Domino

WEBS

WEBS: interface module between DFCP 
controller and Ethernet network with 
Web-Server function

WEBS module has been developed to be used in all appli-
cations of 

Domino

 system where it is required to control the 

domotic system through an Intranet or Internet connection, 
without difficult configuration procedures; for this kind of ap-
plications, in association with the specific program for the 
development   of   graphical   maps,   WEBS   module   is   very 
user-friendly.

To  use  WEBS  module,  

BDGraph  upgraded  to  the  latest  

available version 

is required; this can be freely downloaded 

from the website  www.duemmegi.it. 

WEBS requires DFCP 

controller   with   firmware   upgraded   to   the   latest   available 
version (main microcontroller)

.

WEBS   module   can   be   used   in   two   different   operating 
modes: in the first one it acts as a “bridge” between a local 
Ethernet network and 

Domino

 system, while in the second 

operating mode it can be used as WEB-Server, with web 
pages that can be created by the user.

WEBS   module   allows   to   manage   any  

Domino

  bus   vari-

ables, like:

input status

status and command of real outputs

status and command of virtual points

registers

system clock

WEBS module has a 2-way terminal block for the connec-
tion to power-supply in the range 9 to 24V=  (ter 
and -). On the opposite side, the module features an Ether-
net connector and a 10-way connector allowing the con-
nection to DFCP controller by means of the provided flat 
cable. Three LEDs on the front panel show the operating 
status of the module: the green LED is on when the module 
is supplied, while the yellow and the red LEDs report more 
complex information (for more details see the “LEDs mean-
ing” paragraph).
A little hole on the front panel allows accessing to the Re-
set   button;   for   more   details   see   the   related   paragraph. 
WEBS module is housed in a 3M DIN standard module.

The   development   of   the   maps   to   be   loaded   into   WEBS 
module is supported by the specific tool named BDGraph; 
for details about the development of maps, see the related 
manual “Graphical Maps”.

WARNING:

  the   present   technical   sheet   is   applicable   to 

WEBS  

module   with   firmware   upgraded   to   the   latest 

available release.

NOTE:

  the   WEBS   module   can   be   used   in   Domino   and 

Contatto plants, with the same firmware, because it is able  
to  automatically recognize   if  the  module is connected  to 
DFCP or MCPXT; for the Domino case, refer however to  
the specific technical sheet.

Module Connection

The connections for the proper operation of WEBS module 
are shown in the next schematic diagram.

+

Supply

_

/ ~

SUPPLY

BUS

+

-

+

-

DFCP

+ _

WEBS

Web Server Module

Power supply   24V=  ±25% / 55mA

Eth

DEVICE

ON

SYS

SD

DUEMMEGI

MILANO-ITALY

As shown before, WEBS module must be connected to  a 
dc power supply in the range 9 to 24V. After that it is nec-
essary to connect the module to the Ethernet network and 
to 

Domino

 DFCP controller; in this way WEBS module will 

be full operating.

WARNING:

  for   the   connection   to   an   Ethernet   HUB,   a  

straight cable category 5 must be used, whereas for the di-
rect   connection   to   a   PC   a   cross   cable   is   needed   (both  
these cables are not provided).

Operation

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.2 October 2012

Page 1 of 7

HOME AND BUILDING AUTOMATION

Содержание Domino WEBS

Страница 1: ...een LED is on when the module is supplied while the yellow and the red LEDs report more complex information for more details see the LEDs mean ing paragraph A little hole on the front panel allows acc...

Страница 2: ...passwords each one with its own credentials it is possible to set username and password for an Admin user and 4 different usernames and passwords for the other users It is possible to differen tiate i...

Страница 3: ...to login of each user in the event of a LAN connection in practice for which the user has enabled the Auto Login when connected to the LAN will no longer provide the login credentials How ever using a...

Страница 4: ...ual it is necessary to enter in the address bar of the browser the following as suming to have assigned the IP address 192 168 1 253 to WEBS module http 192 168 1 253 webupload htm The upload page loo...

Страница 5: ...and the connected unit The related screen shot is the follow ing WARNING the access to diagnostic page is granted only to the Administrator Logout To close the connection with WEBS module however op t...

Страница 6: ...ed into WEBS module Select Communication and the Program in this way the following window will be shown The ID Ver button allows to visualize the current ver sion of the firmware uploaded in the WEBS...

Страница 7: ...specific data sheet of the product and according to the applicable standards All the relevant safety regulations e g accident prevention regula tions law on technical work equipment must also be obser...

Отзывы: