function of 
the violet/white and violet wires are to provide an electrical 
connection so that the FSG can override, the temperature 
controller and drive the air damper actuator without a 4mA 
signal. If such connections are not needed in the application, 
simply tape them off, and safely stow away.

Low Voltage

FACTORY CONFIGURATION

REVEARSE CONFIGURATION

Содержание CP -9302-702

Страница 1: ...ring connections to the remaining terminals can be Class 2 thermostat cable if desired Allow 6 inches 152mm clearance above the actuator wiring compartment Installation must be done by a qualified licensed technician The system must meet all applicable codes Improper system design or setup may cause explosions property damage and injuries Disconnect all power to the valves before wiring to prevent...

Страница 2: ...electrical shock and equipment damage Do not exceed the electrical ratings given in the specifications and on the actuator Attach a flexible 1 2 NPT conduit to the actuator Route the wires through the conduit Use 14 or 16 guage wire for at least 105 C 221 F Connect the wiring to the appropriate terminals Do not adjust the limit switch beyond 90 unless the standard slidewire has been replaced with ...

Страница 3: ...a slight delay approx 3 seconds in actua tor movement when a potentiometer is adjusted Make final adjustments slowly to prevent over adjusting If adjusted properly when the unit just begins to drive it should stop within 5 degrees Over adjusting will lower the actual start point 3 With the desired current input for the minimum position applied typically 4mA adjust the zero point potentiometer so t...

Страница 4: ...tuator fails this test repeat the CP 9302 702 Adjustment section Short the Violet White wire to the Violet wire the actuator shaft should turn counterclockwise Short the Violet White wire to the Bluewire the actuator shaft should turn clockwise When you break the connection between the Violet White and Violet wires the shaft should return fully clockwise If the actuator fails this test perform Tes...

Отзывы: