Duemmegi Domino WEBS Скачать руководство пользователя страница 2

Domino

WEBS

WEBS module has been developed to be used in associa-
tion with DFCP 

Domino

 bus controller, which does not re-

quire any configuration procedure.
As said above, WEBS module can be used in two ways, as 
bridge   (interface   between   DFCP   and   Ethernet)   or   Web-
Server.

WEBS: bridge mode

By means of the bridge operating mode, it is possible to 
make each operation allowed by the programming and di-
agnostics Tools (BDGraph, DCP IDE). It is possible to use 
these tools through the local network (LAN) or through In-
ternet (but in this case a VPN has to be enabled, or anyway 
the router must be set in a proper way) after having entered 
the IP address assigned to WEBS in the opening communi-
cation window used for the connection; in this way it will be 
possible to interact with  

Domino

 

system from any location 

in the world (see “Configuration and setting up”).

The bridge modality is MONO-CLIENT, therefore WEBS al-
lows the access to only one user at a time (although at the 
same time with Web-Server users).

WEBS: Web-Server mode

By   means   of   this   modality   it   is   possible   to   upload   into 
WEBS a series of customized WEB pages that have been 
created through the proper Tool BDGraph upgraded to the 
latest available version. Through this modality, WEBS mod-
ule allows the interfacing to a common Web-browser (Fire-
Fox, Internet Explorer, etc.); to navigate across the WEB 
pages,   a   password   will     be   required   (even   if   this   is 
optional). The pages loaded by the browser and stored in-
side the WEBS memory, must be created and customized 
according to the plant and to the user's requirement. About 
the development of these pages, see the “Graphical Maps” 
manual.
Web-Server modality is MULTI-CLIENT; it is possible the 
simultaneous access to a maximum of 4 users (plus one 
user in bridge mode).
It is also possible to use 5 different login/passwords, each 
one with its own credentials; it is possible to set username 
and password for an Admin user and 4 different usernames 

and passwords for the other users. It is possible to differen-
tiate, in this way, the maps for each user and therefore the 
controls that each user can perform.

LEDs meaning

Three LEDs (green, red and yellow) on the front panel of 
WEBS show the operating status of WEBS module. The 
green LED shows the power on condition; the red LED fea-
tures the function of System LED (SYS) and it offers a visu-
al signaling and flashing with different duration depending 
on the module operating status; the next table lists these 
modes:

Red LED

On [sec]

Off [sec]

DFCP Connected

0.1

1.5

DFCP Not connected 

0.9

0.1

Wrong MAC address

Fisso

----------

SD-Card not present

0.5

0.5

Reset in progress

0.1

0.1

If a polling is running trough the bridge mode, the flashing 
of red LED is fast and irregular. In the case of firmware up-
grading, the red LED flashing with “dimming” effect.

The  yellow   LED   (SD)  shows   the   access  to   the  SD-card 
memory and it flashes in irregular mode when a client is 
connected in Web-Server mode.

Reset button

A little hole on the front panel allows the access to the Re-
set button; this button must be used only in the case of ef-
fective needing and it has the following functions:

Reset of the module:

 while the module is powered, push 

and   hold   down   the  button;   when   the   Red   LED  starts  to 
flash quickly (after 2 seconds about) release the button.

Restoring   of   default   parameters

:   while   the   module   is 

powered, push and hold down the button; after 2 seconds 
about the Red LED starts to flash quickly. The flashing con-
tinues  for  3  seconds  about,  after  that   the  flashing  slows 
down; after further 10 seconds, the Red LED return to flash 
quickly. At this time release the button and the default pa-
rameters (IP address, password, etc.) will be restored.

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.2 October 2012

Page 2 of 7

HOME AND BUILDING AUTOMATION

Содержание Domino WEBS

Страница 1: ...een LED is on when the module is supplied while the yellow and the red LEDs report more complex information for more details see the LEDs mean ing paragraph A little hole on the front panel allows acc...

Страница 2: ...passwords each one with its own credentials it is possible to set username and password for an Admin user and 4 different usernames and passwords for the other users It is possible to differen tiate i...

Страница 3: ...to login of each user in the event of a LAN connection in practice for which the user has enabled the Auto Login when connected to the LAN will no longer provide the login credentials How ever using a...

Страница 4: ...ual it is necessary to enter in the address bar of the browser the following as suming to have assigned the IP address 192 168 1 253 to WEBS module http 192 168 1 253 webupload htm The upload page loo...

Страница 5: ...and the connected unit The related screen shot is the follow ing WARNING the access to diagnostic page is granted only to the Administrator Logout To close the connection with WEBS module however op t...

Страница 6: ...ed into WEBS module Select Communication and the Program in this way the following window will be shown The ID Ver button allows to visualize the current ver sion of the firmware uploaded in the WEBS...

Страница 7: ...specific data sheet of the product and according to the applicable standards All the relevant safety regulations e g accident prevention regula tions law on technical work equipment must also be obser...

Отзывы: