12 … 20
MC • Edition 06.2020 • No
. 291 422
13 … 20
9.2 Description of installation
• Carry out the installation according to the
installation layout indicated below.
• Install the safety pressure relief valve in the
direction of flow (arrow / housing).
•
Maximum flow velocity in the stabilisation section:
≤ 30 m/s.
• SBV drain pipeline 1" pipe.
Item
Designation
1
Input side shut-off valve (e.g. ball valve or shut-off flap)
2
Filter
3
Reducing adapter
4
Input side manometer
5
Controller
6
Stabilisation section
7
SBV
8
Ball valve
9
Output side manometer
10
Pressure tap
11
Pulse tap, SAV
12
Pulse tap, controller
13
Solenoid valve
14
Compensator
• Prevent the accumulation of condensate: Lay the pulse
lines on an incline.
1
2
3
4
5
6
7
8
9
10
11
12
13
Stabilisation section
> 5 x DN
Installation layout
14